Admin 5.1 2 = Configuration =
Admin 1.1 3
4 (% data-numbered-headings-start="4" style="--numbered-headings-start: 3;font-size: 0px;color: rgba(0, 0, 0, 0.0);margin-bottom: 0px; margin-top: 0px;" %)
5 == Protections ==
6
7 The BMS Main 3 device continuously monitors the state of the cells, the external environment and, when detecting abnormalities, protects the battery and system components from damage.
8
Admin 2.1 9 === Overcurrent ===
Admin 1.1 10
11 The BMS Main 3 device performs the overcurrent protection depending on current sensor values.
12
13 To change the overcurrent protection of the battery, select the "Protections → Overcurrent" section:
14
Admin 2.1 15 [[image:1733328382376-958.png||data-xwiki-image-style-alignment="center" data-xwiki-image-style-border="true" height="138" width="800"]]
Admin 1.1 16
17 In this section:
18
19 * Enable – a flag to enable the protection;
20 * Maximum charging current, А;
21 * Tolerant charging current, А;
22 * Maximum discharging current, А;
23 * Tolerant discharging current, А;
24 * Delay before setting the error, millisecond;
25 * Delay before clearing the error, second;
26 * Lock – a flag to block the error until the device is restarted.
27
28 As a result of operation of the overcurrent protection, the "Overcurrent" error is generated.
29
30 Error generation conditions:
31
32 * the current is positive (charging), and its modulo value is greater than the “Maximum charging current” value for the “Delay before setting the error” time;
33 * the current is negative (discharging), and its modulo value is greater than the “Maximum discharging current” value for the “Delay before setting the error” time.
34
35 Conditions for removing the error:
36
37 * the current is positive (charging) or zero, and its modulo value is less than the “Tolerant charging current” value for the “Delay before clearing the error” time;
38 * the current is negative (discharging) or zero, and its modulo value is less than the “Tolerant discharging current” value for the “Delay before clearing the error” time.
39
Admin 2.1 40 (% class="box infomessage" %)
41 (((
42 If there is the "Overcurrent" error, the **charging **and **discharging **contactors open.
43 )))
Admin 1.1 44
Admin 6.2 45 === Charge current limit ===
46
Admin 6.3 47 TBA
Admin 6.2 48
49 === Discharge current limit ===
50
Admin 6.3 51 TBA
Admin 6.2 52
Admin 2.1 53 === Undervoltage ===
Admin 1.1 54
55 The BMS Main 3 device implements battery protection from too low voltage on the cells.
56
57 To change the battery protection parameters from low voltage on the cells, select the "Protections → Undervoltage" section:
58
Admin 2.1 59 [[image:1733328382380-760.png||data-xwiki-image-style-alignment="center" data-xwiki-image-style-border="true" height="127" width="800"]]
Admin 1.1 60
61 In this section:
62
63 * Enable – a flag to enable the protection;
64 * Minimum cell voltage, V;
65 * Tolerant cell voltage, V;
66 * Delay before setting the error, millisecond;
67 * Delay before clearing the error, second;
68 * Lock – a flag to block the error until the device is restarted.
69
70 As a result of the operation of battery protection from low voltage, the "Undervoltage" error is generated.
71
72 Error generation conditions:
73
74 * the minimum voltage among all cells of the battery is less than the “Minimum cell voltage” value for the “Delay before setting the error” time.
75
76 Conditions for removing the error:
77
78 * the minimum voltage among all cells of the battery is greater than the “Tolerant cell voltage” value for the “Delay before clearing the error” time.
79
Admin 2.1 80 (% class="box infomessage" %)
81 (((
82 If there is the "Undervoltage" error, the **discharging **contactor opens.
83 )))
Admin 1.1 84
Admin 2.1 85 === Overvoltage ===
Admin 1.1 86
87 The BMS Main 3 device implements battery protection from too high voltage on the cells.
88
89 To change the battery protection parameters from high voltage on the cells, select the "Protections → Overvoltage" section:
90
Admin 2.1 91 [[image:1733328382382-607.png||data-xwiki-image-style-alignment="center" data-xwiki-image-style-border="true" height="138" width="800"]]
Admin 1.1 92
93 In this section:
94
95 * Enable – a flag to enable the protection;
96 * Maximum cell voltage, V;
97 * Tolerant cell voltage, V;
98 * Delay before setting the error, millisecond;
99 * Delay before clearing the error, second;
100 * Switch off the discharging contactor on error – a flag to open the discharging contactor when the "Overvoltage" error is generated;
101 * Lock – a flag to block the error until the device is restarted.
