Changes for page 3.3 Control

Last modified by Admin on 2025/05/30 16:50

From version 29.1
edited by Admin
on 2025/02/28 13:04
Change comment: There is no comment for this version
To version 22.2
edited by Admin
on 2025/02/19 14:56
Change comment: There is no comment for this version

Summary

Details

Page properties
Content
... ... @@ -10,8 +10,6 @@
10 10  
11 11  [[image:1734023979572-693.png||data-xwiki-image-style-alignment="center" data-xwiki-image-style-border="true" height="79" width="600"]]
12 12  
13 -In this section:
14 -
15 15  * Initialization delay – a delay before processing functions after finishing device initialization (initialization includes current sensors calibration and battery modules search), millisecond.
16 16  
17 17  === Battery modules ===
... ... @@ -59,18 +59,18 @@
59 59  * Always on;
60 60  * Automatic, when the main contactor closes by the internal charging and discharging algorithms at the same time with Precharging, Charging, Discharging and Charging/Discharging contactors.
61 61  
62 -In “Always on” mode main contactor closes if all the following is true:
60 +In “Always on” mode, the main contactor closes if all the following is true:
63 63  
64 -* Other contactors are open;
65 -* There are no errors from the "Errors 1, 2 ..." bitfileds.
62 +* “Charging” contactor is open;
63 +* “Discharging” contactor is open;
64 +* there are no errors from the list of activated in "Errors 1,2..." bitfields.
66 66  
67 -In “Always on” mode main contactor opens if all the following is true:
66 +In “Always on” mode, the main contactor opens if “Charging” and “Discharging” contactors are open and any of the following is true:
68 68  
69 -* Other contactors are open;
70 -* There is an error from the the "Errors 1, 2 ..." bitfileds.
68 +* “Charging current present” is set;
69 +* “Discharging current present” is set;
70 +* one or more errors persistfrom the list of activated in "Errors 1,2..." bitfields..
71 71  
72 -In “Automatic” mode, the main contactor closes by internal algorithms at the same time with other contactors.
73 -
74 74  To change the parameters of the main contactor, select the "Control → Main contactor" section:
75 75  
76 76  [[image:1734024131196-608.png||data-xwiki-image-style-alignment="center" data-xwiki-image-style-border="true" height="94" width="600"]]
... ... @@ -112,10 +112,10 @@
112 112  
113 113  To change the precharge parameters, select the section “Control → Precharge”:
114 114  
115 -[[image:1739970002016-142.png||data-xwiki-image-style-alignment="center" data-xwiki-image-style-border="true" height="119" width="600"]]
116 -
117 117  In this section:
118 118  
115 +[[image:1739970002016-142.png||data-xwiki-image-style-alignment="center" data-xwiki-image-style-border="true" height="119" width="600"]]
116 +
119 119  * Precharge current threshold to close the discharging contactor – a current value to ensure that precharge process has finished and it is allowed to close the discharging contactor, A;
120 120  * Check voltages before and after contactors to finish precharging – a flag to check the voltages before and after contactors to ensure that precharge process has finished and it is allowed to close the discharging contactor;
121 121  * Minimum voltage difference before and after contactors to finish precharging – a minimum voltage difference before and after contactors to ensure precharge process finished, V;
... ... @@ -274,12 +274,6 @@
274 274  * Dependent - Charge/Discharge contactor depends on Charge and Discharge algorithms and their signals and behaves as Charging contactor if "Charging" signal is set, otherwise – as Discharging contactor;
275 275  * Independent - Charge/Discharge contactor is based on its own controller.
276 276  
277 -(% class="box warningmessage" %)
278 -(((
279 -**Warning!**
280 -Charge/Discharge algorithms on BMS Main 3X and on battery modules controllers must **be the same**!
281 -)))
282 -
283 283  The charging/discharging controller supports the following modes:
284 284  
285 285  1. Charging/Discharging is always allowed (Always on) – the device ignores voltage and current unbalance of the battery modules and commands to close the discharging contactors of the battery modules and the main discharging contactor.
... ... @@ -312,9 +312,6 @@
312 312  In this section:
313 313  
314 314  * Enable – a flag to enable battery charge/discharge controller;
315 -* Mode:
316 -** Dependent - Charge/Discharge contactor depends on Charge and Discharge algorithms and their signals;
317 -** Independent - Charge/Discharge contactor is based on its own controller.
318 318  * Algorithm:
319 319  ** Always on – discharging is always allowed;
320 320  ** Balanced – discharging is allowed provided that all battery modules are balanced;
1739977307594-438.png
Author
... ... @@ -1,1 +1,0 @@
1 -XWiki.admin
Size
... ... @@ -1,1 +1,0 @@
1 -39.2 KB
Content