41 41  * Minimal SOC – SOC of the modular battery is assumed to be the minimum SOC among the battery modules;
42 42  * Average SOC – SOC of the modular battery is taken equal to the arithmetic average of the SOC of the battery modules;
43 43  * Min-Max SOC – the battery SOC is calculated based on the minimum and maximum SOC of the modules. Final SOC will be a) 100% if any module has 100% SOC, b) 0% if any module has 0% SOC;
44 -* Max-Min SOC – the battery SOC is calculated based on the minimum and maximum SOC of the cells. Final SOC will be a) 100% if all modules have 100% SOC, b) 0% if all modules have 0% SOC;
44 +* Max-Min SOC – the battery SOC is calculated based on the minimum and maximum SOC of the modules. Final SOC will be a) 100% if all modules have 100% SOC, b) 0% if all modules have 0% SOC;
45 45  
46 46  Calculation of the battery state of health (SOH) is configured in the "Control → Calculation → Final SOH" section. The following battery SOH calculation methods are supported:
47 47