Wiki source code of 3.3 Control

Version 66.2 by Admin on 2025/12/11 09:57

Hide last authors
Admin 4.1 1 (% data-numbered-headings-start="3" style="--numbered-headings-start: 2;font-size: 0px;color: rgba(0, 0, 0, 0.0);margin-bottom: 0px; margin-top: 0px;" %)
Admin 33.1 2 = Configuration =
Admin 1.3 3
Admin 4.1 4 (% data-numbered-headings-start="3" style="--numbered-headings-start: 2;font-size: 0px;color: rgba(0, 0, 0, 0.0);margin-bottom: 0px; margin-top: 0px;" %)
5 == Control ==
Admin 3.1 6
7 === Common settings ===
8
Admin 1.3 9 To change the common BMS settings, select the "Control → Common settings" section:
10
Admin 6.2 11 [[image:1735054851946-552.png||data-xwiki-image-style-alignment="center" data-xwiki-image-style-border="true" height="105" width="800"]]
Admin 1.3 12
13 In this section:
14
15 * Cell capacity – nominal capacity of cells, Ah;
16 * Cell resistance – nominal (maximum) internal resistance of the cells, Ohm;
17 * Relax time (after charging) – a relaxation time after charging, second;
18 * Relax time (atfer discharging) – a relaxation time after discharging, second;
Admin 6.2 19 * Reset parameters – a command to reset cells state of charge, capacity, and resistance;
20 * Method of calculating the battery voltage:
Admin 6.4 21 ** Summation of cell voltages – the overall voltage is calculated as on sum of all cells in the battery;
Admin 6.5 22 ** Using voltage before contactors – the overall voltage is estimated as voltage before contactors measured by BMS.
Admin 1.3 23
Admin 42.2 24 The values “Capacity” and “Resistance” are used to calculate the SOC of cells and the battery.
Admin 1.3 25
26 The values of “Relax time” are used to determine the state of the battery. If the battery is in a state of relaxation, the system recalculates the voltage on the cells to the state of charge of the battery.
27
28 The “Reset parameters” will reset:
29
30 * state of charge (new cell SOC values will be calculated based on cell voltage and “Uocv (open-circuit voltage) table”: in the “Control → SOC estimation” section);
31 * cell resistance to “Cell resistance” value;
32 * battery capacity to “Cell capacity” value.
33
34 The “Reset parameters” command is used for starting-up and adjustment of the battery.
35
Admin 3.1 36 === SOC estimation ===
Admin 1.3 37
38 The BMS Main 3 device calculates the state of charge of the battery (SOC) using two algorithms:
39
40 * by open circuit voltage;
41 * by voltage and current.
42
43 It is recommended to use the algorithm of calculation of SOC by voltage and current.
44
45 To change the estimation algorithm for calculating the battery SOC, select the "Control → SOC estimation → Algorithm" section:
46
47
Admin 8.2 48 [[image:1735056107942-306.png||data-xwiki-image-style-alignment="center" data-xwiki-image-style-border="true" height="141" width="800"]]
49
Admin 1.3 50 The following estimation algorithms supported:
51
52 * Voltage – by open circuit voltage;
53 * Current and voltage (simplified) – recommended for LFP cells;
54 * Current and voltage (enhanced) – recommended for NMC cells.
55
56 The **“Voltage”** SOC calculation algorithm calculates cells SOC based on the tabular dependence Uocv = Uocv(SOC, t °C).
57
58 The **“Current and voltage (simplified)”** SOC calculation algorithm works as follows:
59
60 * if I = 0, the battery is in the state of relaxation and the cell voltage Uocv is outside the [U,,ocv[point 1],,; U,,ocv[point 2],,], the SOC calculation is based on the tabular dependency Uocv = Uocv(SOC, t °C);
61 * in any other cases, the SOC value is proportional to the charge (coulomb) passed through the battery (current time integral).
62
63 The **“Current and voltage (enhanced)” **SOC calculation algorithm differs from the simplified algorithm by online correction of the effective capacity. When using this algorithm, it is necessary to fine tune the tabular dependence Uocv = Uocv (SOC, t °C).
64
65 To change the algorithm for calculating the Final SOC, select the "Control → SOC estimation → Final SOC" section:
66
Admin 2.1 67 [[image:1733322611551-852.png||data-xwiki-image-style-alignment="center" data-xwiki-image-style-border="true" height="148" width="800"]]
Admin 1.3 68
69 The following calculation methods are supported (“Final SOC”):
70
71 * Minimal SOC – the battery SOC is assumed to be the minimum SOC among the cells;
72 * Average SOC – the battery SOC is taken equal to the arithmetic average of the cell SOC;
Admin 35.1 73 * Min-Max SOC – the battery SOC is calculated based on the minimum and maximum SOC of the cells. Final SOC will be a) 100% if any cell has 100% SOC, b) 0% if any cell has 0% SOC;
Admin 42.3 74 * Max-Min SOC – the battery SOC is calculated based on the minimum and maximum SOC of the cells. Final SOC will be a) 100% if all cells have 100% SOC, b) 0% if all cells have 0% SOC.
Admin 1.3 75
76 Other parameters:
77
78 * Scale the final SOC – a flag to scale the battery SOC by the following values;
79 * SOC corresponding to 0% – the battery SOC that sets to be 0%;
80 * SOC corresponding to 100% – the battery SOC that sets to be 100%.
81 * Uocv (open-circuit voltage) table – the dependence of the cell open circuit voltage Uocv on SOC and the cell temperature (selected for specific batteries);
82 * Linear zone - linear zone of the Uocv = Uocv(SOC, t°C) dependency, inside which the cell voltage changes insignificantly:
83 ** Linear zone: point 1 – starting point of the Uocv linear zone;
84 ** Linear zone: point 2 – ending point of the Uocv linear zone;
85 * Coulomb counting correction (temperature) – the dependence of battery capacity on temperature;
86 * Coulomb counting correction (cycles) – the dependence of battery capacity on the number of charge-discharge cycles.
87
Admin 3.1 88 === SOC correction ===
Admin 1.3 89
Admin 5.1 90 The BMS Main 3 device can recalculate the battery SOC after long-term storage or after long-term working in the case when the battery was not charged fully or discharged totally. Recalculation is done based on the tabular dependency Uocv = Uocv (SOC, t) (see [[SOC estimation>>doc:||anchor="HSOCestimation"]]).
Admin 1.3 91
92 To configure parameters for periodically correcting the battery state of charge, select the "Control → SOC correction" section:
93
Admin 2.1 94 [[image:1733322624656-766.png||data-xwiki-image-style-alignment="center" data-xwiki-image-style-border="true" height="121" width="800"]]
Admin 1.3 95
96 In this section:
97
98 * Enable – a flag to enable the SOC correction;
99 * Shutdown period – a time the battery is off, day. If the BMS detects on its startup that it was off during the “Shutdown period” time, the BMS recalculates the battery state of charge based on the tabular dependency Uocv = Uocv (SOC, t);
100 * Correction period – a period of correcting the battery SOC, day. If the BMS detects that the last correction was more than the “Correction period” ago, the BMS recalculates the battery state of charge based on the tabular dependency Uocv = Uocv (SOC, t) and tunes it gradually during the “SOC change time”.
