Wiki source code of 3.3 Control

Version 30.2 by Admin on 2024/12/26 16:40

Hide last authors
Admin 4.1 1 (% data-numbered-headings-start="3" style="--numbered-headings-start: 2;font-size: 0px;color: rgba(0, 0, 0, 0.0);margin-bottom: 0px; margin-top: 0px;" %)
2 = Settings =
Admin 1.3 3
Admin 4.1 4 (% data-numbered-headings-start="3" style="--numbered-headings-start: 2;font-size: 0px;color: rgba(0, 0, 0, 0.0);margin-bottom: 0px; margin-top: 0px;" %)
5 == Control ==
Admin 3.1 6
7 === Common settings ===
8
Admin 1.3 9 To change the common BMS settings, select the "Control → Common settings" section:
10
Admin 6.2 11 [[image:1735054851946-552.png||data-xwiki-image-style-alignment="center" data-xwiki-image-style-border="true" height="105" width="800"]]
Admin 1.3 12
13 In this section:
14
15 * Cell capacity – nominal capacity of cells, Ah;
16 * Cell resistance – nominal (maximum) internal resistance of the cells, Ohm;
17 * Relax time (after charging) – a relaxation time after charging, second;
18 * Relax time (atfer discharging) – a relaxation time after discharging, second;
Admin 6.2 19 * Reset parameters – a command to reset cells state of charge, capacity, and resistance;
20 * Method of calculating the battery voltage:
Admin 6.4 21 ** Summation of cell voltages – the overall voltage is calculated as on sum of all cells in the battery;
Admin 6.5 22 ** Using voltage before contactors – the overall voltage is estimated as voltage before contactors measured by BMS.
Admin 1.3 23
24 The values “Capacity”, “Resistance”, “Cycles” are used to calculate the SOC of cells and the battery.
25
26 The values of “Relax time” are used to determine the state of the battery. If the battery is in a state of relaxation, the system recalculates the voltage on the cells to the state of charge of the battery.
27
28 The “Reset parameters” will reset:
29
30 * state of charge (new cell SOC values will be calculated based on cell voltage and “Uocv (open-circuit voltage) table”: in the “Control → SOC estimation” section);
31 * cell resistance to “Cell resistance” value;
32 * battery capacity to “Cell capacity” value.
33
34 The “Reset parameters” command is used for starting-up and adjustment of the battery.
35
Admin 3.1 36 === SOC estimation ===
Admin 1.3 37
38 The BMS Main 3 device calculates the state of charge of the battery (SOC) using two algorithms:
39
40 * by open circuit voltage;
41 * by voltage and current.
42
43 It is recommended to use the algorithm of calculation of SOC by voltage and current.
44
45 To change the estimation algorithm for calculating the battery SOC, select the "Control → SOC estimation → Algorithm" section:
46
47
Admin 8.2 48 [[image:1735056107942-306.png||data-xwiki-image-style-alignment="center" data-xwiki-image-style-border="true" height="141" width="800"]]
49
Admin 1.3 50 The following estimation algorithms supported:
51
52 * Voltage – by open circuit voltage;
53 * Current and voltage (simplified) – recommended for LFP cells;
54 * Current and voltage (enhanced) – recommended for NMC cells.
55
56 The **“Voltage”** SOC calculation algorithm calculates cells SOC based on the tabular dependence Uocv = Uocv(SOC, t °C).
57
58 The **“Current and voltage (simplified)”** SOC calculation algorithm works as follows:
59
60 * if I = 0, the battery is in the state of relaxation and the cell voltage Uocv is outside the [U,,ocv[point 1],,; U,,ocv[point 2],,], the SOC calculation is based on the tabular dependency Uocv = Uocv(SOC, t °C);
61 * in any other cases, the SOC value is proportional to the charge (coulomb) passed through the battery (current time integral).
62
63 The **“Current and voltage (enhanced)” **SOC calculation algorithm differs from the simplified algorithm by online correction of the effective capacity. When using this algorithm, it is necessary to fine tune the tabular dependence Uocv = Uocv (SOC, t °C).
