Changes for page 6.2 Modbus protocol

Last modified by Admin on 2025/07/14 15:28

From version 5.5
edited by Admin
on 2025/02/04 09:38
Change comment: There is no comment for this version
To version 15.1
edited by Admin
on 2025/03/20 12:11
Change comment: There is no comment for this version

Summary

Details

Page properties
Content
... ... @@ -225,7 +225,9 @@
225 225  
226 226  bit 25 — signal “Power up”;
227 227  
228 -bits 26-31 — not used.
228 +bit 26 — signal “External 1”;
229 +
230 +bits 27-31 — not used.
229 229  )))|(% style="width:37px" %)U32
230 230  |(% style="width:73px" %)**0x200B**|(% style="width:66px" %)1|(% style="width:437px" %)(((
231 231  Discrete output signals (bitfield):
... ... @@ -298,7 +298,9 @@
298 298  
299 299  bit 18 — “Power fault”;
300 300  
301 -bits 19-31 — not used.
303 +bit 19 — “Current limit" error;
304 +
305 +bits 20-31 — not used.
302 302  )))|(% style="width:37px" %)U32
303 303  |(% style="width:73px" %)**0x2010**|(% style="width:66px" %)1|(% style="width:437px" %)Address of the BMS Logic device the parameters of which are in registers 0x2011-0x20C9|(% style="width:37px" %)U16
304 304  |(% style="width:73px" %)**0x2011**|(% style="width:66px" %)1|(% style="width:437px" %)(((
... ... @@ -454,9 +454,10 @@
454 454  === Holding registers ===
455 455  
456 456  (% style="width:617px" %)
457 -|(% style="width:71px" %)**Register address**|(% style="width:75px" %)**Number of registers**|(% style="width:469px" %)**Content**
458 -|(% style="width:71px" %)**0x4000**|(% style="width:75px" %)1|(% style="width:469px" %)Address of the BMS Logic device whose parameters should be in the input registers 0x2011-0x20C9
459 -|(% style="width:71px" %)**0x5100**|(% style="width:75px" %)1|(% style="width:469px" %)(((
461 +|(% style="width:71px" %)**Register address**|(% style="width:75px" %)**Number of registers**|(% style="width:389px" %)**Content**|(% style="width:87px" %)**Type**
462 +|(% style="width:71px" %)**0x4000**|(% style="width:75px" %)1|(% style="width:389px" %)Address of the BMS Logic device whose parameters should be in the input registers 0x2011-0x20C9|(% style="width:87px" %)U16
463 +|(% style="width:71px" %)**0x4000-0x4101**|(% style="width:75px" %)2|(% style="width:389px" %)Acknowledgment of errors. Each single bit acknowledges corresponding error (see Errors 1 bitfield at address 0x2007-0x2008)|(% style="width:87px" %)U32
464 +|(% style="width:71px" %)**0x5100**|(% style="width:75px" %)1|(% style="width:389px" %)(((
460 460  Software control of the "Battery cover" signal. Allowable values:
461 461  
462 462  0 – clear the signal;
... ... @@ -464,8 +464,8 @@
464 464  1 – set the signal;
465 465  
466 466  2-65535 – use the physical input "Battery cover".
467 -)))
468 -|(% style="width:71px" %)**0x5101**|(% style="width:75px" %)1|(% style="width:469px" %)(((
472 +)))|(% style="width:87px" %)U16
473 +|(% style="width:71px" %)**0x5101**|(% style="width:75px" %)1|(% style="width:389px" %)(((
469 469  Software control of the "Charger connected" signal. Allowable values:
470 470  
471 471  0 – clear the signal;
... ... @@ -473,8 +473,8 @@
473 473  1 – set the signal;
474 474  
475 475  2-65535 – use the physical input "Charger connected".
476 -)))
477 -|(% style="width:71px" %)**0x5102**|(% style="width:75px" %)1|(% style="width:469px" %)(((
481 +)))|(% style="width:87px" %)U16
482 +|(% style="width:71px" %)**0x5102**|(% style="width:75px" %)1|(% style="width:389px" %)(((
478 478  Software control of the "Power up/down request" signal. Allowable values:
479 479  
480 480  0 – clear the signal;
... ... @@ -482,8 +482,8 @@
482 482  1 – set the signal;
483 483  
484 484  2-65535 – use the physical input "Power down request".
485 -)))
486 -|(% style="width:71px" %)**0x5103**|(% style="width:75px" %)1|(% style="width:469px" %)(((
490 +)))|(% style="width:87px" %)U16
491 +|(% style="width:71px" %)**0x5103**|(% style="width:75px" %)1|(% style="width:389px" %)(((
487 487  Software control of the "Inhibit charging" signal. Allowable values:
488 488  
489 489  0 – clear the signal;
... ... @@ -491,8 +491,8 @@
491 491  1 – set the signal;
492 492  
493 493  2-65535 – use the physical input "Inhibit charging".
494 -)))
495 -|(% style="width:71px" %)**0x5104**|(% style="width:75px" %)1|(% style="width:469px" %)(((