101 * SOC change time – a duration of the linear changing the battery SOC to the value calculated by the correction algorithm, minute;
102 * Ignore the linear zone – a flag to ignore linear SOC zone while correction (recommended to be unset);
103 * Last correction timestamp – time when last correction was made.
104
Admin 65.2 105 === SOH estimation ===
106
107 The BMS Main 3 device calculates the state of health of the battery (SOH) using two algorithms:
108
109 * by effective capacity;
Admin 66.2 110 * by total charge-.
Admin 65.2 111
Admin 66.2 112 In "By effective capacity" mode SOH is calculated as
Admin 65.2 113
Admin 3.1 114 === Resistance estimation ===
Admin 1.3 115
116 Calculation of the resistance of cells is carried out in two ways. The first method is used when the battery passes from a relaxation state to a charge or discharge state, wherein the cell resistance value
117
Admin 10.6 118 {{formula fontSize="SMALL" imageType="PNG"}}
Admin 10.3 119 R = \frac{U-U_{ocv}}{I_{stable}}
120 {{/formula}}
Admin 1.3 121
Admin 10.3 122 where U — the cell voltage measured in the charge or discharge state, V; U,,ocv,, — cell voltage measured in the state of relaxation (before switching to the state of charge or discharge); I,,stable,, — stabilized current through the cell in the state of charge or discharge.
Admin 10.2 123
Admin 1.3 124 The second method is used for a stepwise change in the current through the cell, while the value of the cell resistance:
125
Admin 10.6 126 {{formula fontSize="SMALL"}}
Admin 10.5 127 R = \frac{U_2-U_1}{I_{stable2}-I_{stable1}}
128 {{/formula}}
Admin 1.3 129
Admin 10.5 130 provided that
131
Admin 10.6 132 {{formula fontSize="SMALL"}}
133 | I_{stable2}-I_{stable1} | > 0.2 × Qmax
Admin 10.4 134 {{/formula}}
Admin 10.3 135
Admin 10.6 136 where Q,,max,, — the maximum cell capacity,U,,2,, — voltage on the cell at the moment when the stabilized current I,,stable2,, is flowing through it; U,,1,, — the voltage on the cell at the moment when the stabilized current I,,stable1,, flowing through it.
Admin 1.3 137
138 The stabilized current I,,stable,, = I, if during the stabilization time the instantaneous current I is in the range from 0.95 × I to 1.05 × I.
139
140 To change parameters of the algorithm for calculating the cell resistance, select the "Control → Resistance estimation" section:
141
Admin 2.1 142 [[image:1733322624659-473.png||data-xwiki-image-style-alignment="center" data-xwiki-image-style-border="true" height="108" width="800"]]
Admin 1.3 143
144 In this section:
145
146 * Current stabilization time, millisecond;
147 * Maximum calculation period – maximum time between resistance measurements. If more time has elapsed since the last determination of the stabilized current I,,stable,, than is determined in this field, the resistance calculation is not performed, second;
148 * Maximum resistance factor – the coefficient of calculation of the maximum acceptable resistance of the cell;
149 * Minimum SOC – minimum cell SOC value for resistance calculation;
150 * Maximum SOC – maximum cell SOC value for resistance calculation.
151
Admin 10.7 152 The calculated resistance is accepted by the system as valid (and therefore updated) if its value is in the range from Resistance / 2 to “Maximum resistance factor” × Resistance, where "Resistance" is the nominal resistance of the cell (see [[Common settings>>doc:||anchor="HCommonsettings"]]). If the calculated resistance value is greater than the value (Maximum resistance factor × Resistance), the updated resistance value will be equal to the value (Maximum resistance factor × Resistance).
Admin 1.3 153
Admin 3.1 154 === Low SOC (signal) ===
Admin 1.3 155
156 To change the parameters of the generation a signal about low battery level, select the "Control → Low SOC (signal)" section:
157
Admin 2.1 158 [[image:1733322624660-513.png||data-xwiki-image-style-alignment="center" data-xwiki-image-style-border="true" height="116" width="800"]]
Admin 1.3 159
160 In this section:
161
162 * Enable – a flag to enable signal generation;
163 * Minimum SOC, %;
164 * Tolerant SOC, %;
165 * Delay before setting the signal, second;
166 * Delay before clearing the signal, second;
167 * Lock – lock the signal until the device is reset.
168
169 Signal generation conditions:
170
171 * the battery SOC is less than the “Minimum SOC” value during the “Delay before setting the signal” time.
172
173 Conditions for clearing the signal:
174
175 * the battery SOC is greater than the “Tolerant SOC” during the “Delay before clearing the signal” time.
176
Admin 30.2 177 (% class="box infomessage" %)
178 (((
Admin 1.3 179 The "Low SOC signal" is indicative and can be output to a discrete output or a power switch.
Admin 30.2 180 )))
Admin 1.3 181
Admin 3.1 182 === High charging current (signal) ===
Admin 1.3 183
184 To change the parameters of the generation high-current signal, select the "Control → High charging current (signal)" section:
185
Admin 2.1 186 [[image:1733322624661-915.png||data-xwiki-image-style-alignment="center" data-xwiki-image-style-border="true" height="107" width="800"]]
Admin 1.3 187
188 In this section:
189
190 * Enable – a flag to enable signal generation;
191 * Maximum charging current, А;
192 * Tolerant charging current, А;
193 * Delay before setting the signal, second;
194 * Delay before clearing the signal, second;
195 * Lock – lock the signal until the device is reset.
196
197 Signal generation conditions:
198
199 * the measured current is greater than the “Maximum charging current” value during the “Delay before setting the signal” time.
200
201 Conditions for clearing the signal:
202
203 * the measured current is less than the “Tolerant charging current” value during the “Delay before clearing the signal” time.
204
Admin 30.2 205 (% class="box infomessage" %)
206 (((
Admin 1.3 207 The "High charging current" signal is indicative and can be output to a discrete output or a power switch.
Admin 30.2 208 )))
Admin 1.3 209
Admin 3.1 210 === Charge map ===
Admin 1.3 211
212 The BMS Main 3 device calculates the maximum allowable charge current values in respect to SOC, battery temperature, contactor temperature and cell voltage.
213
214 Calculated current values are sent to a charger or an intellectual load over the CAN bus. External devices based on received data provide correct battery operation.
