... ... @@ -57,18 +57,18 @@
57 57  * Always on;
58 58  * Automatic, when the main contactor closes by the internal charging and discharging algorithms at the same time with Precharging, Charging, Discharging and Charging/Discharging contactors.
59 59  
60 -In “Always on” mode main contactor closes if all the following is true:
60 +In “Always on” mode, the main contactor closes if all the following is true:
61 61  
62 -* Other contactors are open;
63 -* There are no errors from the "Errors 1, 2 ..." bitfileds.
62 +* “Charging” contactor is open;
63 +* “Discharging” contactor is open;
64 +* there are no errors.
64 64  
65 -In “Always on” mode main contactor opens if all the following is true:
66 +In “Always on” mode, the main contactor opens if “Charging” and “Discharging” contactors are open and any of the following is true:
66 66  
67 -* Other contactors are open;
68 -* There is an error from the the "Errors 1, 2 ..." bitfileds.
68 +* “Charging current present” is set;
69 +* “Discharging current present” is set;
70 +* one or more errors persist.
69 69  
70 -In “Automatic” mode, the main contactor closes by internal algorithms at the same time with other contactors.
71 -
72 72  To change the parameters of the main contactor, select the "Control → Main contactor" section:
73 73  
74 74  [[image:1734024131196-608.png||data-xwiki-image-style-alignment="center" data-xwiki-image-style-border="true" height="94" width="600"]]