499 +)))|(% style="width:87px" %)U16
500 +|(% style="width:71px" %)**0x5104**|(% style="width:75px" %)1|(% style="width:389px" %)(((
496 496  Software control of the "Inhibit discharging" signal. Allowable values:
497 497  
498 498  0 – clear the signal;
... ... @@ -500,8 +500,8 @@
500 500  1 – set the signal;
501 501  
502 502  2-65535 – use the physical input "Inhibit discharging".
503 -)))
504 -|(% style="width:71px" %)**0x5105**|(% style="width:75px" %)1|(% style="width:469px" %)(((
508 +)))|(% style="width:87px" %)U16
509 +|(% style="width:71px" %)**0x5105**|(% style="width:75px" %)1|(% style="width:389px" %)(((
505 505  Software control of the "CH contactor feedback" signal. Allowable values:
506 506  
507 507  0 – clear the signal;
... ... @@ -509,8 +509,8 @@
509 509  1 – set the signal;
510 510  
511 511  2-65535 – use the physical input "Charging contactor feedback".
512 -)))
513 -|(% style="width:71px" %)**0x5106**|(% style="width:75px" %)1|(% style="width:469px" %)(((
517 +)))|(% style="width:87px" %)U16
518 +|(% style="width:71px" %)**0x5106**|(% style="width:75px" %)1|(% style="width:389px" %)(((
514 514  Software control of the "DCH contactor feedback" signal. Allowable values:
515 515  
516 516  0 – clear the signal;
... ... @@ -518,8 +518,8 @@
518 518  1 – set the signal;
519 519  
520 520  2-65535 – use the physical input "Discharging contactor feedback".
521 -)))
522 -|(% style="width:71px" %)**0x5107**|(% style="width:75px" %)1|(% style="width:469px" %)(((
526 +)))|(% style="width:87px" %)U16
527 +|(% style="width:71px" %)**0x5107**|(% style="width:75px" %)1|(% style="width:389px" %)(((
523 523  Software control of the "Insulation status" signal. Allowable values:
524 524  
525 525  0 – clear the signal;
... ... @@ -527,8 +527,8 @@
527 527  1 – set the signal;
528 528  
529 529  2-65535 – use the physical input "Insulation status".
530 -)))
531 -|(% style="width:71px" %)**0x5108**|(% style="width:75px" %)1|(% style="width:469px" %)(((
535 +)))|(% style="width:87px" %)U16
536 +|(% style="width:71px" %)**0x5108**|(% style="width:75px" %)1|(% style="width:389px" %)(((
532 532  Software control of the "Charge request" signal. Allowable values:
533 533  
534 534  0 – clear the signal;
... ... @@ -536,8 +536,8 @@
536 536  1 – set the signal;
537 537  
538 538  2-65535 – use the physical input "Charge request".
539 -)))
540 -|(% style="width:71px" %)**0x5109**|(% style="width:75px" %)1|(% style="width:469px" %)(((
544 +)))|(% style="width:87px" %)U16
545 +|(% style="width:71px" %)**0x5109**|(% style="width:75px" %)1|(% style="width:389px" %)(((
541 541  Software control of the "Precharge request" signal. Allowable values:
542 542  
543 543  0 – clear the signal;
... ... @@ -545,8 +545,8 @@
545 545  1 – set the signal;
546 546  
547 547  2-65535 – use the physical input "Precharge request".
548 -)))
549 -|(% style="width:71px" %)**0x510A**|(% style="width:75px" %)1|(% style="width:469px" %)(((
553 +)))|(% style="width:87px" %)U16
554 +|(% style="width:71px" %)**0x510A**|(% style="width:75px" %)1|(% style="width:389px" %)(((
550 550  Software control of the "Discharge request" signal. Allowable values:
551 551  
552 552  0 – clear the signal;
... ... @@ -554,8 +554,8 @@
554 554  1 – set the signal;
555 555  
556 556  2-65535 – use the physical input "Discharge request".
557 -)))
558 -|(% style="width:71px" %)**0x510B**|(% style="width:75px" %)1|(% style="width:469px" %)(((
562 +)))|(% style="width:87px" %)U16
563 +|(% style="width:71px" %)**0x510B**|(% style="width:75px" %)1|(% style="width:389px" %)(((
559 559  Software control of the "PCH contactor feedback" signal. Allowable values:
560 560  
561 561  0 – clear the signal;
... ... @@ -563,8 +563,8 @@
563 563  1 – set the signal;
564 564  
565 565  2-65535 – use the physical input "PCH contactor feedback".
566 -)))
567 -|(% style="width:71px" %)**0x510C**|(% style="width:75px" %)1|(% style="width:469px" %)(((
571 +)))|(% style="width:87px" %)U16
572 +|(% style="width:71px" %)**0x510C**|(% style="width:75px" %)1|(% style="width:389px" %)(((
568 568  Software control of the "CH/DCH contactor feedback" signal. Allowable values:
569 569  
570 570  0 – clear the signal;
... ... @@ -572,8 +572,8 @@
572 572  1 – set the signal;
573 573  
