Changes for page 3.3 Control

Last modified by Admin on 2025/05/30 16:50

From version 26.2
edited by Admin
on 2025/02/19 16:26
Change comment: There is no comment for this version
To version 29.2
edited by Admin
on 2025/02/28 13:50
Change comment: There is no comment for this version

Summary

Details

Page properties
Content
... ... @@ -10,6 +10,8 @@
10 10  
11 11  [[image:1734023979572-693.png||data-xwiki-image-style-alignment="center" data-xwiki-image-style-border="true" height="79" width="600"]]
12 12  
13 +In this section:
14 +
13 13  * Initialization delay – a delay before processing functions after finishing device initialization (initialization includes current sensors calibration and battery modules search), millisecond.
14 14  
15 15  === Battery modules ===
... ... @@ -274,8 +274,8 @@
274 274  
275 275  (% class="box warningmessage" %)
276 276  (((
277 -Warning!
278 -Charge/Discharge algorithms on BMS Main 3X and on battery modules controllers must be **the same**!
279 +**Warning!**
280 +Charge/Discharge algorithms on BMS Main 3X and on battery modules controllers must **be the same**!
279 279  )))
280 280  
281 281  The charging/discharging controller supports the following modes:
... ... @@ -353,6 +353,7 @@
353 353  * Balance on charging – a flag to enable module balancing when the battery is charging;
354 354  * Delta voltage – a voltage difference at which the most charged modules are switched off (those modules whose voltage exceeds the minimum voltage among the modules by the “Delta voltage” value are switched off), V;
355 355  * Delta current – a current difference at which the most charged modules are switched off (those modules are switched off, the charge current of which is less than the maximum charge current among the modules by the “Delta current” value), A;
358 +* Detection time – a time for module to be estimated as u millisecond;
356 356  * Waiting time – a time the battery modules are in the disconnected state (after this time, the modules previously disconnected during the balancing process are reconnected to the common bus), second;
357 357  * Balance on discharging – a flag to enable module balancing when the battery is discharging (if flag is enabled operation logic and settings are equal to balancing on charging);
358 358  * Required discharging current – a value of the discharge current at which the device switches off the most discharged battery modules, A.