102
103 As a result of the operation of the battery protection from high voltage, the "Overvoltage" error is generated.
104
105 Error generation conditions:
106
107 * the maximum voltage among all cells of the battery is greater than the “Maximum cell voltage” value for the “Delay before setting the error” time.
108
109 Conditions for removing the error:
110
111 * the maximum voltage among all cells of the battery is less than the “Tolerant cell voltage” value for the “Delay before clearing the error” time.
112
Admin 2.1 113 (% class="box infomessage" %)
114 (((
115 If there is the "Overvoltage" error, the **charging** contactor and **discharging **contactor open (if the “Switch off the discharging contactor on error” flag is set).
116 )))
Admin 1.1 117
Admin 2.1 118 === Low temperature ===
Admin 1.1 119
120 The BMS Main 3 device implements battery protection from too low temperature.
121
122 To change the battery protection parameters from low temperature, select the "Protections → Low temperature" section:
123
Admin 2.1 124 [[image:1733328382382-670.png||data-xwiki-image-style-alignment="center" data-xwiki-image-style-border="true" height="137" width="800"]]
Admin 1.1 125
126 In this section:
127
128 * Enable – a flag to enable the protection;
129 * Minimum charge temperature, °C;
130 * Tolerant charge temperature, °C;
131 * Minimum discharge temperature, °C;
132 * Tolerant discharge temperature, °C;
133 * Delay before setting the error, millisecond;
134 * Delay before clearing the error, second;
135 * Lock – a flag to block the error until the device is restarted.
136
137 As a result of the operation of the battery protection from low temperature, the "Low temperature (CH)" and/or “Low temperature (DCH)” error are generated.
138
139 Error generation conditions:
140
141 * the minimum temperature among all cells of the battery is less than the “Minimum charging (discharging) temperature” value for the “Delay before setting the error” time.
142
143 Conditions for removing the error:
144
145 * the minimum temperature among all cells of the battery is greater than the “Tolerant charging (discharging) temperature” value for the “Delay before clearing the error” time.
146
Admin 2.1 147 (% class="box infomessage" %)
148 (((
149 If there is the "Low temperature (CH)" error, the **charging **contactor opens.
150 If there is the "Low temperature (DCH)" error, the **discharging **contactor opens.
151 )))
Admin 1.1 152
Admin 2.1 153 === High temperature ===
Admin 1.1 154
155 The BMS Main 3 device implements battery protection from too high temperature.
156
157 To change the battery protection parameters from high temperature, select the "Protections → High temperature" section:
158
Admin 2.1 159 [[image:1733328399408-279.png||data-xwiki-image-style-alignment="center" data-xwiki-image-style-border="true" height="138" width="800"]]
Admin 1.1 160
161 In this section:
162
163 * Enable – a flag to enable the protection;
164 * Maximum charge temperature, °C;
165 * Tolerant charge temperature, °C;
166 * Maximum discharge temperature, °C;
167 * Tolerant discharge temperature, °C;
168 * Delay before setting the error, millisecond;
169 * Delay before clearing the error, second;
170 * Lock – a flag to block the error until the device is restarted.
171
172 As a result of the operation of the battery protection from high temperature, the "High temperature (CH)" or “High temperature (DCH)” error is generated.
173
174 Error generation conditions:
175
176 * the maximum temperature among all cells of the battery is greater than the “Maximum charging (discharging) temperature” value for the “Delay before setting the error” time.
177
178 Conditions for removing the error:
179
180 * the maximum temperature among all cells of the battery is less than the “Tolerant charging (discharging) temperature” value for the “Delay before clearing the error” time.
181
Admin 2.1 182 (% class="box infomessage" %)
183 (((
184 If there is the "High temperature (CH)" error, the **charging **contactor opens.
185 If there is the "High temperature (DCH)" error, the **discharging **contactor opens.
186 )))
Admin 1.1 187
Admin 2.1 188 === Battery cover ===
Admin 1.1 189
190 To change the protection parameters from opening the battery cover, select the "Protections → Battery cover" section:
191
Admin 2.1 192 [[image:1733328399410-529.png||data-xwiki-image-style-alignment="center" data-xwiki-image-style-border="true" height="113" width="800"]]
Admin 1.1 193
194 In this section:
195
196 * Enable – a flag to enable the protection;
197 * Delay before setting the error, millisecond;
198 * Delay before clearing the error, second;
199 * Lock – a flag to block the error until the device is restarted.
