... ... @@ -282,7 +282,9 @@
282 282  
283 283  The operation of the **joining battery modules** depends on the signal received:
284 284  
285 -* If "Join to charge" is received, joining procedure is
285 +* If "Join to charge" is received, joining procedure is done as described in Charge section;
286 +* If "Join to discharge" is received, joining procedure is done as described in Discharge section;
287 +* If both signals received, "Join to charge" has a priority.