... ... @@ -112,7 +112,7 @@
112 112  
113 113  In this section:
114 114  
115 -[[image:1739290619354-792.png||data-xwiki-image-style-alignment="center" data-xwiki-image-style-border="true" height="155" width="800"]]
115 +[[image:1739290619354-792.png||data-xwiki-image-style-alignment="center" data-xwiki-image-style-border="true" height="117" width="600"]]
116 116  
117 117  * Precharge current threshold to close the discharging contactor – a current value to ensure that precharge process has finished and it is allowed to close the discharging contactor, A;
118 118  * Check voltages before and after contactors to finish precharging – a flag to check the voltages before and after contactors to ensure that precharge process has finished and it is allowed to close the discharging contactor;
... ... @@ -187,10 +187,10 @@
187 187  * Minimum number of modules allowed to join – a minimum number of battery modules that can be connected in parallel;
188 188  * Allowable battery current to rejoin modules – a battery current at which joining of battery modules is permitted, A;
189 189  * Allowable voltage difference to rejoin modules – a difference between the voltage of the disconnected module and the battery voltage at which its joining is permitted, V;
190 -* Checking voltages time – a time of checking voltages of battery modules, millisecond;
191 -* Balancing modules time – a time of balancing battery modules, millisecond;
192 -* Control the precharging contactor – a flag to control the main precharging contactor;
193 -* Canceling charging time – a delay before opening the main charging contactor, ms;
190 +* Checking voltages time – a time of checking voltages of battery modules before starting joining modules, millisecond;
191 +* Balancing modules time – a time of balancing battery modules b, millisecond;
192 +* Control the precharging contactor – a flag to control the precharging contactor;
193 +* Canceling charging time – a delay before opening the charging contactor, ms;
194 194  * Disconnect modules that are not ready to charge – a flag for disconnecting modules that have the “Ready to charge” signal cleared.
195 195  * Disconnect all modules if one is not ready to charge – a flag for disconnecting all modules if any of the modules have the “Ready to charge” signal cleared;
196 196  * Join modules on the “Charge request” signal – a flag to enable automatic modules joining if “Charge request” signal appears;