... ... @@ -15,7 +15,7 @@
15 15  * ElectricDeviceMonitor application for Windows OS which is used for configuring the BMS Main 3 / BMS Main 3X;
16 16  * USB/CAN adapter for updating via CAN bus;
17 17  * USB-mini cable for updating via USB;
18 -* BMS Wi-Fi or BMS LANmodule installed on BMS Main 3 if updating via TCP;
18 +* BMS Wi-Fi or BMS LANmodule installed on BMS Main 3 via configuration interface by TCP;
19 19  * Firmware file (must be in .bin format).
20 20  
21 21  == Updating via bootloader ==
... ... @@ -48,7 +48,6 @@
48 48  
49 49  [[image:1735233018575-198.png||data-xwiki-image-style-alignment="center" data-xwiki-image-style-border="true" height="316" width="300"]]2.2 From the drop-down menu of the Unified bootloader window, select the method of connecting to the BMS Main 3 / BMS Main 3X and configure the connection parameters (the "Settings..." button).
50 50  
51 -
52 52  * **USB connection**: select the connection method “Serial port transport”, click the “Settings...” button. In the window that appears, select the COM port through which the PC connects to the device (the baud rate can be set to any):
53 53  
54 54  [[image:1733406142376-880.png||data-xwiki-image-style-alignment="center" data-xwiki-image-style-border="true"]]