Changes for page 6.2 Modbus protocol

Last modified by Admin on 2025/03/20 12:12

From version 16.1
edited by Admin
on 2025/03/20 12:12
Change comment: There is no comment for this version
To version 5.4
edited by Admin
on 2025/02/04 08:57
Change comment: There is no comment for this version

Summary

Details

Page properties
Content
... ... @@ -225,9 +225,7 @@
225 225  
226 226  bit 25 — signal “Power up”;
227 227  
228 -bit 26 — signal “External 1”;
229 -
230 -bits 27-31 — not used.
228 +bits 26-31 — not used.
231 231  )))|(% style="width:37px" %)U32
232 232  |(% style="width:73px" %)**0x200B**|(% style="width:66px" %)1|(% style="width:437px" %)(((
233 233  Discrete output signals (bitfield):
... ... @@ -259,7 +259,7 @@
259 259  
260 260  bits 6-15 — not used.
261 261  )))|(% style="width:37px" %)U16
262 -|(% style="width:73px" %)**0x200E-0x200F**|(% style="width:66px" %)2|(% style="width:437px" %)(((
260 +|(% style="width:73px" %)**0x200E**|(% style="width:66px" %)2|(% style="width:437px" %)(((
263 263  Errors 2 (bitfield):
264 264  
265 265  bit 0 — error "Low temperature (CH)";
... ... @@ -300,9 +300,7 @@
300 300  
301 301  bit 18 — “Power fault”;
302 302  
303 -bit 19 — “Current limit" error;
304 -
305 -bits 20-31 — not used.
301 +bits 19-31 — not used.
306 306  )))|(% style="width:37px" %)U32
307 307  |(% style="width:73px" %)**0x2010**|(% style="width:66px" %)1|(% style="width:437px" %)Address of the BMS Logic device the parameters of which are in registers 0x2011-0x20C9|(% style="width:37px" %)U16
308 308  |(% style="width:73px" %)**0x2011**|(% style="width:66px" %)1|(% style="width:437px" %)(((
... ... @@ -432,10 +432,8 @@
432 432  |(% style="width:73px" %)**0x217D-0x217E**|(% style="width:66px" %)2|(% style="width:437px" %)Coulomb consumed by the load, A×h|(% style="width:37px" %)REAL32
433 433  |(% style="width:73px" %)**0x21B8**|(% style="width:66px" %)1|(% style="width:437px" %)Flag indicating that some cell is being balanced|(% style="width:37px" %)U16
434 434  |(% style="width:73px" %)**0x21CA-0x21CB**|(% style="width:66px" %)2|(% style="width:437px" %)Average cell voltage, V|(% style="width:37px" %)REAL32
435 -|(% style="width:73px" %)**0x2400-0x2401**|(% style="width:66px" %)2|(% style="width:437px" %)Current (sensor 1, low range), A|(% style="width:37px" %)REAL32
436 -|(% style="width:73px" %)(((
437 -**0x2402-0x2403**
438 -)))|(% style="width:66px" %)2|(% style="width:437px" %)Final battery current, A|(% style="width:37px" %)REAL32
431 +|(% style="width:73px" %)**0x2400**|(% style="width:66px" %)2|(% style="width:437px" %)Current (sensor 1, low range), A|(% style="width:37px" %)REAL32
432 +|(% style="width:73px" %)**0x2402**|(% style="width:66px" %)2|(% style="width:437px" %)Final battery current, A|(% style="width:37px" %)REAL32
439 439  |(% style="width:73px" %)**0x2410**|(% style="width:66px" %)1|(% style="width:437px" %)(((
440 440  Battery state (enumeration):
441 441  
... ... @@ -453,14 +453,14 @@
453 453  
454 454  6 – Relaxed (after discharging).