200
201 As a result of the operation of the protection against opening the battery cover, the “Battery cover error” is generated.
202
203 Error generation conditions:
204
205 * there is a signal from the battery cover during the “Delay before setting the error” time.
206
207 Conditions for removing the error:
208
209 * no signal from the battery cover during the “Delay before clearing the error” time.
210
Admin 2.1 211 (% class="box warningmessage" %)
212 (((
213 If there is the "Battery cover error", the **“Critical error” **is generated **and all contactors open.**
214 )))
Admin 1.1 215
Admin 2.1 216 === High humidity ===
Admin 1.1 217
218 The BMS Main 3 can detect that the battery is operating in high humidity conditions.
219
220 To change the detection parameters, select the "Protections → High humidity" section:
221
Admin 2.1 222 [[image:1733328399412-184.png||data-xwiki-image-style-alignment="center" data-xwiki-image-style-border="true" height="106" width="800"]]
Admin 1.1 223
224 In this section:
225
226 * Enable – a flag to enable the detection;
227 * Maximum humidity, RH%;
228 * Tolerant humidity, RH%;
229 * Delay before setting the error, second;
230 * Delay before clearing the error, second;
231 * Lock the error until the device is reset.
232
233 As a result of the operation of the battery protection from high humidity, the "High humidity" error is generated.
234
235 Error generation conditions:
236
237 * the measured humidity is greater than “Maximum humidity” during the “Delay before setting the error” time.
238
239 Conditions for removing the error:
240
241 * the measured humidity is less than the “Tolerant humidity” during the “Delay before clearing the error” time.
242
Admin 2.1 243 (% class="box infomessage" %)
244 (((
Admin 1.1 245 If there is the "High humidity" error, no action is taken. The error is indicative.
Admin 2.1 246 )))
Admin 1.1 247
Admin 2.1 248 === Water ===
Admin 1.1 249
250 The BMS Main 3 can protect the battery from working in very high humidity conditions.
251
252 To change the protection parameters, select the "Protections → Water" section:
253
Admin 2.1 254 [[image:1733328399413-393.png||data-xwiki-image-style-alignment="center" data-xwiki-image-style-border="true" height="107" width="800"]]
Admin 1.1 255
256 In this section:
257
258 * Enable – a flag to enable the protection;
259 * Maximum humidity, RH%;
260 * Tolerant humidity, RH%;
261 * Delay before setting the error, second;
262 * Delay before clearing the error, second;
263 * Lock – lock the error until the device is reset.
264
265 As a result of the operation of the battery protection from water, the "Water" error is generated.
266
267 Error generation conditions:
268
269 * the measured humidity is greater than the “Maximum humidity” value during the “Delay before setting the error” time.
270
271 Conditions for removing the error:
272
273 * the measured humidity is less than the “Tolerant humidity” value during the “Delay before clearing the error” time.
274
Admin 2.1 275 (% class="box infomessage" %)
276 (((
277 If there is the “Water” error, the **“Critical error”** is generated and **all relays open**.
278 )))
Admin 1.1 279
Admin 2.1 280 === High Logic temperature ===
Admin 1.1 281
282 To change the overheating protection parameters of BMS Logic devices, select the "Protections → High Logic temperature" section:
283
Admin 2.1 284 [[image:1733328399414-280.png||data-xwiki-image-style-alignment="center" data-xwiki-image-style-border="true" height="105" width="800"]]
Admin 1.1 285
286 In this section:
287
288 * Enable – a flag to enable the protection;
289 * Maximum temperature, °C;
290 * Tolerant temperature, °C;
291 * Delay before setting the error, second;
292 * Delay before clearing the error, second;
293 * Lock – lock the error until the device is reset.
294
295 As a result of the operation of the protection from high temperatures of BMS Logic devices, the "High Logic temperature" is generated.
296
297 Error generation conditions:
298
299 * a BMS Logic device temperature is higher than the “Maximum temperature” value.
300
301 Conditions for removing the error:
302
303 * a BMS Logic device temperature is less than the “Tolerant temperature” value.
304
Admin 4.1 305 (% class="box infomessage" %)
Admin 2.1 306 (((
Admin 4.1 307 Cell balancing is disabled on Logic devices with high temperature.
