... ... @@ -299,7 +299,7 @@
299 299  
300 300  The charge/discharge contactor control is configured in the “Control → Charge/Discharge” section:
301 301  
302 -[[image:1734089702994-738.png||data-xwiki-image-style-alignment="center" data-xwiki-image-style-border="true" height="92" width="600"]]
302 +[[image:1739292809635-913.png||data-xwiki-image-style-alignment="center" data-xwiki-image-style-border="true" height="238" width="800"]]
303 303  
304 304  In this section:
305 305  
... ... @@ -324,8 +324,8 @@
324 324  * Maximum CONTINUOUS discharge current limit – a maximum allowed continuous discharging current of all the battery, A;
325 325  * Maximum discharge current limit – a maximum allowed discharging current of all the battery, A;
326 326  * Errors 1 (2) to disconnect all battery modules – errors that cause all battery modules to be disconnected from the common bus;
327 -* Errors 1 (2) to open the discharging contactor – errors that cause the main discharging contactor "Discharging" to open,
328 -* Switch of the discharging contactor on errors without a delay – a flag that allows the main discharging contactor “Discharging” to be opened without delay if errors are detected.
327 +* Errors 1 (2) to open the charging/discharging contactor – errors that cause the main charging/discharging contactor "Discharging" to open,
328 +* Switch of the charging/discharging contactor on errors without a delay – a flag that allows the main charging/discharging contactor to be opened without delay if errors are detected.