Changes for page 3.3 Control

Last modified by Admin on 2025/05/30 16:50

From version 12.19
edited by Admin
on 2025/02/11 16:39
Change comment: There is no comment for this version
To version 12.18
edited by Admin
on 2025/02/11 16:38
Change comment: There is no comment for this version

Summary

Details

Page properties
Content
... ... @@ -282,9 +282,7 @@
282 282  
283 283  The operation of the **joining battery modules** depends on the signal received:
284 284  
285 -* If "Join to charge" is received, joining procedure is done as described in Charge section;
286 -* If "Join to discharge" is received, joining procedure is done as described in Discharge section;
287 -* If both signals received, "Join to charge" has a priority.
285 +* If "Join to charge" is received, joining procedure is
288 288  
289 289  The operation of **closing main charging/discharging contactor **depends on the signal received:
290 290