Admin 2.1 308 )))
Admin 1.1 309
Admin 2.1 310 === Logic offline ===
Admin 1.1 311
312 To change the protection parameters from loss of communication with BMS Logic devices, select the "Protections → Logic offline" section:
313
Admin 2.1 314 [[image:1733328399416-818.png||data-xwiki-image-style-alignment="center" data-xwiki-image-style-border="true" height="86" width="800"]]
Admin 1.1 315
316 In this section:
317
318 * Enable – a flag to enable the protection;
319 * Lock – lock the error until the device is reset.
320
321 As a result of the protection from loss of communication with BMS Logic devices, the "Logic offline" error is generated.
322
323 Error generation conditions:
324
325 * at least one of the connected BMS Logic devices does not respond to the commands of the BMS Main device for 10 seconds.
326
327 Conditions for removing the error:
328
329 * all connected BMS Logic devices respond to the commands of the BMS Main device.
330
Admin 2.1 331 (% class="box warningmessage" %)
332 (((
333 If there is the "Logic offline" error, the **“Critical error” **is generated and **all relays open.**
334 )))
335
336 === Cell count ===
337
338 To change the protection parameters from the mismatch of the number of cells to the set value, select the "Protections → Cell count" section:
339
340 [[image:1733328415731-223.png||data-xwiki-image-style-alignment="center" data-xwiki-image-style-border="true" height="97" width="800"]]
341
342 In this section:
343
344 * Enable – a flag to enable the protection;
345 * Number of cells – a number of cells connected to the BMS;
346 * Delay before setting the error, millisecond;
347 * Delay before clearing the error, second;
348 * Lock – a flag to block the error until the device is restarted.
349
350 As a result of the operation of the protection from the mismatch of the number of cells, the "Cell count error" is generated.
351
352 Error generation conditions:
353
354 * the number of cells connected to the BMS is **not equal** to the “Number of cells” value during the “Delay before setting the error” time.
355
356 Conditions for removing the error:
357
358 * the number of cells connected to the BMS is **equal** to the “Number of cells” value during the “Delay before clearing the error” time.
359
360 (% class="box warningmessage" %)
361 (((
362 If there is the "Cell count error", the **“Critical error” **is generated and **all relays open.**
363 )))
364
365 === Logic count ===
366
367 To change the protection parameters from the mismatch of the number of BMS Logic devices to the set value, select the "Protections → Logic count” section:
368
369 [[image:1733328415732-163.png||data-xwiki-image-style-alignment="center" data-xwiki-image-style-border="true" height="110" width="800"]]
370
371 In this section:
372
373 * Enable – a flag to enable the protection;
374 * Logic count – a number of BMS Logic devices connected to the BMS Main;
375 * Scan fast – a flag to scan BMS Logic devices fast (devices with addresses from 1 to “Logic count” are scanned; this mode reduces BMS system startup time);
376 * Lock – lock the error until the device is reset.
377
378 As a result of the operation of the protection from the mismatch of the number of BMS Logic devices, the "Logic count error" is generated.
379
380 Error generation conditions:
381
382 * the number of BMS Logic devices connected to the BMS Main is **not equal** to the “Logic count” value.
383
384 Conditions for removing the error:
385
386 * the number of BMS Logic devices connected to the BMS Main is **equal** to the “Logic count” value.
387
388 (% class="box warningmessage" %)
389 (((
390 If there is the "Logic count error", the **“Critical error”** is generated and **all relays open.**
391 )))
392
393 === Short circuit ===
394
395 The BMS Main 3 device implements the protection of power circuits (contactors, power wires) against overheating caused by the flow of high current for a long time.
396
397 To change the protection parameters from short circuit, select the "Protections → Short circuit" section:
398
399 [[image:1733328415733-309.png||data-xwiki-image-style-alignment="center" data-xwiki-image-style-border="true" height="210" width="800"]]
400
401 In this section:
402
403 * Level 1, 2, 3 – three protection levels. The following parameters are configured at each level:
404 ** Enable – a flag to enable the protection;
405 ** Maximum current, A;
406 ** Delay before setting the error, second;
407 * Switch off the charging contactor on error – a flag to open the charging contactor when the "Short circuit" error occurs;
408 * Switch off the discharging contactor on error – a flag to open the discharging contactor when the "Short circuit" error occurs;
409 * Delay before clearing the error, second;
410 * Lock – a flag to block the error until the device is restarted.
