... ... @@ -140,7 +140,7 @@
140 140  1. Checking intermodular balancing currents (the duration of the check is set in the settings). If there is no current unbalance (“Current unbalance (CH)”) or errors are ignored (“Always on”), go to step 6, otherwise open all charging contactors, and go to step 1.
141 141  1. The battery modules are joined. If the “Join to charge” request is cleared or the "Charging current unbalance" error occurs, go to step 1.
142 142  
143 -The operation of** closing main charging contactor** is described in the following steps:
143 +The operation of** closing main charging contactor** is described in the following steps:
144 144  
145 145  1. The main charging contactor “Charging” is open. When the “Charge request” is received, the voltage and current unbalance errors (“Voltage unbalance (CH)”, “Current unbalance (CH)”, “Charging current unbalance”) are cleared, and the battery modules are joined, go to step 2.
146 146  1. Closing the main precharging contactor “Precharging” (optional). Go to step 3.
... ... @@ -393,7 +393,7 @@
393 393  
394 394  To configure the parameters for counting the number of contactor openings, select the section “Control → Load open counter”:
395 395  