Changes for page 3.3 Control
Last modified by Admin on 2025/05/30 16:50
Summary
-
Page properties (1 modified, 0 added, 0 removed)
Details
- Page properties
-
- Content
-
... ... @@ -299,7 +299,7 @@ 299 299 300 300 The charge/discharge contactor control is configured in the “Control → Charge/Discharge” section: 301 301 302 -[[image:173 4089702994-738.png||data-xwiki-image-style-alignment="center" data-xwiki-image-style-border="true" height="92" width="600"]]302 +[[image:1739292809635-913.png||data-xwiki-image-style-alignment="center" data-xwiki-image-style-border="true" height="238" width="800"]] 303 303 304 304 In this section: 305 305 ... ... @@ -324,8 +324,8 @@ 324 324 * Maximum CONTINUOUS discharge current limit – a maximum allowed continuous discharging current of all the battery, A; 325 325 * Maximum discharge current limit – a maximum allowed discharging current of all the battery, A; 326 326 * Errors 1 (2) to disconnect all battery modules – errors that cause all battery modules to be disconnected from the common bus; 327 -* Errors 1 (2) to open the discharging contactor – errors that cause the main discharging contactor "Discharging" to open, 328 -* Switch of the discharging contactor on errors without a delay – a flag that allows the main discharging contactor “Discharging”to be opened without delay if errors are detected.327 +* Errors 1 (2) to open the charging/discharging contactor – errors that cause the main charging/discharging contactor "Discharging" to open, 328 +* Switch of the charging/discharging contactor on errors without a delay – a flag that allows the main charging/discharging contactor to be opened without delay if errors are detected. 329 329 330 330 === Module balancing === 331 331