411
412 If there is a short circuit, the "Short circuit" error is generated.
413
414 Error generation conditions:
415
416 * at any of the three protection levels, the current modulo is greater than the “Maximum current” value during the “Delay before setting the error” time.
417
418 Conditions for removing the error:
419
420 * the current modulo is lower than the “Maximum current” values for all three protection levels during the “Delay before setting the error” time.
421
422 (% class="box infomessage" %)
423 (((
424 If there is the "Short circuit" error, **charging **contactor opens (if the “Switch off the charging contactor on error” flag is set) and **discharging **contactor opens (if the “Switch off the discharging contactor on error flag” is set).
425 )))
426
427 === High contactor temperature ===
428
429 The BMS Main 3 device protects power contactors from overheating. To measure the temperature of the contactor, one of the thermistors connected to the X5 connector is used.
430
431 To change the overheating protection parameters of power contactors, select the "Protections → High contactor temperature" section:
432
433 [[image:1733328415734-986.png||data-xwiki-image-style-alignment="center" data-xwiki-image-style-border="true" height="138" width="800"]]
434
435 In this section:
436
437 * Enable – a flag to enable the protection;
438 * Thermistor – a selection of which cell thermistor will be used as contactor temperature sensor;
439 * Maximum contactor temperature, °C;
440 * Tolerant contactor temperature, °C;
441 * Delay before setting the error, second;
442 * Switch off the charging contactor on error – a flag to open the charging contactor when the "High contactor temperature" error occurs;
443 * Switch off the discharging contactor on error – a flag to open the discharging contactor when the "High contactor temperature" error occurs;
444 * Delay before clearing the error, second;
445 * Lock – a flag to block the error until the device is restarted.
446
447 If there is a contactor overheat, the "High contactor temperature" error is generated.
448
449 Error generation conditions:
450
451 * the contactor temperature is greater than the “Maximum contactor temperature” value during the “Delay before setting the error” time.
452
453 Conditions for removing the error:
454
455 * the contactor temperature is lower than the “Tolerant contactor temperature” value during the “Delay before clearing the error” time.
456
457 (% class="box infomessage" %)
458 (((
459 If there is the "High contactor temperature" error, **charging **contactor opens (if the “Switch off the charging contactor on error” flag is set) and **discharging **contactor opens (if the “Switch off the discharging contactor on error” flag is set).
460 )))
461
462 === Current sensor ===
463
464 The BMS Main 3 device checks the current sensor connection circuits. The circuits are checked for breakage and short-circuit to the +5 V supply line.
465
466 To change the test parameters of the current sensor connection circuits, select the "Protections → Current sensor" section:
467
468 [[image:1733328461552-948.png||data-xwiki-image-style-alignment="center" data-xwiki-image-style-border="true" height="128" width="800"]]
469
470 In this section:
471
472 * Enable – a flag to enable the protection;
473 * Maximum voltage, V;
474 * Minimum voltage, V;
475 * Voltage hysteresis – a hysteresis value to clear the error, V;
476 * Delay before setting the error, second;
477 * Delay before clearing the error, second;
478 * Lock – a flag to block the error until the device is restarted.
479
480 If there is an open or short circuit connection of a current sensor, the "Current sensor error" is generated.
481
482 Error generation conditions:
483
484 * the voltage in the signal line or reference line of the current sensor is greater than the “Maximum voltage” value during the “Delay before setting the error” time;
485 * the voltage in the signal line or reference line of the current sensor is less than the “Minimum voltage” value during the “Delay before setting the error” time.
486
487 Conditions for removing the error:
488
489 * the voltage in the signal line or reference line of the current sensor is in range from (Minimum voltage + Voltage hysteresis) to (Maximum voltage - Voltage hysteresis) during the “Delay before clearing the error” time.
490
491 (% class="box warningmessage" %)
492 (((
493 If there is the “Current sensor error”, the **“Critical error” **is generated and **all relays open.**
494 )))
495
496 === Power switch ===
497
498 BMS Main 3 device checks the status of power switches that are used to control the contactors. To change the parameters of the power switch protection, select the "Protections → Power switch" section:
499
500 [[image:1733328461554-241.png||data-xwiki-image-style-alignment="center" data-xwiki-image-style-border="true" height="99" width="800"]]
501
502 In this section:
503
504 * Delay before clearing the error, second;
505 * Lock – a flag to block the error until the device is restarted.
