... ... @@ -284,8 +284,10 @@
284 284  
285 285  * If "Join to charge" is received, joining procedure is
286 286  
287 -The operation of **closing main discharging contactor** is described in the following steps:
287 +The operation of **closing main charging/discharging contactor **depends on the signal received:
288 288  
289 +If "Charge request" is received, joining procedure is
290 +
289 289  1. The main discharging contactor “Discharging” is open. When the “Discharge request” is received, the voltage and current unbalance errors (“Voltage unbalance (DCH)”, “Current unbalance (DCH)”, “Discharging current unbalance”) are cleared, and the battery modules are joined, go to step 2.
290 290  1. Closing the main precharging contactor (optional). Go to step 3.
291 291  1. Closing the main discharging contactor "Discharging". Go to step 4.