Changes for page 3.3 Control

Last modified by Admin on 2025/05/30 16:50

From version 41.1
edited by Admin
on 2025/03/27 15:34
Change comment: There is no comment for this version
To version 49.3
edited by Admin
on 2025/05/30 16:17
Change comment: There is no comment for this version

Summary

Details

Page properties
Content
... ... @@ -4,15 +4,17 @@
4 4  (% data-numbered-headings-start="3" style="--numbered-headings-start: 2;font-size: 0px;color: rgba(0, 0, 0, 0.0);margin-bottom: 0px; margin-top: 0px;" %)
5 5  == Control ==
6 6  
7 -=== General parameters ===
7 +=== Initialization ===
8 8  
9 -General parameters of BMS Main 3X are configured in the «Control → General» section:
9 +Initialization parameters of BMS Main 3X are configured in the «Control → Initialization» section:
10 10  
11 11  [[image:1734023979572-693.png||data-xwiki-image-style-alignment="center" data-xwiki-image-style-border="true" height="79" width="600"]]
12 12  
13 13  In this section:
14 14  
15 -* Initialization delay – a delay before processing functions after finishing device initialization (initialization includes current sensors calibration and battery modules search), millisecond.
15 +* Module initialization timeout – a timeout for modules to answer the requests from
16 +* Minimum number of found modules to finish initialization;
17 +* Device initialization delay after modules are initialized – a delay before processing functions after finishing device initialization (initialization includes current sensors calibration and battery modules search), millisecond.
16 16  
17 17  === Battery modules ===
18 18  
... ... @@ -176,7 +176,7 @@
176 176  
177 177  The battery charge management is configured in the "Control → Charge" section:
178 178  
179 -[[image:1742473171584-412.png||data-xwiki-image-style-alignment="center" data-xwiki-image-style-border="true" height="209" width="600"]]
181 +[[image:1744733920147-654.png||data-xwiki-image-style-alignment="center" data-xwiki-image-style-border="true" height="209" width="600"]]
180 180  
181 181  In this section:
182 182  
... ... @@ -189,7 +189,8 @@
189 189  * Allowable battery current to rejoin modules – a battery current at which joining of battery modules is permitted, A;
190 190  * Allowable voltage difference to rejoin modules – a difference between the voltage of the disconnected module and the battery voltage at which its joining is permitted, V;
191 191  * Checking voltages time – a time of checking voltages of battery modules before starting joining modules, millisecond;
192 -* Balancing modules time – a time of balancing battery modules after joining modules and before closing main charging contactor, millisecond;
194 +* Module balancing time – a time of balancing battery modules after joining modules and before closing main charging contactor, millisecond;
195 +* Interrupt balancing when modules are joined – a flag to break balancing time after all modules are joined;
193 193  * Control the precharging contactor – a flag to control the main precharging contactor;
194 194  * Canceling charging time – a delay before opening the main charging contactor, ms;
195 195  * Disconnect modules that are not ready to charge – a flag for disconnecting modules that have the “Ready to charge” signal cleared.
... ... @@ -240,7 +240,7 @@
240 240  
241 241  The battery discharge management is configured in the "Control → Discharge" section:
242 242  
243 -[[image:1742473693993-991.png||data-xwiki-image-style-alignment="center" data-xwiki-image-style-border="true" height="237" width="600"]]
246 +[[image:1744735777632-647.png||data-xwiki-image-style-alignment="center" data-xwiki-image-style-border="true" height="226" width="600"]]
244 244  
245 245  In this section:
246 246  
... ... @@ -253,7 +253,8 @@
253 253  * Allowable battery current to rejoin modules – a battery current at which joining of battery modules is permitted, A;
254 254  * Allowable voltage difference to rejoin modules – a difference between the voltage of the disconnected module and the battery voltage at which its joining is permitted, V;
255 255  * Checking voltages time – a time of checking voltages of battery modules before starting joining modules, millisecond;
256 -* Balancing modules time – a time of balancing battery modules after joining modules and before closing main discharging contactor, millisecond;
259 +* Module balancing time – a time of balancing battery modules after joining modules and before closing main discharging contactor, millisecond;
260 +* Interrupt balancing when modules are joined – a flag to break balancing time after all modules are joined;
257 257  * Control the precharging contactor – a flag to control the main precharging contactor;
258 258  * Canceling discharging time – a delay before opening the main discharging contactor, millisecond;
259 259  * Disconnect modules that are not ready to discharge – a flag for disconnecting modules that have the “Ready to discharge” signal cleared.
... ... @@ -309,9 +309,8 @@
309 309  
310 310  The charge/discharge contactor control is configured in the “Control → Charge/Discharge” section:
311 311  
316 +[[image:1744735816351-271.png||data-xwiki-image-style-alignment="center" data-xwiki-image-style-border="true" height="249" width="600"]]
312 312  
313 -[[image:1742475800208-207.png||data-xwiki-image-style-alignment="center" data-xwiki-image-style-border="true" height="237" width="600"]]
314 -
315 315  In this section:
316 316  
317 317  * Enable – a flag to enable battery charge/discharge controller;
... ... @@ -326,7 +326,8 @@
326 326  * Allowable battery current to rejoin modules – a battery current at which joining of battery modules is permitted, A;
327 327  * Allowable voltage difference to rejoin modules – a difference between the voltage of the disconnected module and the battery voltage at which its joining is permitted, V;
328 328  * Checking voltages time – a time of checking voltages of battery modules before starting joining modules, millisecond;
329 -* Balancing modules time – a time of balancing battery modules after joining modules and before closing main discharging contactor, millisecond;
332 +* Module balancing time – a time of balancing battery modules after joining modules and before closing main charging/discharging contactor, millisecond;
333 +* Interrupt balancing when modules are joined – a flag to break balancing time after all modules are joined;
330 330  * Control the precharging contactor – a flag to control the main precharging contactor;
331 331  * Canceling discharging time – a delay before opening the main discharging contactor, millisecond;
332 332  * Disconnect modules that are not ready to charge – a flag for disconnecting modules that have the “Ready to charge” signal cleared;
1744733920147-654.png
Author
... ... @@ -1,0 +1,1 @@
1 +XWiki.admin
Size
... ... @@ -1,0 +1,1 @@
1 +53.6 KB
Content
1744735701575-567.png
Author
... ... @@ -1,0 +1,1 @@
1 +XWiki.admin
Size
... ... @@ -1,0 +1,1 @@
1 +54.5 KB
Content
1744735777632-647.png
Author
... ... @@ -1,0 +1,1 @@
1 +XWiki.admin
Size
... ... @@ -1,0 +1,1 @@
1 +54.5 KB
Content
1744735816351-271.png
Author
... ... @@ -1,0 +1,1 @@
1 +XWiki.admin
Size
... ... @@ -1,0 +1,1 @@
1 +62.5 KB
Content