... ... @@ -1005,7 +1005,7 @@
1005 1005  1 – set the signal;
1006 1006  
1007 1007  2-65535 – use the physical input "Circuit breaker status".
1008 -)))|(% style="width:47px" %)
1008 +)))|(% style="width:47px" %)U16
1009 1009  |(% style="width:70px" %)**0x5113**|(% style="width:66px" %)1|(% style="width:429px" %)(((
1010 1010  Software control of the "Balancing request" signal. Allowable values:
1011 1011  
... ... @@ -1014,7 +1014,7 @@
1014 1014  1 – set the signal;
1015 1015  
1016 1016  2-65535 – use the physical input "Balancing request".
1017 -)))|(% style="width:47px" %)
1017 +)))|(% style="width:47px" %)U16
1018 1018  |(% style="width:70px" %)**0x5114**|(% style="width:66px" %)1|(% style="width:429px" %)(((
1019 1019  Software control of the "Close Main contactor" signal. Allowable values:
1020 1020  
... ... @@ -1023,6 +1023,6 @@
1023 1023  1 – set the signal;
1024 1024  
1025 1025  2-65535 – use the physical input "Close Main contactor".
1026 -)))|(% style="width:47px" %)
1026 +)))|(% style="width:47px" %)U16
1027 1027  