Changes for page 6.2 Modbus protocol
Last modified by Admin on 2025/03/20 12:12
Summary
-
Page properties (1 modified, 0 added, 0 removed)
Details
- Page properties
-
- Content
-
... ... @@ -225,7 +225,9 @@ 225 225 226 226 bit 25 — signal “Power up”; 227 227 228 -bits 26-31 — not used. 228 +bit 26 — signal “External 1”; 229 + 230 +bits 27-31 — not used. 229 229 )))|(% style="width:37px" %)U32 230 230 |(% style="width:73px" %)**0x200B**|(% style="width:66px" %)1|(% style="width:437px" %)((( 231 231 Discrete output signals (bitfield): ... ... @@ -257,7 +257,7 @@ 257 257 258 258 bits 6-15 — not used. 259 259 )))|(% style="width:37px" %)U16 260 -|(% style="width:73px" %)**0x200E**|(% style="width:66px" %)2|(% style="width:437px" %)((( 262 +|(% style="width:73px" %)**0x200E-0x200F**|(% style="width:66px" %)2|(% style="width:437px" %)((( 261 261 Errors 2 (bitfield): 262 262 263 263 bit 0 — error "Low temperature (CH)"; ... ... @@ -298,7 +298,9 @@ 298 298 299 299 bit 18 — “Power fault”; 300 300 301 -bits 19-31 — not used. 303 +bit 19 — “Current limit" error; 304 + 305 +bits 20-31 — not used. 302 302 )))|(% style="width:37px" %)U32 303 303 |(% style="width:73px" %)**0x2010**|(% style="width:66px" %)1|(% style="width:437px" %)Address of the BMS Logic device the parameters of which are in registers 0x2011-0x20C9|(% style="width:37px" %)U16 304 304 |(% style="width:73px" %)**0x2011**|(% style="width:66px" %)1|(% style="width:437px" %)((( ... ... @@ -428,8 +428,10 @@ 428 428 |(% style="width:73px" %)**0x217D-0x217E**|(% style="width:66px" %)2|(% style="width:437px" %)Coulomb consumed by the load, A×h|(% style="width:37px" %)REAL32 429 429 |(% style="width:73px" %)**0x21B8**|(% style="width:66px" %)1|(% style="width:437px" %)Flag indicating that some cell is being balanced|(% style="width:37px" %)U16 430 430 |(% style="width:73px" %)**0x21CA-0x21CB**|(% style="width:66px" %)2|(% style="width:437px" %)Average cell voltage, V|(% style="width:37px" %)REAL32 431 -|(% style="width:73px" %)**0x2400**|(% style="width:66px" %)2|(% style="width:437px" %)Current (sensor 1, low range), A|(% style="width:37px" %)REAL32 432 -|(% style="width:73px" %)**0x2402**|(% style="width:66px" %)2|(% style="width:437px" %)Final battery current, A|(% style="width:37px" %)REAL32 435 +|(% style="width:73px" %)**0x2400-0x2401**|(% style="width:66px" %)2|(% style="width:437px" %)Current (sensor 1, low range), A|(% style="width:37px" %)REAL32 436 +|(% style="width:73px" %)((( 437 +**0x2402-0x2403** 438 +)))|(% style="width:66px" %)2|(% style="width:437px" %)Final battery current, A|(% style="width:37px" %)REAL32 433 433 |(% style="width:73px" %)**0x2410**|(% style="width:66px" %)1|(% style="width:437px" %)((( 434 434 Battery state (enumeration): 435 435 ... ... @@ -447,7 +447,7 @@ 447 447 448 448 6 – Relaxed (after discharging). 449 449 )))|(% style="width:37px" %)U16 450 -|(% style="width:73px" %)**0x2411**|(% style="width:66px" %)2|(% style="width:437px" %)Duration of the battery state (0x2410), seconds|(% style="width:37px" %)U32 456 +|(% style="width:73px" %)**0x2411-0x2412**|(% style="width:66px" %)2|(% style="width:437px" %)Duration of the battery state (0x2410), seconds|(% style="width:37px" %)U32 451 451 452 452 === Holding registers === 453 453 ... ... @@ -454,6 +454,7 @@ 454 454 (% style="width:617px" %) 455 455 |(% style="width:71px" %)**Register address**|(% style="width:75px" %)**Number of registers**|(% style="width:469px" %)**Content** 456 456 |(% style="width:71px" %)**0x4000**|(% style="width:75px" %)1|(% style="width:469px" %)Address of the BMS Logic device whose parameters should be in the input registers 0x2011-0x20C9 463 +|(% style="width:71px" %)**0x4000-0x4101**|(% style="width:75px" %)2|(% style="width:469px" %)Acknowledgment of errors. Each single bit corresponds to the error (see) 457 457 |(% style="width:71px" %)**0x5100**|(% style="width:75px" %)1|(% style="width:469px" %)((( 458 458 Software control of the "Battery cover" signal. Allowable values: 459 459 ... ... @@ -643,5 +643,14 @@ 643 643 644 644 2-65535 – use the physical input "Close Main contactor". 645 645 ))) 653 +|(% style="width:71px" %)**0x5115**|(% style="width:75px" %)1|(% style="width:469px" %)((( 654 +Software control of the "Close External 1" signal. Allowable values: 646 646 656 +0 – clear the signal; 657 + 658 +1 – set the signal; 659 + 660 +2-65535 – use the physical input "Close External 1". 661 +))) 662 + 647 647