64
65 To change the algorithm for calculating the Final SOC, select the "Control → SOC estimation → Final SOC" section:
66
Admin 2.1 67 [[image:1733322611551-852.png||data-xwiki-image-style-alignment="center" data-xwiki-image-style-border="true" height="148" width="800"]]
Admin 1.3 68
69 The following calculation methods are supported (“Final SOC”):
70
71 * Minimal SOC – the battery SOC is assumed to be the minimum SOC among the cells;
72 * Average SOC – the battery SOC is taken equal to the arithmetic average of the cell SOC;
Admin 9.7 73 * Min-Max SOC – the battery SOC is calculated based on the minimum and maximum SOC of the cells. Final SOC will be a) 100% if any cell have 100% SOC, b) 0% if any cell have 0% SOC;
Admin 9.8 74 * Max-Min SOC – the battery SOC is calculated based on the minimum and maximum SOC of the cells. Final SOC will be a) 100% if all cells have 100% SOC, b) 0% if all cells have 0% SOC;
Admin 1.3 75
76 Other parameters:
77
78 * Scale the final SOC – a flag to scale the battery SOC by the following values;
79 * SOC corresponding to 0% – the battery SOC that sets to be 0%;
80 * SOC corresponding to 100% – the battery SOC that sets to be 100%.
81 * Uocv (open-circuit voltage) table – the dependence of the cell open circuit voltage Uocv on SOC and the cell temperature (selected for specific batteries);
82 * Linear zone - linear zone of the Uocv = Uocv(SOC, t°C) dependency, inside which the cell voltage changes insignificantly:
83 ** Linear zone: point 1 – starting point of the Uocv linear zone;
84 ** Linear zone: point 2 – ending point of the Uocv linear zone;
85 * Coulomb counting correction (temperature) – the dependence of battery capacity on temperature;
86 * Coulomb counting correction (cycles) – the dependence of battery capacity on the number of charge-discharge cycles.
87
Admin 3.1 88 === SOC correction ===
Admin 1.3 89
Admin 5.1 90 The BMS Main 3 device can recalculate the battery SOC after long-term storage or after long-term working in the case when the battery was not charged fully or discharged totally. Recalculation is done based on the tabular dependency Uocv = Uocv (SOC, t) (see [[SOC estimation>>doc:||anchor="HSOCestimation"]]).
Admin 1.3 91
92 To configure parameters for periodically correcting the battery state of charge, select the "Control → SOC correction" section:
93
Admin 2.1 94 [[image:1733322624656-766.png||data-xwiki-image-style-alignment="center" data-xwiki-image-style-border="true" height="121" width="800"]]
Admin 1.3 95
96 In this section:
97
98 * Enable – a flag to enable the SOC correction;
99 * Shutdown period – a time the battery is off, day. If the BMS detects on its startup that it was off during the “Shutdown period” time, the BMS recalculates the battery state of charge based on the tabular dependency Uocv = Uocv (SOC, t);
100 * Correction period – a period of correcting the battery SOC, day. If the BMS detects that the last correction was more than the “Correction period” ago, the BMS recalculates the battery state of charge based on the tabular dependency Uocv = Uocv (SOC, t) and tunes it gradually during the “SOC change time”.
101 * SOC change time – a duration of the linear changing the battery SOC to the value calculated by the correction algorithm, minute;
102 * Ignore the linear zone – a flag to ignore linear SOC zone while correction (recommended to be unset);
103 * Last correction timestamp – time when last correction was made.
104
Admin 3.1 105 === Resistance estimation ===
Admin 1.3 106
107 Calculation of the resistance of cells is carried out in two ways. The first method is used when the battery passes from a relaxation state to a charge or discharge state, wherein the cell resistance value
108
Admin 10.6 109 {{formula fontSize="SMALL" imageType="PNG"}}
Admin 10.3 110 R = \frac{U-U_{ocv}}{I_{stable}}
111 {{/formula}}
Admin 1.3 112
Admin 10.3 113 where U — the cell voltage measured in the charge or discharge state, V; U,,ocv,, — cell voltage measured in the state of relaxation (before switching to the state of charge or discharge); I,,stable,, — stabilized current through the cell in the state of charge or discharge.
Admin 10.2 114
Admin 1.3 115 The second method is used for a stepwise change in the current through the cell, while the value of the cell resistance:
116
Admin 10.6 117 {{formula fontSize="SMALL"}}
Admin 10.5 118 R = \frac{U_2-U_1}{I_{stable2}-I_{stable1}}
119 {{/formula}}
Admin 1.3 120
Admin 10.5 121 provided that
122
Admin 10.6 123 {{formula fontSize="SMALL"}}
124 | I_{stable2}-I_{stable1} | > 0.2 × Qmax
Admin 10.4 125 {{/formula}}
Admin 10.3 126
Admin 10.6 127 where Q,,max,, — the maximum cell capacity,U,,2,, — voltage on the cell at the moment when the stabilized current I,,stable2,, is flowing through it; U,,1,, — the voltage on the cell at the moment when the stabilized current I,,stable1,, flowing through it.
