165 165  
166 166  The operation of** closing main charging contactor** is described in the following steps:
167 167  
168 -1. The main charging contactor “Charging” is open. When the “Charge request” is received, the voltage and current unbalance errors (“Voltage unbalance (CH)”, “Current unbalance (CH)”, “Charging current unbalance”) are cleared, and the battery modules are joined, go to step 2.
168 +1. The main charging contactor “Charging” is open. When the “Charge request” is received, there are no errors from the "Errors 1, 2 ..." bitfields, and the battery modules are joined, go to step 2.
169 169  1. Closing the main precharging contactor “Precharging” (optional). Go to step 3.
170 170  1. Closing the main charging contactor "Charging". Go to step 4.
171 171  1. The main charging contactor “Charging” is closed. If the "Charge request" is cleared, the battery modules are disconnected, or errors occur, go to step 1.
... ... @@ -227,7 +227,7 @@
227 227  
228 228  The operation of **closing main discharging contactor** is described in the following steps:
229 229  
230 -1. The main discharging contactor “Discharging” is open. When the “Discharge request” is received, the voltage and current unbalance errors (“Voltage unbalance (DCH)”, “Current unbalance (DCH)”, “Discharging current unbalance”) are cleared, and the battery modules are joined, go to step 2.
230 +1. The main discharging contactor “Discharging” is open. When the “Discharge request” is received, there are no errors from the "Errors 1, 2 ..." bitfields, and the battery modules are joined, go to step 2.
231 231  1. Closing the main precharging contactor (optional). Go to step 3.
232 232  1. Closing the main discharging contactor "Discharging". Go to step 4.
233 233  1. The main discharging contactor “Discharging” is closed. If the "Discharge request" is cleared, the battery modules are disconnected, or errors occur, go to step 1.