Changes for page 3.3 Control

Last modified by Admin on 2025/05/30 16:50

From version 12.20
edited by Admin
on 2025/02/11 16:41
Change comment: There is no comment for this version
To version 12.17
edited by Admin
on 2025/02/11 16:36
Change comment: There is no comment for this version

Summary

Details

Page properties
Content
... ... @@ -282,15 +282,10 @@
282 282  
283 283  The operation of the **joining battery modules** depends on the signal received:
284 284  
285 -* If "Join to charge" is received, joining procedure is done as described in [[Charge>>doc:||anchor="HCharge"]] section;
286 -* If "Join to discharge" is received, joining procedure is done as described in [[Discharge>>doc:||anchor="HDischarge"]] section;
287 -* If both signals received, "Join to charge" has a priority.
285 +* If "Join to charge" is received, joining procedure is
288 288  
289 -The operation of **closing main charging/discharging contactor **depends on the signal received:
287 +The operation of **closing main discharging contactor** is described in the following steps:
290 290  
291 -
292 -If "Charge request" is received, joining procedure is
293 -
294 294  1. The main discharging contactor “Discharging” is open. When the “Discharge request” is received, the voltage and current unbalance errors (“Voltage unbalance (DCH)”, “Current unbalance (DCH)”, “Discharging current unbalance”) are cleared, and the battery modules are joined, go to step 2.
295 295  1. Closing the main precharging contactor (optional). Go to step 3.
296 296  1. Closing the main discharging contactor "Discharging". Go to step 4.