Admin 1.3 128
129 The stabilized current I,,stable,, = I, if during the stabilization time the instantaneous current I is in the range from 0.95 × I to 1.05 × I.
130
131 To change parameters of the algorithm for calculating the cell resistance, select the "Control → Resistance estimation" section:
132
Admin 2.1 133 [[image:1733322624659-473.png||data-xwiki-image-style-alignment="center" data-xwiki-image-style-border="true" height="108" width="800"]]
Admin 1.3 134
135 In this section:
136
137 * Current stabilization time, millisecond;
138 * Maximum calculation period – maximum time between resistance measurements. If more time has elapsed since the last determination of the stabilized current I,,stable,, than is determined in this field, the resistance calculation is not performed, second;
139 * Maximum resistance factor – the coefficient of calculation of the maximum acceptable resistance of the cell;
140 * Minimum SOC – minimum cell SOC value for resistance calculation;
141 * Maximum SOC – maximum cell SOC value for resistance calculation.
142
Admin 10.7 143 The calculated resistance is accepted by the system as valid (and therefore updated) if its value is in the range from Resistance / 2 to “Maximum resistance factor” × Resistance, where "Resistance" is the nominal resistance of the cell (see [[Common settings>>doc:||anchor="HCommonsettings"]]). If the calculated resistance value is greater than the value (Maximum resistance factor × Resistance), the updated resistance value will be equal to the value (Maximum resistance factor × Resistance).
Admin 1.3 144
Admin 3.1 145 === Low SOC (signal) ===
Admin 1.3 146
147 To change the parameters of the generation a signal about low battery level, select the "Control → Low SOC (signal)" section:
148
Admin 2.1 149 [[image:1733322624660-513.png||data-xwiki-image-style-alignment="center" data-xwiki-image-style-border="true" height="116" width="800"]]
Admin 1.3 150
151 In this section:
152
153 * Enable – a flag to enable signal generation;
154 * Minimum SOC, %;
155 * Tolerant SOC, %;
156 * Delay before setting the signal, second;
157 * Delay before clearing the signal, second;
158 * Lock – lock the signal until the device is reset.
159
160 Signal generation conditions:
161
162 * the battery SOC is less than the “Minimum SOC” value during the “Delay before setting the signal” time.
163
164 Conditions for clearing the signal:
165
166 * the battery SOC is greater than the “Tolerant SOC” during the “Delay before clearing the signal” time.
167
Admin 30.2 168 (% class="box infomessage" %)
169 (((
Admin 1.3 170 The "Low SOC signal" is indicative and can be output to a discrete output or a power switch.
Admin 30.2 171 )))
Admin 1.3 172
Admin 3.1 173 === High charging current (signal) ===
Admin 1.3 174
175 To change the parameters of the generation high-current signal, select the "Control → High charging current (signal)" section:
176
Admin 2.1 177 [[image:1733322624661-915.png||data-xwiki-image-style-alignment="center" data-xwiki-image-style-border="true" height="107" width="800"]]
Admin 1.3 178
179 In this section:
180
181 * Enable – a flag to enable signal generation;
182 * Maximum charging current, А;
183 * Tolerant charging current, А;
184 * Delay before setting the signal, second;
185 * Delay before clearing the signal, second;
186 * Lock – lock the signal until the device is reset.
187
188 Signal generation conditions:
189
190 * the measured current is greater than the “Maximum charging current” value during the “Delay before setting the signal” time.
191
192 Conditions for clearing the signal:
193
194 * the measured current is less than the “Tolerant charging current” value during the “Delay before clearing the signal” time.
195
Admin 30.2 196 (% class="box infomessage" %)
197 (((
Admin 1.3 198 The "High charging current" signal is indicative and can be output to a discrete output or a power switch.
Admin 30.2 199 )))
Admin 1.3 200
Admin 3.1 201 === Charge map ===
Admin 1.3 202
203 The BMS Main 3 device calculates the maximum allowable charge current values in respect to SOC, battery temperature, contactor temperature and cell voltage.
204
205 Calculated current values are sent to a charger or an intellectual load over the CAN bus. External devices based on received data provide correct battery operation.