215
216 To configure parameters for determining the charge current limit, select the "Control → Charge map" section:
217
Admin 26.1 218 [[image:1735064362593-844.png||data-xwiki-image-style-alignment="center" data-xwiki-image-style-border="true" height="153" width="800"]]
Admin 1.3 219
220 In this section:
221
222 * Enable – a flag to start calculation of the charge current limit;
223 * Maximum charge current – a maximum allowable value of the charge current (under normal conditions), A;
224 * Rate of change – a rate of change the current limit to a new value (0 is for immediate change), A/s;
Admin 45.1 225 * Option 1: Limit charge current by the battery SOC and temperature – a flag to enable correction of maximum allowable charging current** Kcs** depending on __maximum cell SOC__ and battery temperature;
Admin 1.3 226 * Option 1: SOC x Temperature x Factor – the dependence of the correction factor on SOC and battery temperature;
Admin 32.1 227 * Option 2: Limit charge current by the contactor temperature – a flag to enable correction of maximum allowable charging current **Kcc** depending on contactor temperature;
Admin 1.3 228 * Option 2: Contactor temperature x Factor – the dependence of the correction factor on SOC and contactor temperature;
Admin 44.1 229 * Option 3: Limit charge current by the maximum cell voltage - a flag to enable correction of maximum allowable charging current **Kcv** depending on __the maximum cell U,,ocv,, voltage__ (corrected due to current and cell resistance)
Admin 1.3 230 * Option 3: Cell voltage x Factor – the dependence of the correction factor on maximum cell voltage;
Admin 32.1 231 * Option 4: Limit charge current by the cell temperature - a flag to enable correction of maximum allowable charging current **Kct** depending on maximum cell temperature;
Admin 1.3 232 * Option 4: Cell temperature x Factor – the dependence of the correction factor on maximum cell temperature.
233
234 Value of the charge current limit at given SOC, temperature, contactors temperature, maximum cell voltage and maximum cell temperature is calculated as follows:
235
Admin 32.1 236 **Charge current limit = Maximum charge current × Kcs × Kcc × Kcv × Kct**
Admin 1.3 237
Admin 3.1 238 === Discharge map ===
Admin 1.3 239
240 The BMS Main 3 device calculates the maximum allowable discharge current values in respect to SOC, battery temperature, contactor temperature and cell voltage.
241
242 Calculated current values are sent to a charger or an intellectual load over the CAN bus.
243
244 To configure parameters for determining the discharge current limit, select the "Control → Discharge map" section:
245
Admin 26.1 246 [[image:1735064399985-526.png||data-xwiki-image-style-alignment="center" data-xwiki-image-style-border="true" height="152" width="800"]]
Admin 1.3 247
248 In this section:
249
250 * Enable – a flag to start calculation of the discharge current limit;
251 * Maximum discharge current – a maximum allowable value of the discharge current (under normal conditions), A;
252 * Rate of change – a rate of change the current limit to a new value (0 is for immediate change), A/s;
Admin 45.1 253 * Option 1: Limit discharging current by the battery SOC and temperature – a flag to enable correction of maximum allowable discharging current **Kds **depending on __minimum cell SOC__ and temperature;
Admin 1.3 254 * Option 1: SOC x Temperature x Factor – the dependence of the correction factor on SOC and battery temperature;
Admin 32.1 255 * Option 2: Limit discharge current by the contactor temperature – a flag to enable correction of maximum allowable discharging current **Kdc** depending on contactor temperature;
Admin 1.3 256 * Option 2: Contactor temperature x Factor – the dependence of the correction factor on SOC and contactor temperature;
Admin 44.1 257 * Option 3: Limit discharge current by the cell voltage - a flag to enable correction of maximum allowable discharging current **Kdv** depending on __the minimum cell U,,ocv,, voltage__ (corrected due to current and cell resistance)
Admin 1.3 258 * Option 3: Cell voltage x Factor – the dependence of the correction factor on minimum cell voltage;
Admin 32.1 259 * Option 4: Limit discharge current by the cell temperature - a flag to enable correction of maximum allowable discharging current **Kdt** depending on maximum cell temperature;
Admin 1.3 260 * Option 4: Cell voltage x Factor – the dependence of the correction factor on minimum cell temperature.
261
262 Value of the discharge current limit at given SOC, temperature, contactors temperature, minimum cell voltage and maximum cell temperature is calculated as follows:
263
Admin 32.1 264 **Discharge current limit = Maximum discharge current × Kds × Kdc × Kdv × Kdt**
Admin 1.3 265
Admin 3.1 266 === Charge map (PEAK & CONTINUOUS) ===
Admin 1.3 267
268 The BMS Main 3 has an alternative algorithm for the maximum allowed charging current based on peak and continuous battery operating modes.
269
270 To configure parameters for determining the charge current limit, select the "Control → Charge map (PEAK & CONTINUOUS)" section:
271
Admin 26.1 272 [[image:1735064434321-430.png||data-xwiki-image-style-alignment="center" data-xwiki-image-style-border="true" height="124" width="800"]]
Admin 1.3 273
274 In this section:
275
276 * Enable – a flag to start calculation of the charge current limit;
277 * Maximum PEAK charge current – a maximum peak charge current (under normal conditions), A;
278 * Maximum CONTINUOUS charge current – a maximum continuous charge current (under normal conditions), A;
279 * PEAK: SOC x Temperature x Factor – the dependence of the correction factor for peak current K,,cp,, on SOC and battery temperature;
280 * CONTINUOUS: SOC x Temperature x Factor – the dependence of the correction factor for continuous current K,,cc,, on SOC and battery temperature;
281 * PEAK time – a time for peak current to be allowed, s;
282 * Sliding time – a time of linear change of the maximum charging current from peak to continuous and from continuous to peak value, ms;
283 * Waiting time – a time for peak current to be prohibited, s.
284
285 The maximum charging current value equals to the peak or continuous current according to the following diagram:
286
Admin 2.1 287 [[image:1733322717451-608.png||data-xwiki-image-style-alignment="center"]]
Admin 1.3 288
289 I,,peak,, = Maximum PEAK charge current × K,,cp,,
290
291 I,,continuous,, = Maximum CONTINUOUS charge current × K,,cc,,
292
Admin 3.1 293 === Discharge map (PEAK & CONTINUOUS) ===
Admin 1.3 294
295 The BMS Main 3 has an alternative algorithm for the maximum allowed discharging current based on peak and continuous battery operating modes.
296
297 To configure parameters for determining the discharge current limit, select the "Control → Discharge map (PEAK & CONTINUOUS)" section:
298
Admin 26.1 299 [[image:1735064454708-345.png||data-xwiki-image-style-alignment="center" data-xwiki-image-style-border="true" height="124" width="800"]]
Admin 1.3 300
301 In this section:
302
303 * Enable – a flag to start calculation of the discharge current limit;
304 * Maximum PEAK discharge current – a maximum peak discharge current (under normal conditions), A;
305 * Maximum CONTINUOUS discharge current – a maximum continuous discharge current (under normal conditions), A;
306 * PEAK: SOC x Temperature x Factor – the dependence of the correction factor for peak current K,,dp,, on SOC and battery temperature;
307 * CONTINUOUS: SOC x Temperature x Factor – the dependence of the correction factor for continuous current K,,dc,, on SOC and battery temperature;
308 * PEAK time – a time for peak current to be allowed, s;
309 * Sliding time – a time of linear change of the maximum charging current from peak to continuous and from continuous to peak value, ms;
310 * Waiting time – a time for peak current to be prohibited, s.
311
312 The maximum discharging current value equals to the peak or continuous current according to following diagram:
313
Admin 2.1 314 [[image:1733322753429-968.png||data-xwiki-image-style-alignment="center"]]
Admin 1.3 315
316 I,,peak,, = Maximum PEAK discharge current × K,,dp,,
317
318 I,,continuous,, = Maximum CONTINUOUS discharge current × K,,dc,,
319
Admin 10.8 320 === Main contactor ===
321
Admin 11.1 322 The BMS Main 3 device controls the main contactor. The main contactor is usually placed in the common (minus) battery line for opening the charge and discharge circuits in case of sealing of the charging or discharging contactors.
