Changes for page 3.3 Control
Last modified by Admin on 2025/05/30 16:50
Summary
-
Page properties (1 modified, 0 added, 0 removed)
Details
- Page properties
-
- Content
-
... ... @@ -165,7 +165,7 @@ 165 165 166 166 The operation of** closing main charging contactor** is described in the following steps: 167 167 168 -1. The main charging contactor “Charging” is open. When the “Charge request” is received, the voltage and currentunbalanceerrors(“Voltageunbalance (CH)”, “Currentunbalance (CH)”,“Chargingcurrentunbalance”) are cleared, and the battery modules are joined, go to step 2.168 +1. The main charging contactor “Charging” is open. When the “Charge request” is received, there are no errors from the "Errors 1, 2 ..." bitfields, and the battery modules are joined, go to step 2. 169 169 1. Closing the main precharging contactor “Precharging” (optional). Go to step 3. 170 170 1. Closing the main charging contactor "Charging". Go to step 4. 171 171 1. The main charging contactor “Charging” is closed. If the "Charge request" is cleared, the battery modules are disconnected, or errors occur, go to step 1. ... ... @@ -227,7 +227,7 @@ 227 227 228 228 The operation of **closing main discharging contactor** is described in the following steps: 229 229 230 -1. The main discharging contactor “Discharging” is open. When the “Discharge request” is received, the voltage and currentunbalanceerrors(“Voltageunbalance (DCH)”, “Currentunbalance (DCH)”,“Dischargingcurrentunbalance”) are cleared, and the battery modules are joined, go to step 2.230 +1. The main discharging contactor “Discharging” is open. When the “Discharge request” is received, there are no errors from the "Errors 1, 2 ..." bitfields, and the battery modules are joined, go to step 2. 231 231 1. Closing the main precharging contactor (optional). Go to step 3. 232 232 1. Closing the main discharging contactor "Discharging". Go to step 4. 233 233 1. The main discharging contactor “Discharging” is closed. If the "Discharge request" is cleared, the battery modules are disconnected, or errors occur, go to step 1. ... ... @@ -355,6 +355,7 @@ 355 355 * Balance on charging – a flag to enable module balancing when the battery is charging; 356 356 * Delta voltage – a voltage difference at which the most charged modules are switched off (those modules whose voltage exceeds the minimum voltage among the modules by the “Delta voltage” value are switched off), V; 357 357 * Delta current – a current difference at which the most charged modules are switched off (those modules are switched off, the charge current of which is less than the maximum charge current among the modules by the “Delta current” value), A; 358 +* Detection time – a time for module to be estimated as unbalanced, millisecond; 358 358 * Waiting time – a time the battery modules are in the disconnected state (after this time, the modules previously disconnected during the balancing process are reconnected to the common bus), second; 359 359 * Balance on discharging – a flag to enable module balancing when the battery is discharging (if flag is enabled operation logic and settings are equal to balancing on charging); 360 360 * Required discharging current – a value of the discharge current at which the device switches off the most discharged battery modules, A.