455 455  )))|(% style="width:37px" %)U16
456 -|(% style="width:73px" %)**0x2411-0x2412**|(% style="width:66px" %)2|(% style="width:437px" %)Duration of the battery state (0x2410), seconds|(% style="width:37px" %)U32
450 +|(% style="width:73px" %)**0x2411**|(% style="width:66px" %)2|(% style="width:437px" %)Duration of the battery state (0x2410), seconds|(% style="width:37px" %)U32
457 457  
458 458  === Holding registers ===
459 459  
460 460  (% style="width:617px" %)
461 -|(% style="width:71px" %)**Register address**|(% style="width:75px" %)**Number of registers**|(% style="width:389px" %)**Content**|(% style="width:87px" %)**Type**
462 -|(% style="width:71px" %)**0x4000**|(% style="width:75px" %)1|(% style="width:389px" %)Address of the BMS Logic device whose parameters should be in the input registers 0x2011-0x20C9|(% style="width:87px" %)U16
463 -|(% style="width:71px" %)**0x5100**|(% style="width:75px" %)1|(% style="width:389px" %)(((
455 +|(% style="width:71px" %)**Register address**|(% style="width:75px" %)**Number of registers**|(% style="width:469px" %)**Content**
456 +|(% style="width:71px" %)**0x4000**|(% style="width:75px" %)1|(% style="width:469px" %)Address of the BMS Logic device whose parameters should be in the input registers 0x2011-0x20C9
457 +|(% style="width:71px" %)**0x5100**|(% style="width:75px" %)1|(% style="width:469px" %)(((
464 464  Software control of the "Battery cover" signal. Allowable values:
465 465  
466 466  0 – clear the signal;
... ... @@ -468,8 +468,8 @@
468 468  1 – set the signal;
469 469  
470 470  2-65535 – use the physical input "Battery cover".
471 -)))|(% style="width:87px" %)U16
472 -|(% style="width:71px" %)**0x5101**|(% style="width:75px" %)1|(% style="width:389px" %)(((
465 +)))
466 +|(% style="width:71px" %)**0x5101**|(% style="width:75px" %)1|(% style="width:469px" %)(((
473 473  Software control of the "Charger connected" signal. Allowable values:
474 474  
475 475  0 – clear the signal;
... ... @@ -477,8 +477,8 @@
477 477  1 – set the signal;
478 478  
479 479  2-65535 – use the physical input "Charger connected".
480 -)))|(% style="width:87px" %)U16
481 -|(% style="width:71px" %)**0x5102**|(% style="width:75px" %)1|(% style="width:389px" %)(((
474 +)))
475 +|(% style="width:71px" %)**0x5102**|(% style="width:75px" %)1|(% style="width:469px" %)(((
482 482  Software control of the "Power up/down request" signal. Allowable values:
483 483  
484 484  0 – clear the signal;
... ... @@ -486,8 +486,8 @@
486 486  1 – set the signal;
487 487  
488 488  2-65535 – use the physical input "Power down request".
489 -)))|(% style="width:87px" %)U16
490 -|(% style="width:71px" %)**0x5103**|(% style="width:75px" %)1|(% style="width:389px" %)(((
483 +)))
484 +|(% style="width:71px" %)**0x5103**|(% style="width:75px" %)1|(% style="width:469px" %)(((
491 491  Software control of the "Inhibit charging" signal. Allowable values:
492 492  
493 493  0 – clear the signal;
... ... @@ -495,8 +495,8 @@
495 495  1 – set the signal;
496 496  
497 497  2-65535 – use the physical input "Inhibit charging".
498 -)))|(% style="width:87px" %)U16
499 -|(% style="width:71px" %)**0x5104**|(% style="width:75px" %)1|(% style="width:389px" %)(((
492 +)))
493 +|(% style="width:71px" %)**0x5104**|(% style="width:75px" %)1|(% style="width:469px" %)(((
500 500  Software control of the "Inhibit discharging" signal. Allowable values:
501 501  
502 502  0 – clear the signal;
... ... @@ -504,8 +504,8 @@
504 504  1 – set the signal;
505 505  
506 506  2-65535 – use the physical input "Inhibit discharging".
507 -)))|(% style="width:87px" %)U16
508 -|(% style="width:71px" %)**0x5105**|(% style="width:75px" %)1|(% style="width:389px" %)(((
501 +)))
502 +|(% style="width:71px" %)**0x5105**|(% style="width:75px" %)1|(% style="width:469px" %)(((
509 509  Software control of the "CH contactor feedback" signal. Allowable values:
510 510  
511 511  0 – clear the signal;
... ... @@ -513,8 +513,8 @@
513 513  1 – set the signal;
514 514  
515 515  2-65535 – use the physical input "Charging contactor feedback".
516 -)))|(% style="width:87px" %)U16
517 -|(% style="width:71px" %)**0x5106**|(% style="width:75px" %)1|(% style="width:389px" %)(((
510 +)))
511 +|(% style="width:71px" %)**0x5106**|(% style="width:75px" %)1|(% style="width:469px" %)(((
518 518  Software control of the "DCH contactor feedback" signal. Allowable values:
519 519  
520 520  0 – clear the signal;
... ... @@ -522,8 +522,8 @@
522 522  1 – set the signal;
523 523  
524 524  2-65535 – use the physical input "Discharging contactor feedback".