206
207 To configure parameters for determining the charge current limit, select the "Control → Charge map" section:
208
Admin 26.1 209 [[image:1735064362593-844.png||data-xwiki-image-style-alignment="center" data-xwiki-image-style-border="true" height="153" width="800"]]
Admin 1.3 210
211 In this section:
212
213 * Enable – a flag to start calculation of the charge current limit;
214 * Maximum charge current – a maximum allowable value of the charge current (under normal conditions), A;
215 * Rate of change – a rate of change the current limit to a new value (0 is for immediate change), A/s;
216 * Option 1: Limit charge current by the battery SOC and temperature – a flag to enable correction of maximum allowable charging current Kcs depending on SOC and battery temperature;
217 * Option 1: SOC x Temperature x Factor – the dependence of the correction factor on SOC and battery temperature;
218 * Option 2: Limit charge current by the contactor temperature – a flag to enable correction of maximum allowable charging current Kcc depending on contactor temperature;
219 * Option 2: Contactor temperature x Factor – the dependence of the correction factor on SOC and contactor temperature;
220 * Option 3: Limit charge current by the maximum cell voltage - a flag to enable correction of maximum allowable charging current Kcv depending on maximum cell voltage;
221 * Option 3: Cell voltage x Factor – the dependence of the correction factor on maximum cell voltage;
222 * Option 4: Limit charge current by the cell temperature - a flag to enable correction of maximum allowable charging current Kct depending on maximum cell temperature;
223 * Option 4: Cell temperature x Factor – the dependence of the correction factor on maximum cell temperature.
224
225 Value of the charge current limit at given SOC, temperature, contactors temperature, maximum cell voltage and maximum cell temperature is calculated as follows:
226
Admin 30.2 227 **Charging current limit = Maximum charging current × Kcs × Kcc × Kcv × Kct**
Admin 1.3 228
Admin 3.1 229 === Discharge map ===
Admin 1.3 230
231 The BMS Main 3 device calculates the maximum allowable discharge current values in respect to SOC, battery temperature, contactor temperature and cell voltage.
232
233 Calculated current values are sent to a charger or an intellectual load over the CAN bus.
234
235 To configure parameters for determining the discharge current limit, select the "Control → Discharge map" section:
236
Admin 26.1 237 [[image:1735064399985-526.png||data-xwiki-image-style-alignment="center" data-xwiki-image-style-border="true" height="152" width="800"]]
Admin 1.3 238
239 In this section:
240
241 * Enable – a flag to start calculation of the discharge current limit;
242 * Maximum discharge current – a maximum allowable value of the discharge current (under normal conditions), A;
243 * Rate of change – a rate of change the current limit to a new value (0 is for immediate change), A/s;
244 * Option 1: Limit discharging current by the battery SOC and temperature – a flag to enable correction of maximum allowable discharging current Kds depending on SOC and temperature;
245 * Option 1: SOC x Temperature x Factor – the dependence of the correction factor on SOC and battery temperature;
246 * Option 2: Limit discharge current by the contactor temperature – a flag to enable correction of maximum allowable discharging current Kdc depending on contactor temperature;
247 * Option 2: Contactor temperature x Factor – the dependence of the correction factor on SOC and contactor temperature;
248 * Option 3: Limit discharge current by the cell voltage - a flag to enable correction of maximum allowable discharging current Kdv depending on minimum cell voltage;
249 * Option 3: Cell voltage x Factor – the dependence of the correction factor on minimum cell voltage;
250 * Option 4: Limit discharge current by the cell temperature - a flag to enable correction of maximum allowable discharging current Kdt depending on maximum cell temperature;
251 * Option 4: Cell voltage x Factor – the dependence of the correction factor on minimum cell temperature.
252
253 Value of the discharge current limit at given SOC, temperature, contactors temperature, minimum cell voltage and maximum cell temperature is calculated as follows:
254
Admin 30.2 255 **Discharging current limit = Maximum discharging current × Kds × Kdc × Kdv × Kdt**
Admin 1.3 256
Admin 3.1 257 === Charge map (PEAK & CONTINUOUS) ===
Admin 1.3 258
259 The BMS Main 3 has an alternative algorithm for the maximum allowed charging current based on peak and continuous battery operating modes.