Admin 10.8 323
Admin 11.1 324 The Main contactor algorithm supports the following modes:
325
326 * Always on;
Admin 42.1 327 * Automatic.
Admin 11.1 328
329 In “Always on” mode main contactor closes if all the following is true:
330
Admin 33.2 331 * Other contactors are open;
332 * There are no errors from the "Errors 1, 2 ..." bitfileds.
Admin 11.1 333
334 In “Always on” mode main contactor opens if all the following is true:
335
Admin 33.2 336 * Other contactors are open;
337 * There is an error from the the "Errors 1, 2 ..." bitfileds.
Admin 11.1 338
Admin 33.3 339 In “Automatic” mode, the main contactor closes by internal algorithms at the same time with other contactors.
Admin 11.1 340
341 In “On demand” mode, the main contactor closes by external the “Close Main contactor” request.
342
Admin 29.5 343 (% class="box infomessage" %)
344 (((
345 **Note: **when errors occur in the system, the **Main **contactor opens either immediately or with the delay T,,off,, (depends on the settings described below).
346 )))
347
Admin 11.1 348 To change the parameters of the main contactor, select the "Control → Main contactor" section:
349
Admin 26.1 350 [[image:1735064488658-863.png||data-xwiki-image-style-alignment="center" data-xwiki-image-style-border="true" height="112" width="800"]]
Admin 11.1 351
352 In this section:
353
354 * Enable – a flag to enable the main contactor control;
355 * Algorithm – main contactor control algorithm:
356 ** Always on – contactor is always closed;
357 ** Automatic – contactor closes by internal charge and discharge algorithms;
358 ** On demand – contactor is closed by an external request;
359 * Time to keep the contactor closed before closing the others – a time for other contactors to be open after the main contactor is closed;
360 * Delay before opening the contactor – a time which is used to detect conditions for opening the contactor, s;
Admin 26.1 361 * Keep the contactor open until the device is restarted – a flag for keeping the main contactor open until the system is reset;
362 * Errors 1, 2 to open the main contactor – bitfields to choose the errors which will open the main contactor.
Admin 11.1 363
Admin 10.8 364 === Charging status ===
365
Admin 26.1 366 To change the parameters of charging process status, select the "Control → Charging status" section:
367
Admin 63.2 368 [[image:1760435790050-496.png||data-xwiki-image-style-alignment="center" data-xwiki-image-style-border="true" height="140" width="800"]]
Admin 26.1 369
Admin 47.2 370 In this section:
371
Admin 26.1 372 * Current to set the "Charging current present" – a current level to generate the "Charging current present" signal, A;
373 * Current to clear the "Charging current present" – a current level to clear the "Charging current present" signal, A;
Admin 46.1 374 * Voltage to clear the “Ready to charge” – a threshold U,,ocv,, (corrected due to current and cell resistance) voltage level on the cell, V; if the voltage of any cell is above this level, the “Ready to charge” (hence, the “Allow charging”) signal is cleared;
375 * Voltage to reset the “Ready to charge” – a tolerant U,,ocv,, (corrected due to current and cell resistance) voltage level on the cell, V; if all cell voltages are below the tolerant level, the “Ready to charge” (hence, the “Allow charging”) signal is set;
Admin 49.2 376 * Treat negative currents as zero currents for generating the "Ready to charge" signal – a flag to disable voltage correction for "Ready to charge" signal at discharging current;
Admin 26.1 377 * Delay before recharging – a time after which the previously opened the allow charging contactor closes again, minute; to disable the operation by timeout set "Delay before recharging" to 0;
Admin 63.3 378 * Check the 'Charge current limit' value to generate the 'Ready to charge' – a flag to enable check of "Charging current limit" to generate the "Ready to charge" signal;
Admin 65.1 379 * Charge current limit to clear the 'Ready to charge' – a threshold charging current limit value, A; if the limit is //above //this level, the “Ready to charge” signal is cleared;
380 * Charge current limit to set the 'Ready to charge' – a tolerant charging current limit value, A; if the limit is //below //this level, the “Ready to charge” signal is set;
Admin 26.1 381 * Errors 1, 2 to clear the "Ready to charge" – bitfields to choose the errors which will clear the "Ready to charge" signal.
Admin 10.8 382
Admin 11.3 383 (% class="box infomessage" %)
384 (((
Admin 12.2 385 **Note:** The "Allow charging" signal activates under two independent conditions:
Admin 11.3 386 1) the voltage on the cells reaches the “Voltage to reset the “Ready to charge"” level and
387 2) the "Delay before recharging" time has passed since the opening of the allow charging contactor.
388 )))
389
Admin 10.8 390 === Discharging status ===
391
Admin 31.1 392 To change the parameters of discharging process status, select the "Control → Discharging status" section:
Admin 26.1 393
Admin 63.2 394 [[image:1760435802140-274.png||data-xwiki-image-style-alignment="center" data-xwiki-image-style-border="true" height="129" width="800"]]
Admin 26.1 395
Admin 49.2 396 In this section:
397
Admin 26.1 398 * Current to set the "Discharging current present" – a current level to generate the "Discharging current present" signal, А;
399 * Current to clear the "Discharging current present" – a current level to clear the "Discharging current present" signal, А;
Admin 46.1 400 * Voltage to clear the “Ready to discharge” – a threshold U,,ocv,, (corrected due to current and cell resistance) voltage level on the cell, V; if the voltage of any cell is below this level, the “Ready to discharge” signal is cleared;
401 * Voltage to reset the “Ready to discharge” – a tolerant U,,ocv,, (corrected due to current and cell resistance) voltage level on the cell, V; if all cells voltages are above the tolerant level, the “Ready to discharge” signal is set;
Admin 49.2 402 * Treat positive currents as zero currents for generating the "Ready to discharge" signal – a flag to disable voltage correction for "Ready to discharge" signal at charging current;
Admin 63.5 403 * Check the 'Discharge current limit' value to generate the 'Ready to discharge' – a flag to enable check of "Discharging current limit" to generate the "Ready to discharge" signal;
404 * Discharge current limit to clear the 'Ready to discharge' – a threshold discharging current limit value, A; if the limit is //above //this level, the “Ready to discharge” signal is cleared;
Admin 64.1 405 * Discharge current limit to set the 'Ready to discharge' – a tolerant discharging current limit value, A; if the limit is //below //this level, the “Ready to discharge” signal is set;
Admin 26.1 406 * Errors 1, 2 to clear the "Ready to discharge" – bitfields to choose the errors which will clear the "Ready to discharge" signal.
Admin 10.8 407
Admin 31.1 408 === Precharge ===
Admin 10.8 409
Admin 26.1 410 The BMS Main 3 device can control the precharge contactor. The precharge contactor is used to charge the intermediate capacity with low current and usually placed with the limiting resistor in parallel to charging or discharging contactor.
Admin 10.8 411
Admin 28.2 412 BMS Main 3 device detects errors while pre-charging the load capacity by monitoring the current and voltage difference before and after contactors. Also BMS can measure the power dissipated on precharge resistor and generate an error if it greater than configured limit.
