284 284  The operation of the **joining battery modules** is described by the following steps:
285 285  
286 -1. Battery modules are disabled. When the “Join to discharge” “Join to discharge” request is received and the voltage and current unbalance errors (Voltage unbalance (DCH), Current unbalance (DCH), Discharging current unbalance) are cleared, go to step 2.
286 +1. Battery modules are disabled. When the “Join to charge” or “Join to discharge” request is received and the voltage and corresponding current unbalance errors (Voltage unbalance (DCH), Voltage unbalance (DCH), Current unbalance (DCH), Discharging current unbalance) are cleared, go to step 2.
287 287  1. Checking the voltage unbalance of battery modules (the duration of the check is set in the settings). If there is no imbalance or errors are ignored (“Always on” and “Partially balanced”), go to step 3, otherwise open all discharging contactors, and go to step 1.
288 288  1. Closing the precharging contactors of the battery modules (optional). Go to step 4.
289 289  1. Closing the discharging contactors of the battery modules. The battery modules are self-balancing. Go to step 5.