506
507 The “Power switch error” occurs when the device detects a shortage in contactor coil control circuit or an overheating of the power switch. Error is removed when the temperature of power switch is normal during “Delay before clearing the error” time.
508
509 (% class="box warningmessage" %)
510 (((
511 If there is the "Power switch error", the **“Critical error” **is generated and **all relays open.**
512 )))
513
514 === Charge contactor cycles ===
515
516 The BMS Main 3 device protects the charging contactor against frequent switching.
517
518 To change the protection parameters against high frequency switching of the charging contactor, select the "Protections → Charge contactor cycles" section:
519
520 [[image:1733328461555-351.png||data-xwiki-image-style-alignment="center" data-xwiki-image-style-border="true" height="124" width="800"]]
521
522 In this section:
523
524 * Enable – a flag to enable the protection;
525 * Cycles threshold – a number of cycles in a given period, upon which the “CH contactor cycles error” is generated;
526 * Check time – a time in which the BMS counts switching cycles of the charging contactor, second;
527 * Delay before setting the error, millisecond;
528 * Delay before clearing the error, second;
529 * Lock – a flag to block the error until the device is restarted.
530
531 If there is a high switching frequency of the charging contactor, the “CH contactor cycles error” is generated.
532
533 Error generation conditions:
534
535 * the number of switching cycles of the charging contactor for the “Check time” time is greater than or equal to the “Cycles threshold” value. The error is generated with the “Delay before setting the error” delay.
536
537 Conditions for removing the error:
538
539 * the “Delay before clearing the error” time has passed since the error was generated.
540
541 (% class="box infomessage" %)
542 (((
543 If there is the "CH contactor cycles error" error, the **charging **contactor opens.
544 )))
545
Admin 3.1 546 === Discharge contactor cycles ===
Admin 2.1 547
548 The BMS Main 3 device protects the discharging contactor against frequent switching.
549
550 To change the protection parameters against high frequency switching of the discharging contactor, select the "Protections → Discharging contactor cycles" section:
551
552 [[image:1733328461560-301.png||data-xwiki-image-style-alignment="center" data-xwiki-image-style-border="true" height="123" width="800"]]
553
554 In this section:
555
556 * Enable – a flag to enable the protection;
557 * Cycles threshold – a number of cycles in a given period, upon which the “DCH contactor cycles error” is generated;
558 * Check time – a time in which the BMS counts switching cycles of the charging contactor, second;
559 * Delay before setting the error, millisecond;
560 * Delay before clearing the error, second;
561 * Lock – a flag to block the error until the device is restarted.
562
563 If there is the high switching frequency of the discharging contactor, the “DCH contactor cycles error” is generated.
564
565 Error generation conditions:
566
567 * the number of switching cycles of the discharging contactor for the “Check time” time is greater than or equal to the “Cycles threshold” value. The error is generated with the “Delay before setting the error” delay.
568
569 Conditions for removing the error:
570
571 * the “Delay before clearing the error” time has passed since the error was generated.
572
573 (% class="box infomessage" %)
574 (((
575 If there is the "DCH contactor cycles error" error, the **discharging **contactor opens.
576 )))
577
578 === Temperature sensors ===
579
580 The BMS Main 3 device checks the temperature sensors connection circuits. The circuits are checked for breakage and short-circuit.
581
582 To change the protection parameters of the temperature sensors circuits, select the "Protections → Temperature sensors" section:
583
584 [[image:1733328471918-980.png||data-xwiki-image-style-alignment="center" data-xwiki-image-style-border="true" height="102" width="800"]]
585
586 In this section:
587
588 * Enable – a flag to enable the protection;
589 * Delay before setting the error, millisecond;
590 * Delay before clearing the error, second;
591 * Lock – a flag to block the error until the device is restarted.
592
593 If there are no temperature sensors connected to any BMS Logic device or any temperature sensor of the BMS Logic is shorted, the "No temp. sensors" error and "Temp. sensor is shorted" error are generated respectively. These errors generated and removed with the “Delay before setting the error” and “Delay before clearing the error” delays.
594
595 (% class="box warningmessage" %)
596 (((
Admin 4.1 597 If there is the “No temp. sensors” or “Temp. sensor is shorted” error, the **“Critical error”** is generated and **all relays open.**
Admin 2.1 598 )))
599
600 === WDT reset ===
601
602 If the BMS firmware hangs, the watchdog timer resets the device. The BMS can detect that the device was reset and generates the “WDT reset” error.
