281 281  The device controls two processes: **joining battery modules** and **closing the main charging/discharging contactor**.
282 282  
283 +The operation of the **joining battery modules** depends on the signal received:
283 283  
284 -The operation of the **joining battery modules** is described by the following steps:
285 +* If "Join to charge" is received, joining procedure is done as described in Charge section;
286 +* If "Join to discharge" is received, joining procedure is done as described in Discharge section;
287 +* If both signals received, "Join to charge" has a priority.
285 285  
286 -1. Battery modules are disabled. When the “Join to charge” or “Join to discharge” request is received and the voltage and corresponding current unbalance errors (Voltage unbalance (DCH), Current unbalance (DCH), Discharging current unbalance) are cleared, go to step 2.
287 -1. Checking the voltage unbalance of battery modules (the duration of the check is set in the settings). If there is no imbalance or errors are ignored (“Always on” and “Partially balanced”), go to step 3, otherwise open all discharging contactors, and go to step 1.
288 -1. Closing the precharging contactors of the battery modules (optional). Go to step 4.
289 -1. Closing the discharging contactors of the battery modules. The battery modules are self-balancing. Go to step 5.
290 -1. Checking intermodular balancing currents (the duration of the check is set in the settings). If there is no current unbalance (“Current unbalance (DCH)”) or errors are ignored (“Always on”), go to step 6, otherwise open all discharging contactors, and go to step 1.
291 -1. The battery modules are joined. If the “Join to discharge” request is cleared or "Discharging current unbalance" error occurs, go to step 1.
289 +The operation of **closing main charging/discharging contactor **depends on the signal received:
292 292  
293 -The operation of **closing main discharging contactor** is described in the following steps:
291 +If "Charge request" is received, joining procedure is
294 294  
295 295  1. The main discharging contactor “Discharging” is open. When the “Discharge request” is received, the voltage and current unbalance errors (“Voltage unbalance (DCH)”, “Current unbalance (DCH)”, “Discharging current unbalance”) are cleared, and the battery modules are joined, go to step 2.
296 296  1. Closing the main precharging contactor (optional). Go to step 3.