Changes for page 3.3 Control
Last modified by Admin on 2025/05/30 16:50
Summary
-
Page properties (1 modified, 0 added, 0 removed)
Details
- Page properties
-
- Content
-
... ... @@ -118,7 +118,7 @@ 118 118 * Check voltages before and after contactors to finish precharging – a flag to check the voltages before and after contactors to ensure that precharge process has finished and it is allowed to close the discharging contactor; 119 119 * Minimum voltage difference before and after contactors to finish precharging – a minimum voltage difference before and after contactors to ensure precharge process finished, V; 120 120 * Number of precharging attempts – maximum number of precharging attempts before setting the "Precharge error"; 121 -* Delay before current measurement – a delay before first current measurement 121 +* Delay before current measurement – a delay before first current measurement after closing precharge, millisecond; 122 122 * Precharge time – a duration of closing the precharge contactor before closing the discharging contactor, millisecond; 123 123 * Relaxation between attempts – a duration between precharge attempts, millisecond; 124 124 * Check the power dissipated in the preacharge resistor - a flag to enable the calculation of power dissipated in precharge resistor;