21 21  Flags for enabling battery modules are configured in the "Control → Modules → Enable (modules 1 to 8)" and "Control → Modules → Enable (modules 9 to 32)" section:
22 22  
23 -
24 -[[image:1739976358691-364.png||data-xwiki-image-style-alignment="center" data-xwiki-image-style-border="true" height="164" width="600"]]
23 +[[image:1743089636435-519.png||data-xwiki-image-style-alignment="center" data-xwiki-image-style-border="true" height="147" width="600"]]
25 25  The network addresses of the battery modules are configured in the "Control → Modules → Node IDs (modules 1 to 8)” and "Control → Modules → Node IDs (modules 9 to 32)”:
26 26  
27 -
28 28  [[image:1739976370994-390.png||data-xwiki-image-style-alignment="center" data-xwiki-image-style-border="true" height="167" width="600"]]
29 29  Each module in a battery must have a unique address. You can change the address in the battery module settings in the “Connectivity → CAN” section of the BMS Main 3 settings.
30 30  
... ... @@ -178,7 +178,7 @@
178 178  
179 179  The battery charge management is configured in the "Control → Charge" section:
180 180  
181 -[[image:1742473171584-412.png||data-xwiki-image-style-alignment="center" data-xwiki-image-style-border="true" height="209" width="600"]]
179 +[[image:1744733920147-654.png||data-xwiki-image-style-alignment="center" data-xwiki-image-style-border="true" height="209" width="600"]]
182 182  
183 183  In this section:
184 184  
... ... @@ -191,7 +191,8 @@
191 191  * Allowable battery current to rejoin modules – a battery current at which joining of battery modules is permitted, A;
192 192  * Allowable voltage difference to rejoin modules – a difference between the voltage of the disconnected module and the battery voltage at which its joining is permitted, V;
193 193  * Checking voltages time – a time of checking voltages of battery modules before starting joining modules, millisecond;
194 -* Balancing modules time – a time of balancing battery modules after joining modules and before closing main charging contactor, millisecond;
192 +* Module balancing time – a time of balancing battery modules after joining modules and before closing main charging contactor, millisecond;
193 +* Interrupt balancing when modules are joined – a flag to start closing
195 195  * Control the precharging contactor – a flag to control the main precharging contactor;
196 196  * Canceling charging time – a delay before opening the main charging contactor, ms;
197 197  * Disconnect modules that are not ready to charge – a flag for disconnecting modules that have the “Ready to charge” signal cleared.