525 -)))|(% style="width:87px" %)U16
526 -|(% style="width:71px" %)**0x5107**|(% style="width:75px" %)1|(% style="width:389px" %)(((
519 +)))
520 +|(% style="width:71px" %)**0x5107**|(% style="width:75px" %)1|(% style="width:469px" %)(((
527 527  Software control of the "Insulation status" signal. Allowable values:
528 528  
529 529  0 – clear the signal;
... ... @@ -531,8 +531,8 @@
531 531  1 – set the signal;
532 532  
533 533  2-65535 – use the physical input "Insulation status".
534 -)))|(% style="width:87px" %)U16
535 -|(% style="width:71px" %)**0x5108**|(% style="width:75px" %)1|(% style="width:389px" %)(((
528 +)))
529 +|(% style="width:71px" %)**0x5108**|(% style="width:75px" %)1|(% style="width:469px" %)(((
536 536  Software control of the "Charge request" signal. Allowable values:
537 537  
538 538  0 – clear the signal;
... ... @@ -540,8 +540,8 @@
540 540  1 – set the signal;
541 541  
542 542  2-65535 – use the physical input "Charge request".
543 -)))|(% style="width:87px" %)U16
544 -|(% style="width:71px" %)**0x5109**|(% style="width:75px" %)1|(% style="width:389px" %)(((
537 +)))
538 +|(% style="width:71px" %)**0x5109**|(% style="width:75px" %)1|(% style="width:469px" %)(((
545 545  Software control of the "Precharge request" signal. Allowable values:
546 546  
547 547  0 – clear the signal;
... ... @@ -549,8 +549,8 @@
549 549  1 – set the signal;
550 550  
551 551  2-65535 – use the physical input "Precharge request".
552 -)))|(% style="width:87px" %)U16
553 -|(% style="width:71px" %)**0x510A**|(% style="width:75px" %)1|(% style="width:389px" %)(((
546 +)))
547 +|(% style="width:71px" %)**0x510A**|(% style="width:75px" %)1|(% style="width:469px" %)(((
554 554  Software control of the "Discharge request" signal. Allowable values:
555 555  
556 556  0 – clear the signal;
... ... @@ -558,8 +558,8 @@
558 558  1 – set the signal;
559 559  
560 560  2-65535 – use the physical input "Discharge request".
561 -)))|(% style="width:87px" %)U16
562 -|(% style="width:71px" %)**0x510B**|(% style="width:75px" %)1|(% style="width:389px" %)(((
555 +)))
556 +|(% style="width:71px" %)**0x510B**|(% style="width:75px" %)1|(% style="width:469px" %)(((
563 563  Software control of the "PCH contactor feedback" signal. Allowable values:
564 564  
565 565  0 – clear the signal;
... ... @@ -567,8 +567,8 @@
567 567  1 – set the signal;
568 568  
569 569  2-65535 – use the physical input "PCH contactor feedback".
570 -)))|(% style="width:87px" %)U16
571 -|(% style="width:71px" %)**0x510C**|(% style="width:75px" %)1|(% style="width:389px" %)(((
564 +)))
565 +|(% style="width:71px" %)**0x510C**|(% style="width:75px" %)1|(% style="width:469px" %)(((
572 572  Software control of the "CH/DCH contactor feedback" signal. Allowable values:
573 573  
574 574  0 – clear the signal;
... ... @@ -576,8 +576,8 @@
576 576  1 – set the signal;
577 577  
578 578  2-65535 – use the physical input "CH/DCH contactor feedback".
579 -)))|(% style="width:87px" %)U16
580 -|(% style="width:71px" %)**0x510D**|(% style="width:75px" %)1|(% style="width:389px" %)(((
573 +)))
574 +|(% style="width:71px" %)**0x510D**|(% style="width:75px" %)1|(% style="width:469px" %)(((
581 581  Software control of the "Main contactor feedback" signal. Allowable values:
582 582  
583 583  0 – clear the signal;
... ... @@ -585,8 +585,8 @@
585 585  1 – set the signal;
586 586  
587 587  2-65535 – use the physical input "Main contactor feedback".