Admin 26.1 413
Admin 31.1 414 TBA
415
Admin 26.1 416 To change the parameters of precharge contactor, select the "Control → Precharge" section:
417
Admin 53.2 418 [[image:1750328428183-819.png||data-xwiki-image-style-alignment="center" data-xwiki-image-style-border="true" height="178" width="800"]]
Admin 26.1 419
420 * Precharge current threshold to finish precharging – a minimum current value at which precharging process assumed to be finished, A;
421 * Check voltages before and after contactors to finish precharging – a flag to check the voltages before and after contactors to ensure that precharge process has finished and it is allowed to close the discharging contactor;
422 * Minimum voltage difference to finish precharging – minimal voltage difference before and after contactors at which precharge process is meant to be finished, V;
Admin 53.8 423 * Keep the precharging relay closed until precharge is finished – a flag to ignore the Precharge time and wait precharging to finish before open precharge relay;
Admin 26.1 424 * Number of precharging attempts – maximum number of precharging attempts before setting the "Precharge error";
Admin 53.7 425 * Delay before current measurement – a delay before first current measurement after closing precharge, millisecond;
Admin 26.1 426 * Precharge time – a duration of closing the precharge contactor before closing the discharging contactor, millisecond;
427 * Relaxation between attempts – a duration between precharge attempts, millisecond;
428 * Check the power dissipated in the preacharge resistor - a flag to enable the calculation of power dissipated in precharge resistor;
429 * Precharge resistor resistance, Ohm;
430 * Maximum allowable power dissipated in the resistor, W;
431 * Delay before setting the "Precharge error" when checking power, millisecond;
432 * Delay before clearing the "Precharge error", second;
433 * Lock the "Precharge error" – a flag to block the error until the device is restarted.
434
Admin 36.1 435 “Precharge error” generation conditions if any of the following is true:
Admin 26.1 436
Admin 36.1 437 * the precharge current does not decrease during the "Precharge time" after "Number of precharging attempts";
438 * voltages before and after contactors are not equal during the "Precharge time" after "Number of precharging attempts";
Admin 26.1 439 * power dissipated on the precharge resistor is above the maximum value during the “Delay before setting the 'Precharge error' when checking power” time.
440
Admin 29.2 441 (% class="box warningmessage" %)
Admin 26.1 442 (((
Admin 29.2 443 Behavior of contactors at “Precharge error” is configured in corresponding contactor settings!
Admin 26.1 444 )))
445
Admin 3.1 446 === Charge ===
Admin 1.3 447
448 There are two contactors that serve charging the battery: a charging contactor and an allow charging contactor. With the help of the allow charging contactor, the BMS commands the charger to start or stop charging.
449
450 The device supports three charge control algorithms:
451
452 * Always on – charging is always allowed;
453 * On charger connected – charging is allowed when there is a signal “Charger connected”;
454 * On charge request – charging is allowed when there is a signal “Charge request”.
455
Admin 33.7 456 If the "**Always on**" algorithm is selected, the charging contactor and the allow charging contactor are always closed. If at least one of the errors from the "Errors 1, 2 ..." bitfields appears or one of the signals:
Admin 1.3 457
Admin 12.9 458 * Service reset;
459 * Power down request;
Admin 12.8 460 * Inhibit charging,
Admin 1.3 461
Admin 33.7 462 both contactors are open (no current flows).
Admin 1.3 463
464 When the algorithm "**On charger connected**" is selected, the control is performed as follows:
465
Admin 33.7 466 * If there is a signal “Charger connected” and there are no errors (see the "Errors 1, 2 ..." bitfields), then through the delay time T,,on,, the charging contactor and the allow charging contactor close;
Admin 1.3 467 * If the signal “Charger connected” disappears, the allow charging contactor opens and after the delay time T,,off,, the charging contactor opens;
468 * If in the process of charging the voltage on the cell exceeds the “Ready to charge” level, the allow charging contactor opens (while the charging contactor remains closed);
Admin 33.7 469 * If errors from the "Errors 1, 2 ..." bitfields occur the charging contactor and allow charging contactor open.
Admin 1.3 470
471 When the "**On charge request**" algorithm selected, the control is performed as follows:
472
Admin 33.7 473 * If there is a signal “Charge request” and there are no errors (see the "Errors 1, 2 ..." bitfields), then through the delay time T,,on,, the charging contactor and the allow charging contactor close;
Admin 1.3 474 * If the signal “Charge request” disappears, the allow charging contactor opens and after the delay time T,,off,, the charging contactor opens;
475 * If in the process of charging the voltage on the cell exceeds the “Ready to charge” level, the allow charging contactor opens (while the charging contactor remains closed);
Admin 33.8 476 * If errors from the "Errors 1, 2 ..." bitfields occur the charging contactor and allow charging contactor open.
Admin 1.3 477
Admin 12.8 478 (% class="box infomessage" %)
479 (((
Admin 29.5 480 **Note: **when errors occur in the system, the **Charge **contactor opens either immediately or with the delay T,,off,, (depends on the settings described below).
Admin 12.8 481 )))
Admin 1.3 482
483 To change the parameters of the battery charge control algorithm, select the "Control → Charge" section:
484
Admin 12.3 485 [[image:1735063563460-549.png||data-xwiki-image-style-alignment="center" data-xwiki-image-style-border="true" height="262" width="800"]]
Admin 1.3 486
487 In this section:
488
489 * Enable – a flag to activate the charge control;
490 * Algorithm:
491 ** Always on – charging is always allowed;
492 ** On charger connected – charging is allowed when there is a signal “Charger connected”;
493 ** On charge request – charging is allowed when there is a signal “Charge request”;
Admin 12.6 494 * Allow charging only when the "Ready to charge" signal is set – charging contactor will open if "Ready to charge" signal is cleared;
Admin 1.3 495 * Delay before starting charging – a time delay T,,on,, before closing the charging contactor and the allow charging contactor, millisecond;
496 * Delay before stopping charging – a time delay T,,off,, before opening the charging contactor, millisecond;
Admin 42.5 497 * Control the precharging contactor – a flag that allows control of the precharging contactor while closing the charge contactor (see [[Precharge>>path:#HPrecharge]]);
Admin 12.8 498 * Errors 1, 2 to open the charging contactor – bitfields to choose the errors which will open the charging contactor;
Admin 1.3 499 * Use custom delays before stopping charging (on errors) – a flag to enable manual settings of time delays T,,off,, for specific errors;
Admin 12.8 500 * Custom delay: <error> – delay for specific error, millisecond;
Admin 1.3 501 * Switch off the charging contactor on errors without delay – a flag to protectively open the charging contactor without a delay. In the opposite case, when an error is detected, the charging contactor opens always with the delay “Delay before stopping charging”;
502
Admin 3.1 503 === Discharge ===
Admin 1.3 504
505 The device controls the discharging contactor to connect battery to the load.
506
507 The device supports three algorithms to control battery discharging:
508
509 * Always on – load is always connected;
510 * On charger disconnected – load is connected when there is no signal “Charger connected”;
511 * On discharge request – load is connected when there is signal “Discharge request”.
512
Admin 33.8 513 When the algorithm "**Always on**" is selected, the discharging contactor is always closed. If at least one of the errors from the "Errors 1, 2 ..." bitfields appears or one of the signals:
Admin 1.3 514
515 * Service reset
516 * Power down request
517 * Inhibit discharging
518
519 the discharging contactor opens.