603
604 To change the parameters of the watchdog protection, select the "Protections → WDT reset" section:
605
606 [[image:1733328471919-183.png||data-xwiki-image-style-alignment="center" data-xwiki-image-style-border="true" height="101" width="800"]]
607
608 In this section:
609
610 * Enable – a flag to enable the protection;
611 * Delay before clearing the error, second;
612 * Lock – a flag to block the error until the device is restarted.
613
614 Conditions for removing the error:
615
616 * the “Delay before clearing the error” time has passed from the device startup.
617
618 (% class="box warningmessage" %)
619 (((
620 If there is the "WDT reset" error, the **“Critical error” **is generated and **all relays open.**
621 )))
622
Admin 4.1 623 === Unallowable charging ===
Admin 2.1 624
625 The BMS can detect that the battery is charging through the discharging circuit and protectively open the discharging contactor to prevent unallowable battery operation.
626
627 To change the parameters of the unallowable charging protection, select the "Protections → Unallowable charging" section:
628
629 [[image:1733328471920-923.png||data-xwiki-image-style-alignment="center" data-xwiki-image-style-border="true" height="97" width="800"]]
630
631 In this section:
632
633 * Enable – a flag to enable the protection;
634 * Delay before setting the error, second;
635 * Delay before clearing the error, second;
636 * Lock – a flag to block the error until the device is restarted.
637
638 If there is charging the battery through the discharging circuit detected, the "Unallowable charging" error is generated.
639
640 Error generation conditions:
641
642 * the charging contactor is open, and the battery current is not zero during the “Delay before setting the error” time.
643
644 Conditions for removing the error:
645
646 * the battery current is zero during the “Delay before clearing the error” time.
647
648 (% class="box infomessage" %)
649 (((
650 If there is the "Unallowable charging" error, the **discharging **contactor opens.
651 )))
652
Admin 5.1 653 === Stuck contactor ===
Admin 2.1 654
655 The BMS Main 3 device protects contactors against sticking.
656
657 To change the protection parameters against sticking, select the "Protections → Stuck contactor" section:
658
659 [[image:1733328471920-314.png||data-xwiki-image-style-alignment="center" data-xwiki-image-style-border="true" height="123" width="800"]]
660
661 In this section:
662
663 * Enable – a flag to enable the protection;
664 * Delay before setting the error, millisecond;
665 * Delay before clearing the error, second;
666 * Check voltage – a flag to enable checking of voltage before and after contactors to detect the fact of contactor sticking;
667 * Abnormal voltage difference – the difference of voltages before and after contactors at which BMS indicates and error;
668 * Lock – a flag to block the error until the device is restarted.
669
670 If there is a stuck contactor, the “Stuck contactor” error is generated. Error generation conditions:
671
672 * The charging and discharging contactors are open, but the “Charging current present” or “Discharging current present” signal is set or (if “Check voltage” flag is set) “Charging/Discharging” contactor is open and voltage difference before and after contactors is lower than “Abnormal voltage difference”.
673
674 (% class="box warningmessage" %)
675 (((
676 If there is the “Stuck contactor” error, the **“Critical error” **is generated and **all relays open.**
677 )))
678
679 === Contactor feedback ===
680
681 The BMS Main 3 device can receive feedback signals from contactors and detect discrepancy between the control value and the feedback signal. To enable specific contactor protection, the feedback signal must be connected to the corresponding contactor feedback pin on the X3 header.
682
683 To change the contactor feedback check parameters, select the "Protections → Contactor feedback" section:
684
685 [[image:1733328487096-144.png||data-xwiki-image-style-alignment="center" data-xwiki-image-style-border="true" height="109" width="800"]]
686
687 In this section:
688
689 * Enable – a flag to enable the protection;
690 * Delay before setting the error, millisecond;
691 * Delay before clearing the error, second;
692 * Lock – a flag to block the error until the device is restarted.
693
694 If there is a discrepancy at any contactor, the corresponding contactor feedback error is generated. Error generation conditions:
695
696 * a command to the charging, precharging, discharging, charging/discharging or main contactor does not match its feedback value.
697
698 (% class="box warningmessage" %)
699 (((
700 If there is the “Contactor feedback” error, the **“Critical error” **is generated and **all relays open.**
701 )))
702
Admin 5.1 703 === Insulation ===
Admin 2.1 704
705 The BMS Main 3 device can detect a physical signal or CAN bus message from an external insulation monitoring device (such as Bender IR155, iso165C, BMD IMD) to monitor the insulation quality.