588 -)))|(% style="width:87px" %)U16
589 -|(% style="width:71px" %)**0x510E**|(% style="width:75px" %)1|(% style="width:389px" %)(((
582 +)))
583 +|(% style="width:71px" %)**0x510E**|(% style="width:75px" %)1|(% style="width:469px" %)(((
590 590  Software control of the "Interlock" signal. Allowable values:
591 591  
592 592  0 – clear the signal;
... ... @@ -594,8 +594,8 @@
594 594  1 – set the signal;
595 595  
596 596  2-65535 – use the physical input "Interlock".
597 -)))|(% style="width:87px" %)U16
598 -|(% style="width:71px" %)**0x510F**|(% style="width:75px" %)1|(% style="width:389px" %)(((
591 +)))
592 +|(% style="width:71px" %)**0x510F**|(% style="width:75px" %)1|(% style="width:469px" %)(((
599 599  Software control of the "Fuse 1" signal. Allowable values:
600 600  
601 601  0 – clear the signal;
... ... @@ -603,8 +603,8 @@
603 603  1 – set the signal;
604 604  
605 605  2-65535 – use the physical input "Fuse 1".
606 -)))|(% style="width:87px" %)U16
607 -|(% style="width:71px" %)**0x5110**|(% style="width:75px" %)1|(% style="width:389px" %)(((
600 +)))
601 +|(% style="width:71px" %)**0x5110**|(% style="width:75px" %)1|(% style="width:469px" %)(((
608 608  Software control of the "Fuse 2" signal. Allowable values:
609 609  
610 610  0 – clear the signal;
... ... @@ -612,8 +612,8 @@
612 612  1 – set the signal;
613 613  
614 614  2-65535 – use the physical input "Fuse 2".
615 -)))|(% style="width:87px" %)U16
616 -|(% style="width:71px" %)**0x5111**|(% style="width:75px" %)1|(% style="width:389px" %)(((
609 +)))
610 +|(% style="width:71px" %)**0x5111**|(% style="width:75px" %)1|(% style="width:469px" %)(((
617 617  Software control of the "Fuse 3" signal. Allowable values:
618 618  
619 619  0 – clear the signal;
... ... @@ -621,8 +621,8 @@
621 621  1 – set the signal;
622 622  
623 623  2-65535 – use the physical input "Fuse 3".
624 -)))|(% style="width:87px" %)U16
625 -|(% style="width:71px" %)**0x5112**|(% style="width:75px" %)1|(% style="width:389px" %)(((
618 +)))
619 +|(% style="width:71px" %)**0x5112**|(% style="width:75px" %)1|(% style="width:469px" %)(((
626 626  Software control of the "Circuit breaker status" signal. Allowable values:
627 627  
628 628  0 – clear the signal;
... ... @@ -630,8 +630,8 @@
630 630  1 – set the signal;
631 631  
632 632  2-65535 – use the physical input "Circuit breaker status".
633 -)))|(% style="width:87px" %)U16
634 -|(% style="width:71px" %)**0x5113**|(% style="width:75px" %)1|(% style="width:389px" %)(((
627 +)))
628 +|(% style="width:71px" %)**0x5113**|(% style="width:75px" %)1|(% style="width:469px" %)(((
635 635  Software control of the "Balancing request" signal. Allowable values:
636 636  
637 637  0 – clear the signal;
... ... @@ -639,8 +639,8 @@
639 639  1 – set the signal;
640 640  
641 641  2-65535 – use the physical input "Balancing request".
642 -)))|(% style="width:87px" %)U16
643 -|(% style="width:71px" %)**0x5114**|(% style="width:75px" %)1|(% style="width:389px" %)(((
636 +)))
637 +|(% style="width:71px" %)**0x5114**|(% style="width:75px" %)1|(% style="width:469px" %)(((
644 644  Software control of the "Close Main contactor" signal. Allowable values:
645 645  
646 646  0 – clear the signal;
... ... @@ -648,15 +648,6 @@
648 648  1 – set the signal;
649 649  
650 650  2-65535 – use the physical input "Close Main contactor".
651 -)))|(% style="width:87px" %)U16
652 -|(% style="width:71px" %)**0x5115**|(% style="width:75px" %)1|(% style="width:389px" %)(((
653 -Software control of the "Close External 1" signal. Allowable values:
645 +)))
654 654  
655 -0 – clear the signal;
656 -
657 -1 – set the signal;
658 -
659 -2-65535 – use the physical input "Close External 1".
660 -)))|(% style="width:87px" %)U16
661 -
662 662