520
521 If the algorithm "**On charger disconnected**" is selected, the control is performed as follows:
522
Admin 33.8 523 * if there is no signal “Charger connected”, the charging contactor is open and there are no errors (see the "Errors 1, 2 ..." bitfields), then through the delay time T,,on,, the discharging contactor closes;
524 * If the signal “Charger connected” appears or errors occur (see the "Errors 1, 2 ..." bitfields), then after the delay time T,,off,, the discharging contactor opens.
Admin 1.3 525
526 When the "**On discharge request**" algorithm selected, the control is performed as follows:
527
Admin 33.9 528 * if there is signal “Discharge request”, the charging contactor is open and there are no errors (see the "Errors 1, 2 ..." bitfields), then through the delay time T,,on,, the discharging contactor closes;
Admin 33.8 529 * If the signal “Discharge request” disappears or errors occur (see the "Errors 1, 2 ..." bitfields), then after the delay time T,,off,, the discharging contactor opens.
Admin 1.3 530
Admin 12.9 531 (% class="box infomessage" %)
532 (((
Admin 29.5 533 **Note: **when errors occur in the system, the **Discharge **contactor opens either immediately or with the delay T,,off,, (depends on the settings described below).
Admin 12.9 534 )))
Admin 1.3 535
536 To change the parameters of the battery discharge control algorithm, select the "Control → Discharge" section:
537
Admin 13.2 538 [[image:1735064038329-836.png||data-xwiki-image-style-alignment="center" data-xwiki-image-style-border="true" height="273" width="800"]]
Admin 1.3 539
540 In this section:
541
542 * Enable – a flag to activate the discharge control;
543 * Algorithm:
544 ** Always on – load is always connected;
545 ** On charger disconnected – load is connected when there is no signal “Charger connected”;
546 ** On discharge request – load is connected when there is signal “Discharge request”;
Admin 13.3 547 * Allow charging only when the "Ready to discharge" signal is set – discharging contactor will open if "Ready to discharge" signal is cleared;
Admin 1.3 548 * Delay before starting discharging – a time delay T,,on,, before closing the discharging contactor, millisecond;
549 * Delay before stopping discharging – a time delay T,,off,, before opening the discharging contactor, millisecond;
Admin 42.6 550 * Control the precharging contactor – a flag that allows control of the precharging contactor while closing the discharge contactor (see [[Precharge>>doc:||anchor="HPrecharge"]]);
Admin 13.2 551 * Errors 1, 2 to open the discharging contactor – bitfields to choose the errors which will open the discharging contactor;
Admin 1.3 552 * Use custom delays before stopping discharging (on errors) – a flag to enable manual settings of time delays T,,off,, for specific errors;
553 * Custom delay: <error> – specific error delay, millisecond;
554 * Switch off the discharging contactor on errors without delay – a flag to protectively open the discharging contactor without a delay. In the opposite case, when an error is detected, the discharging contactor opens always with the delay “Delay before stopping discharging”.
555
Admin 3.1 556 === Charge/Discharge ===
Admin 1.3 557
Admin 27.3 558 The BMS Main 3 device can control the charge/discharge contactor, which combines algorithms of charging and discharging contactor.
Admin 1.3 559
Admin 27.3 560 Charge/Discharge contactor has three algorithms of operation:
Admin 27.2 561
Admin 28.1 562 * Dependent (on Charging and Discharging signals) - Charge/Discharge contactor depends on Charge and Discharge algorithms and their signals and behaves as Charging contactor if Charging signal is set, otherwise – as Discharging contactor;
563 * Independent (Always) - Charge/Discharge contactor is always closed if there is no errors;
Admin 28.3 564 * Independent (on Charge request or Discharge request) - Charge/Discharge contactor is based on its own controller that listen to Charge and Discharge requests and closes if one of these signals occurs.
Admin 27.3 565
Admin 31.1 566 TBA
567
Admin 29.2 568 (% class="box infomessage" %)
569 (((
Admin 29.5 570 **Note: **when errors occur in the system, the **Charge/Discharge **contactor opens either immediately or with the delay T,,off,, (depends on the settings described below).
Admin 29.2 571 )))
572
Admin 1.3 573 The charging/discharging contactor control is configured in the “Control – Charge/Discharge” section:
574
Admin 27.2 575 [[image:1735122153011-166.png||data-xwiki-image-style-alignment="center" data-xwiki-image-style-border="true" height="162" width="800"]]
Admin 1.3 576
577 In this section:
578
579 * Enable – a flag to enable the charge/discharge controller.
Admin 28.1 580 * Algorithm:
581 ** Dependent (on Charging and Discharging signals) - Charge/Discharge contactor depends on Charge and Discharge algorithms and their signals and behaves as Charging contactor if Charging signal is set, otherwise – as Discharging contactor;
582 ** Independent (Always) - Charge/Discharge contactor is always closed if there is no errors;
583 ** Independent (on Charge request or Discharge request);
584 * Delay before starting charging or discharging, millisecond;
585 * Delay before stopping charging or discharging, millisecond;
586 * Control the precharging contactor – a flag that enables control of precharging contactor while closing the charge/discharge contactor;
587 * Emulate the "Charging" and "Discharging" signals – a flag to enable generation of "Charging" and "Discharging" signals when closing charge/discharge contactor;
588 * Errors 1, 2 to prevent CHARGING through charging/discharging contactor, Errors 1, 2 to prevent DISCHARGING through charging/discharging contactor – bitfields to choose the errors which will open the charging/discharging contactor. This bitfields are combined by bitwise OR and intended to separate settings for charging and discharging processes;
589 * Errors 1, 2 which affect the contactor only if battery CHARGING is detected – a bitfield to choose the errors which will trigger only if charging current is present. This bitfield is combined with "Errors 1, 2 to prevent CHARGING through charging/discharging contactor" by bitwise AND;
590 * Errors 1, 2 which affect the contactor only if battery DISCHARGING is detected – a bitfield to choose the errors which will trigger only if discharging current is present. This bitfield is combined with "Errors 1, 2 to prevent DISCHARGING through charging/discharging contactor" by bitwise AND;
591 * Switch off the charging/discharging contactor on errors without delay – a flag to protectively open the charging/discharging contactor without a delay. In the opposite case, when an error is detected, the charging/discharging contactor opens always with the delay “Delay before stopping discharging”.
Admin 1.3 592
Admin 3.1 593 === Discharge (AUX) ===
Admin 1.3 594
595 The BMS Main 3 device can control the power supply of external equipment using the auxiliary (AUX) discharging contactor. An example of external equipment can be an inverter that converts DC to AC to power a service laptop and other devices.
596
597 The power supply circuit of the external equipment using the auxiliary (AUX) discharging contactor is independent of the battery load circuit. The closing and opening of the auxiliary (AUX) discharging contactor is performed according to its program.
598
599 If the power supply function of the external equipment is enabled, the auxiliary (AUX) discharging contactor closes. The opening of this contactor occurs on three independent conditions:
600
601 * the battery has low SOC;
602 * the battery voltage is out of range;
Admin 33.10 603 * the errors are detected (configured in the "Errors 1, 2 ..." bitfields).