574 574  2-65535 – use the physical input "CH/DCH contactor feedback".
575 -)))
576 -|(% style="width:71px" %)**0x510D**|(% style="width:75px" %)1|(% style="width:469px" %)(((
580 +)))|(% style="width:87px" %)U16
581 +|(% style="width:71px" %)**0x510D**|(% style="width:75px" %)1|(% style="width:389px" %)(((
577 577  Software control of the "Main contactor feedback" signal. Allowable values:
578 578  
579 579  0 – clear the signal;
... ... @@ -581,8 +581,8 @@
581 581  1 – set the signal;
582 582  
583 583  2-65535 – use the physical input "Main contactor feedback".
584 -)))
585 -|(% style="width:71px" %)**0x510E**|(% style="width:75px" %)1|(% style="width:469px" %)(((
589 +)))|(% style="width:87px" %)U16
590 +|(% style="width:71px" %)**0x510E**|(% style="width:75px" %)1|(% style="width:389px" %)(((
586 586  Software control of the "Interlock" signal. Allowable values:
587 587  
588 588  0 – clear the signal;
... ... @@ -590,8 +590,8 @@
590 590  1 – set the signal;
591 591  
592 592  2-65535 – use the physical input "Interlock".
593 -)))
594 -|(% style="width:71px" %)**0x510F**|(% style="width:75px" %)1|(% style="width:469px" %)(((
598 +)))|(% style="width:87px" %)U16
599 +|(% style="width:71px" %)**0x510F**|(% style="width:75px" %)1|(% style="width:389px" %)(((
595 595  Software control of the "Fuse 1" signal. Allowable values:
596 596  
597 597  0 – clear the signal;
... ... @@ -599,8 +599,8 @@
599 599  1 – set the signal;
600 600  
601 601  2-65535 – use the physical input "Fuse 1".
602 -)))
603 -|(% style="width:71px" %)**0x5110**|(% style="width:75px" %)1|(% style="width:469px" %)(((
607 +)))|(% style="width:87px" %)U16
608 +|(% style="width:71px" %)**0x5110**|(% style="width:75px" %)1|(% style="width:389px" %)(((
604 604  Software control of the "Fuse 2" signal. Allowable values:
605 605  
606 606  0 – clear the signal;
... ... @@ -608,8 +608,8 @@
608 608  1 – set the signal;
609 609  
610 610  2-65535 – use the physical input "Fuse 2".
611 -)))
612 -|(% style="width:71px" %)**0x5111**|(% style="width:75px" %)1|(% style="width:469px" %)(((
616 +)))|(% style="width:87px" %)U16
617 +|(% style="width:71px" %)**0x5111**|(% style="width:75px" %)1|(% style="width:389px" %)(((
613 613  Software control of the "Fuse 3" signal. Allowable values:
614 614  
615 615  0 – clear the signal;
... ... @@ -617,8 +617,8 @@
617 617  1 – set the signal;
618 618  
619 619  2-65535 – use the physical input "Fuse 3".
620 -)))
621 -|(% style="width:71px" %)**0x5112**|(% style="width:75px" %)1|(% style="width:469px" %)(((
625 +)))|(% style="width:87px" %)U16
626 +|(% style="width:71px" %)**0x5112**|(% style="width:75px" %)1|(% style="width:389px" %)(((
622 622  Software control of the "Circuit breaker status" signal. Allowable values:
623 623  
624 624  0 – clear the signal;
... ... @@ -626,8 +626,8 @@
626 626  1 – set the signal;
627 627  
628 628  2-65535 – use the physical input "Circuit breaker status".
629 -)))
630 -|(% style="width:71px" %)**0x5113**|(% style="width:75px" %)1|(% style="width:469px" %)(((
634 +)))|(% style="width:87px" %)U16
635 +|(% style="width:71px" %)**0x5113**|(% style="width:75px" %)1|(% style="width:389px" %)(((
631 631  Software control of the "Balancing request" signal. Allowable values:
632 632  
633 633  0 – clear the signal;
... ... @@ -635,8 +635,8 @@
635 635  1 – set the signal;
636 636  
637 637  2-65535 – use the physical input "Balancing request".
638 -)))
639 -|(% style="width:71px" %)**0x5114**|(% style="width:75px" %)1|(% style="width:469px" %)(((
643 +)))|(% style="width:87px" %)U16
644 +|(% style="width:71px" %)**0x5114**|(% style="width:75px" %)1|(% style="width:389px" %)(((
640 640  Software control of the "Close Main contactor" signal. Allowable values:
641 641  
642 642  0 – clear the signal;
... ... @@ -644,6 +644,15 @@
644 644  1 – set the signal;
645 645  
646 646  2-65535 – use the physical input "Close Main contactor".
647 -)))
652 +)))|(% style="width:87px" %)U16
653 +|(% style="width:71px" %)**0x5115**|(% style="width:75px" %)1|(% style="width:389px" %)(((
654 +Software control of the "Close External 1" signal. Allowable values:
648 648  
656 +0 – clear the signal;
657 +
658 +1 – set the signal;
659 +
660 +2-65535 – use the physical input "Close External 1".
661 +)))|(% style="width:87px" %)U16
662 +
649 649