Changes for page 3.3 Control
Last modified by Admin on 2025/05/30 16:50
Summary
-
Page properties (1 modified, 0 added, 0 removed)
Details
- Page properties
-
- Content
-
... ... @@ -10,8 +10,6 @@ 10 10 11 11 [[image:1734023979572-693.png||data-xwiki-image-style-alignment="center" data-xwiki-image-style-border="true" height="79" width="600"]] 12 12 13 -In this section: 14 - 15 15 * Initialization delay – a delay before processing functions after finishing device initialization (initialization includes current sensors calibration and battery modules search), millisecond. 16 16 17 17 === Battery modules === ... ... @@ -274,12 +274,6 @@ 274 274 * Dependent - Charge/Discharge contactor depends on Charge and Discharge algorithms and their signals and behaves as Charging contactor if "Charging" signal is set, otherwise – as Discharging contactor; 275 275 * Independent - Charge/Discharge contactor is based on its own controller. 276 276 277 -(% class="box warningmessage" %) 278 -((( 279 -**Warning!** 280 -Charge/Discharge algorithms on BMS Main 3X and on battery modules controllers must **be the same**! 281 -))) 282 - 283 283 The charging/discharging controller supports the following modes: 284 284 285 285 1. Charging/Discharging is always allowed (Always on) – the device ignores voltage and current unbalance of the battery modules and commands to close the discharging contactors of the battery modules and the main discharging contactor.