706
707 To change the insulation monitoring parameters, select the "Protections → Insulation" section:
708
709 [[image:1733328487098-963.png||data-xwiki-image-style-alignment="center" data-xwiki-image-style-border="true" height="121" width="800"]]
710
711 In this section:
712
713 * Enable – a flag to enable the protection;
714 * Checking algorithm – isolation checking mode:
715 ** Always on – check is always performed;
716 ** On charging – check is performed only if “Charger connected” or “Charge request” is set;
717 ** Except charging - check is performed only if “Charger connected” and “Charge request” are cleared;
718 * Delay before setting the error, second;
719 * Delay before clearing the error, second;
720 * Lock – a flag to block the error until the device is restarted.
721
722 The “Insulation fault” is set if the “Insulation status” signal is detected during the “Delay before setting the error” time. The “Insulation status” signal can be received through the discrete input or by the CAN bus from an insulation monitoring device. The “Insulation fault” is cleared if the “Insulation status” signal is cleared during the “Delay before clearing the error” time.
723
724 (% class="box warningmessage" %)
725 (((
726 If there is the “Insulation fault”, the **“Critical error”** is generated and **all relays open.**
727 )))
728
729 === HVIL ===
730
731 The BMS Main 3 allows to control the high voltage interlock loop by applying current to a testing loop and monitoring the difference between the measured current and the required value.
732
733 To change the HVIL measurement parameters, select the "Protections → HVIL" section:
734
735 [[image:1733328487099-371.png||data-xwiki-image-style-alignment="center" data-xwiki-image-style-border="true" height="85" width="800"]]
736
737 In this section:
738
739 * Enable – a flag to enable the protection;
740 * Lock – a flag to block the error until the device is restarted.
741
742 If interlock loop breaks, the “HVIL error” is generated. Error clears if interlock loop is being restored.
743
744 (% class="box warningmessage" %)
745 (((
746 If there is the “HVIL error”, the **“Critical error”** is generated and **all relays open.**
747 )))
748
749 === Critical error ===
750
751 To change the critical error parameters, select the "Protections → Critical error" section:
752
753 [[image:1733328487100-898.png||data-xwiki-image-style-alignment="center" data-xwiki-image-style-border="true" height="101" width="800"]]
754
755 In this section:
756
757 * Enable – a flag to enable the protection;
758 * Delay before setting the error, millisecond;
759 * Delay before clearing the error, second;
760 * Lock – a flag to block the error until the device is restarted.
761
762 The critical error flag is generated if at least one of the following errors is generated during the “Delay before setting the error” time:
763
764 * “Battery cover error”;
765 * “Water”;
766 * “Logic offline”;
767 * “Cell count error”;
768 * “ADC error”;
769 * “Current sensor error”;
770 * “Shunt offline”;
771 * “Shunt error”;
772 * “WDT reset”
773 * “No temp. sensors”;
774 * “Temperature sensor shorted”;
775 * “Stuck contactor”;
776 * “CH contactor feedback error”;
777 * “DCH contactor feedback error”;
778 * “Insulation fault”;
779 * “PCH contactor feedback error”;
780 * “CH/DCH contactor feedback error”;
781 * “Main contactor feedback error”;
782 * “High voltage fault”;
783 * “Power switch error”;
784 * “HVIL error”l
785 * “Power fault”.
786
787 The “Critical error” is cleared if there are no errors from the list above during the “Delay before clearing the error” time.
788
789 (% class="box infomessage" %)
790 (((
791 If there is the “Critical error”, **all **contactors open.
792 )))
793
Admin 6.1 794 === General error ===
Admin 2.1 795
796 To change the general error parameters, select the "Protections → Critical error" section:
797
798 [[image:1733328487101-216.png||data-xwiki-image-style-alignment="center" data-xwiki-image-style-border="true" height="262" width="800"]]
799
800 In this section:
801
802 * Enable – a flag to enable the protection;
803 * Delay before setting the error, millisecond;
804 * Delay before clearing the error, second;
805 * Lock – a flag to block the error until the device is restarted;
806 * Check: <error> – a flags to enable check of corresponding errors.
807
808 The general error flag is generated if at least one of the enabled errors is generated during the “Delay before setting the error” time.
809
810 The “General error” is cleared if there are no errors from the enabled errors during the “Delay before clearing the error” time.
811
812 (% class="box infomessage" %)