127 127  * Delay before clearing the "Precharge error", second;
128 128  * Lock – a flag to block the error until the device is restarted.
129 129  
130 -“Precharge error” generation conditions:
130 +“Precharge error” generation conditions if any of the following is true:
131 131  
132 -* the precharge current does not decrease during the P after "Number of precharging attempts";
133 -* voltages before and after contactors are not equal after "Number of precharging attempts";
132 +* the precharge current does not decrease during the "Precharge time" after "Number of precharging attempts";
133 +* voltages before and after contactors are not equal during the "Precharge time" after "Number of precharging attempts";
134 134  * power dissipated on the precharge resistor is above the maximum value during the “Delay before setting the 'Precharge error' when checking power” time.
135 135  