Admin 1.3 604
605 To change the parameters of the powering of external equipment, select the "Control → Discharge (AUX)" section:
606
Admin 26.1 607 [[image:1735066190419-838.png||data-xwiki-image-style-alignment="center" data-xwiki-image-style-border="true" height="161" width="800"]]
Admin 1.3 608
609 In this section:
610
611 * Enable – a flag to activate the auxiliary discharge control;
612 * Switch off the discharging (AUX) contactor if the SOC is too low;
613 * Minimum SOC – a minimum SOC value, when reached, the auxiliary (AUX) discharging contactor opens, %;
614 * Tolerant SOC – a permissive SOC value, upon reaching which the auxiliary (AUX) discharging contactor re-closes, %;
Admin 38.1 615 * Switch off the discharging (AUX) contactor if the cell voltage is out of the range;
616 * Minimum cell voltage, V;
617 * Maximum cell voltage, V;
Admin 1.3 618 * Switch off the discharging (AUX) contactor if the battery voltage is out of the range;
Admin 26.1 619 * Minimum battery voltage, V;
620 * Maximum battery voltage, V;
Admin 42.7 621 * Errors 1, 2 to open the auxiliary discharging contactor – bitfields to choose the errors which will open the auxiliary discharging contactor.
Admin 1.3 622
Admin 3.1 623 === Cell balancing ===
Admin 1.4 624
625 Balancing makes the voltage of all cells equal to the minimum cell voltage.
626
627 The following balancing rules are supported:
628
629 * when the battery is charging (current I > 0) and time after until the battery is relaxed;
630 * when the battery is charging (current I > 0) or when the battery is in a state of relaxation;
631 * always (regardless of battery state).
632
633 A balancing resistor is connected to the cell if the following conditions are simultaneously met:
634
635 * the voltage on the cell is higher than the balancing start voltage;
Admin 39.2 636 * the difference between the voltage on the cell and the minimum voltage among the battery cells is greater than the balancing start threshold;
Admin 1.4 637
638 A balancing resistor is disconnected from the cell if any of the following conditions are met:
639
Admin 41.1 640 * the voltage on the cell is less than the balancing stop voltage;
Admin 1.4 641 * the difference between the voltage on the cell and the minimum voltage among the battery cells is less than the balancing stop threshold.
642
Admin 42.7 643 (% class="box infomessage" %)
644 (((
Admin 1.4 645 If the “High logic temperature” occurs, then the balancing of the cells connected to the overheated BMS Logic device will not be performed.
Admin 42.7 646 )))
Admin 1.4 647
648 The BMS Main 3 can enable the cell balancing by the external “Balancing request” signal. Balancing process will be started to cells which the voltage is higher than the balancing start voltage and the difference between the cell voltage and the minimum voltage among all the cells is greater than the balancing stop threshold.
649
Admin 40.1 650 BMS Main 3 can force a cell balancing, if its voltage is higher than estimated value.
Admin 39.2 651
Admin 1.4 652 To change the cell balancing parameters, select the "Control → Cell balancing" section:
653
Admin 26.1 654 [[image:1735065702806-422.png||data-xwiki-image-style-alignment="center" data-xwiki-image-style-border="true" height="130" width="800"]]
Admin 1.4 655
656 In this section:
657
658 * Enable – a flag to enable cell balancing;
659 * Balancing rule:
660 ** Balance on charge – balancing is performed while and after the charging (in the “Charge ON” and “Charge OFF” states);
661 ** Balance on charge or relaxed - balancing is performed while and after the charging and in the relaxed state (in “Charge ON”, “Charge OFF”, “Relaxed (after charging)” and “Relaxed (after discharging)” states);
662 ** Balance always – balancing is always performed regardless the battery state;
Admin 26.1 663 * Balancing condition:
664 ** Automatic – balancing will be performed automatically if needed conditions are met;
665 ** On balancing request – balancing will start only if a remote request is received. In this case cells will start to balance regardless the "Voltage deviation to start balancing" value;
Admin 1.4 666 * Minimum cell voltage to start balancing, V;
667 * Voltage deviation to start balancing;
668 * Voltage deviation to stop balancing;
Admin 28.4 669 * Voltage for forced balancing – if cell voltage is above this value, it will start discharging through balancing resistor;
Admin 26.1 670 * Maximum allowable temperature of BMS Logic devices, ºC;
Admin 1.4 671 * Command to discharge all cells – a flag to force the balancing of all cells.
672
Admin 3.1 673 === Series balancing ===
Admin 1.4 674
675 The BMS Main 3 device supports work with two independent (galvanically unrelated) cell series. To monitor the status of two series, two current sensors are used. A series of cells must be equivalent: they must have the same number of cells and the same capacity.
676
677 Since the series of cells can operate at different loads, they must be balanced. For this, the BMS Main 3 provides two signals to power switches: “Balancing series 1” and “Balancing series 2”, as well as a combined algorithm that considers both the voltage of each series and the charge that these series gave load. The “Balancing series 1” and “Balancing series 2” signals are used to connect high-power balancing resistors in parallel with cell series 1 and 2.
678
679 When charging the battery, balancing is performed based on the voltage of the series. A balancing resistor is connected to the cell series if:
680
681 * the series voltage is higher than the start balancing voltage;
682 * the difference between the voltage of a series of cells and the minimum voltage among the battery series is greater than the balancing threshold.
683
684 When the battery is discharging (work on load), balancing is turned on if one of the series gives the load a charge (Ah), which is more by the amount Qthr of the charge given off by another series.
685
686 To change the series balancing parameters, select the "Control → Series balancing" section:
687
Admin 2.1 688 [[image:1733322892811-410.png||data-xwiki-image-style-alignment="center" data-xwiki-image-style-border="true" height="126" width="800"]]
Admin 1.4 689
690 In this section:
691
692 * Enable – a flag to enable series balancing;
693 * Number of Logics in a series;
694 * Minimum series voltage to start balancing, V;
695 * Balancing threshold, V;
696 * Coulomb threshold – the difference of the charges Qthr, given by a series of cells, above which balancing to be started, Ah;
697 * Period – a period to reset of charge counters for each series (to avoid accumulation of error), second;
Admin 2.1 698 * Do not sum series voltages – a flag to disable the summing of series voltages.3
Admin 1.4 699
Admin 3.1 700 === Power down ===
Admin 1.4 701
702 The BMS Main 3 device can shut down itself if the battery voltage is low or the battery is idle for a long time.
703
704 Shutting down the battery system is performed according to the following conditions:
705
706 * the battery voltage is below the minimum level;
707 * the “Charger connected” signal is cleared for 60 seconds.
708
709 The BMS Main 3 device also shuts down the battery if it stays in the “Charging OFF”, “Discharging OFF”, “Relaxed (after charging)” or “Relaxed (after discharging)” for the configured time.
710
711 To change the parameters of the power down control, select the "Control → Power down" section:
712
Admin 2.1 713 [[image:1733322892813-562.png||data-xwiki-image-style-alignment="center" data-xwiki-image-style-border="true" height="103" width="800"]]
Admin 1.4 714
715 In this section:
716
717 * Minimum voltage to power down – a minimum voltage level of the battery below which the BMS commands to shut down the battery, V;
718 * Idle time to power down – a time of battery inactivity after which the battery is shut down, minute;
719 * Wait the "Power up/down request" is cleared (on startup) – a flag to enable delay for clearing the “Power up/down request” signal while starting the BMS.
