... ... @@ -41,7 +41,7 @@
41 41  * Minimal SOC – SOC of the modular battery is assumed to be the minimum SOC among the battery modules;
42 42  * Average SOC – SOC of the modular battery is taken equal to the arithmetic average of the SOC of the battery modules;
43 43  * Min-Max SOC – the battery SOC is calculated based on the minimum and maximum SOC of the modules. Final SOC will be a) 100% if any module has 100% SOC, b) 0% if any module has 0% SOC;
44 -* Max-Min SOC – the battery SOC is calculated based on the minimum and maximum SOC of the cells. Final SOC will be a) 100% if all modules have 100% SOC, b) 0% if all modules have 0% SOC;
44 +* Max-Min SOC – the battery SOC is calculated based on the minimum and maximum SOC of the modules. Final SOC will be a) 100% if all modules have 100% SOC, b) 0% if all modules have 0% SOC;
45 45  
46 46  Calculation of the battery state of health (SOH) is configured in the "Control → Calculation → Final SOH" section. The following battery SOH calculation methods are supported:
47 47  
... ... @@ -110,8 +110,9 @@
110 110  
111 111  To change the precharge parameters, select the section “Control → Precharge”:
112 112  
113 -[[image:1738080762857-975.png||data-xwiki-image-style-alignment="center" data-xwiki-image-style-border="true" height="108" width="600"]]In this section:
113 +In this section:
114 114  
115 +[[image:1739290619354-792.png||data-xwiki-image-style-alignment="center" data-xwiki-image-style-border="true" height="155" width="800"]]
115 115  
116 116  * Precharge current threshold to close the discharging contactor – a current value to ensure that precharge process has finished and it is allowed to close the discharging contactor, A;
117 117  * Check voltages before and after contactors to finish precharging – a flag to check the voltages before and after contactors to ensure that precharge process has finished and it is allowed to close the discharging contactor;
... ... @@ -124,11 +124,11 @@
124 124  * Maximum allowable power dissipated in the resistor, W;
125 125  * Delay before setting the "Precharge error" when checking power, millisecond;
126 126  * Delay before clearing the "Precharge error", second;
127 -* Lock the "Precharge error" – a flag to block the error until the device is restarted.
128 +* Lock – a flag to block the error until the device is restarted.
128 128  
129 129  “Precharge error” generation conditions:
130 130  
131 -* the precharge current does not decrease after "Number of precharging attempts";
132 +* the precharge current does not decrease during the P after "Number of precharging attempts";
132 132  * voltages before and after contactors are not equal after "Number of precharging attempts";
133 133  * power dissipated on the precharge resistor is above the maximum value during the “Delay before setting the 'Precharge error' when checking power” time.
134 134  