720 * Power down if KEYRUN and CHARGE_ON are cleared – a flag to power down the device if KEYRUN and CHARGE_ON signals are cleared;
721 * Delay before setting the internal power down signal – a delay before turning off the device power when removing KEYRUN and CHARGE_ON or receiving the “Power down request” command, ms.
722
Admin 3.1 723 === Heater ===
Admin 1.4 724
725 To change the parameters of the heater control algorithm, select the "Control → Heater" section:
726
Admin 2.1 727 [[image:1733322901923-144.png||data-xwiki-image-style-alignment="center" data-xwiki-image-style-border="true" height="108" width="800"]]
Admin 1.4 728
729 In this section:
730
731 * Enable – a flag to enable the heater control;
732 * Minimum cell temperature, °C;
733 * Tolerant cell temperature, °C;
734 * Delay before starting the heater, millisecond;
735 * Delay before stopping the heater, millisecond;
736 * Switch off the heater on errors (Undervoltage, Overcurrent, High temperature, Short circuit or Critical error).
737
738 As a result of operating the heating algorithm, the “Heater” signal is generated.
739
740 Conditions for signal generation:
741
742 * the minimum temperature among all cells of the battery is less than the “Minimum cell temperature” value during the “Delay before starting the heater” time.
743
744 Conditions for clearing the signal:
745
746 * the minimum temperature among all cells of the battery is greater than the “Tolerant cell temperature” value during the “Delay before stopping the heater” time.
747
Admin 39.1 748 (% class="box infomessage" %)
749 (((
Admin 33.10 750 If there is the "Heater" signal, the heater contactor closes and/or a signal is set to the corresponding digital output.
Admin 39.1 751 )))
Admin 1.4 752
Admin 3.1 753 === Cooler ===
Admin 1.4 754
755 To change the parameters of the cooler control algorithm, select the "Control → Cooler" section:
756
Admin 2.1 757 [[image:1733322901924-962.png||data-xwiki-image-style-alignment="center" data-xwiki-image-style-border="true" height="107" width="800"]]
Admin 1.4 758
759 In this section:
760
761 * Enable – a flag to enable the cooler control;
762 * Maximum cell temperature, °C;
763 * Tolerant cell temperature, °C;
764 * Delay before starting the cooler, millisecond;
765 * Delay before stopping the cooler, millisecond;
766 * Switch off the cooler contactor on errors (Undervoltage, Overcurrent, Low temperature, Short circuit or Critical error).
767
768 As a result of operating the cooling algorithm, the "Cooler" signal is generated.
769
770 Conditions for signal generation:
771
772 * the maximum temperature among all cells of the battery is greater than the “Maximum cell temperature” value during the “Delay before starting the cooler” time.
773
774 Conditions for clearing the signal:
775
776 * the maximum temperature among all cells of the battery is less than the “Tolerant cell temperature” value during the “Delay before stopping the cooler” time.
777
Admin 39.1 778 (% class="box infomessage" %)
779 (((
Admin 33.10 780 If there is the "Cooler" signal, the cooler contactor closes and/or a signal is set to the corresponding digital output.
Admin 39.1 781 )))
Admin 1.4 782
Admin 3.1 783 === High voltage ===
Admin 1.4 784
785 The BMS Main 3 device has an ability to measure high voltages before and after contactors.
786
787 To change the parameters of high voltage fault, select the "Control → High voltage" section:
788
Admin 3.1 789 [[image:1733322914683-203.png||data-xwiki-image-style-alignment="center" data-xwiki-image-style-border="true" height="87" width="800"]]
Admin 1.4 790
791 In this section:
792
793 * Enable – a flag to enable High voltage control;
794 * Delay before clearing the High voltage fault, second;
795 * Lock the High voltage fault.
796
797 The BMS Main 3 implements a self-diagnostics of high-voltage measurement lines. If measurement line breaks or high-voltage polarity is wrong, “High voltage fault” is generated.
798
Admin 26.1 799 (% class="box warningmessage" %)
800 (((
Admin 29.5 801 If there is the “High voltage fault”, **the “Critical error” is generated.**
Admin 26.1 802 )))
Admin 1.4 803
Admin 3.1 804 === Cell analysis ===
Admin 1.4 805
806 The battery discharge characteristic – the dependence Uocv = Uocv(DOD) – is used to determine the tabular dependence Uocv = Uocv(SOC, t°C), which is necessary for calculating the battery charge level.
807
808 The BMS Main 3 device can automatically determine the battery discharge characteristic.
809
810 Before starting the process of determining the discharge characteristic, it is necessary to prepare a BMS:
811
812 1. Charge the battery.
813 1. Connect a resistive load to the discharging contactor, which will provide a discharge current of 0.5C (where C is the cell capacitance).
814
815 To configure parameters for determining the discharge characteristic of the battery, select the "Control → Cell analysis" section:
816
Admin 3.1 817 [[image:1733322914685-558.png||data-xwiki-image-style-alignment="center" data-xwiki-image-style-border="true" height="107" width="800"]]
Admin 1.4 818
819 In this section:
820
821 * Enable – a flag to enable cell analysis;
822 * Discharge step, Ah;
823 * Delta voltage – a maximum allowable voltage drop for the cell, V;
824 * Logic index, Cell index – a position of the analyzed cell;
825 * Analyse the most discharged cell – a flag to analyse of the least charged cell (in this case, the values “Logic index” and “Cell index” are ignored).
826
827 Discharge step should be set equal to
828
829 Discharge step= С/21,
830
831 where C is the cell capacity.
832
833 The discharge characteristic will be constructed for the given cell (its position is determined by the fields “Logic index” and “Cell index”).
834
835 The algorithm for determining the discharge characteristic of the battery will be started if the “Enable” flag is set. From this moment, the control of the discharge contactor is performed by this algorithm.
836
837 Algorithm steps:
838
839 1. DOD = 0.
840 1. Opening the discharging contactor.
841 1. Waiting for the relaxation of the battery.
842 1. Measuring Uocv = U.
843 1. Saving the point of the discharge characteristic (Q, U,,OCV,,).
844 1. Closing of the discharging contactor. DOD,,1,, = DOD + Discharge step, U,,1,, = U
845 1. If DOD = DOD,,1,, or U < (U,,1,, – Delta voltage), then go to step 2.
846 1. If the "Undervoltage" error is detected, then the end of the algorithm.
847
848 During the operation of the algorithm, a file with the name "CELLANALYSIS.TXT" in the CSV format will be created on the SD card.
849
850 File structure:
851
852 |**Time**|**DOD**|**Logic**|**Cell**|**OCV**|**Resistance**
853 |**10.11.2017 12:28:34**|0.0|1|1|4.180|0.080000
854 |**...**|...| |…|...|...
855
856 Parameter names:
857
858 * Time – date and time;
859 * DOD – depth of discharge, Ah;
860 * Logic - position of the Logic device to which the analyzed cell is connected;