260
261 To configure parameters for determining the charge current limit, select the "Control → Charge map (PEAK & CONTINUOUS)" section:
262
Admin 26.1 263 [[image:1735064434321-430.png||data-xwiki-image-style-alignment="center" data-xwiki-image-style-border="true" height="124" width="800"]]
Admin 1.3 264
265 In this section:
266
267 * Enable – a flag to start calculation of the charge current limit;
268 * Maximum PEAK charge current – a maximum peak charge current (under normal conditions), A;
269 * Maximum CONTINUOUS charge current – a maximum continuous charge current (under normal conditions), A;
270 * PEAK: SOC x Temperature x Factor – the dependence of the correction factor for peak current K,,cp,, on SOC and battery temperature;
271 * CONTINUOUS: SOC x Temperature x Factor – the dependence of the correction factor for continuous current K,,cc,, on SOC and battery temperature;
272 * PEAK time – a time for peak current to be allowed, s;
273 * Sliding time – a time of linear change of the maximum charging current from peak to continuous and from continuous to peak value, ms;
274 * Waiting time – a time for peak current to be prohibited, s.
275
276 The maximum charging current value equals to the peak or continuous current according to the following diagram:
277
Admin 2.1 278 [[image:1733322717451-608.png||data-xwiki-image-style-alignment="center"]]
Admin 1.3 279
280 I,,peak,, = Maximum PEAK charge current × K,,cp,,
281
282 I,,continuous,, = Maximum CONTINUOUS charge current × K,,cc,,
283
Admin 3.1 284 === Discharge map (PEAK & CONTINUOUS) ===
Admin 1.3 285
286 The BMS Main 3 has an alternative algorithm for the maximum allowed discharging current based on peak and continuous battery operating modes.
287
288 To configure parameters for determining the discharge current limit, select the "Control → Discharge map (PEAK & CONTINUOUS)" section:
289
Admin 26.1 290 [[image:1735064454708-345.png||data-xwiki-image-style-alignment="center" data-xwiki-image-style-border="true" height="124" width="800"]]
Admin 1.3 291
292 In this section:
293
294 * Enable – a flag to start calculation of the discharge current limit;
295 * Maximum PEAK discharge current – a maximum peak discharge current (under normal conditions), A;
296 * Maximum CONTINUOUS discharge current – a maximum continuous discharge current (under normal conditions), A;
297 * PEAK: SOC x Temperature x Factor – the dependence of the correction factor for peak current K,,dp,, on SOC and battery temperature;
298 * CONTINUOUS: SOC x Temperature x Factor – the dependence of the correction factor for continuous current K,,dc,, on SOC and battery temperature;
299 * PEAK time – a time for peak current to be allowed, s;
300 * Sliding time – a time of linear change of the maximum charging current from peak to continuous and from continuous to peak value, ms;
301 * Waiting time – a time for peak current to be prohibited, s.
302
303 The maximum discharging current value equals to the peak or continuous current according to following diagram:
304
Admin 2.1 305 [[image:1733322753429-968.png||data-xwiki-image-style-alignment="center"]]
Admin 1.3 306
307 I,,peak,, = Maximum PEAK discharge current × K,,dp,,
308
309 I,,continuous,, = Maximum CONTINUOUS discharge current × K,,dc,,
310
Admin 10.8 311 === Main contactor ===
312
Admin 11.1 313 The BMS Main 3 device controls the main contactor. The main contactor is usually placed in the common (minus) battery line for opening the charge and discharge circuits in case of sealing of the charging or discharging contactors.
Admin 10.8 314
Admin 11.1 315 The Main contactor algorithm supports the following modes:
316
317 * Always on;
318 * Automatic;
319 * On demand.
320
321 In “Always on” mode main contactor closes if all the following is true:
322
323 * Charging contactor is open;
324 * Discharging contactor is open;
325 * There are no errors from the list below:
326 ** Overcurrent;
327 ** Undervoltage;
328 ** Overvoltage;
329 ** High temperature (CH);
330 ** High temperature (DCH);
331 ** Unallowable charging;
332 ** Critical error.
333
334 In “Always on” mode main contactor opens if all the following is true:
335
336 * Charging contactor is open;
337 * Discharging contactor is open;
338 * There is an error from the list below:
339 ** Overcurrent;
340 ** Undervoltage;
341 ** Overvoltage;
342 ** High temperature (CH);
343 ** High temperature (DCH);
344 ** Unallowable charging;
345 ** Critical error.
346
347 In “Automatic” mode, the main contactor closes by internal charging and discharging algorithms at the same time with Precharging, Charging and Discharging contactors.
348
349 In “On demand” mode, the main contactor closes by external the “Close Main contactor” request.
350
Admin 29.5 351 (% class="box infomessage" %)
352 (((
353 **Note: **when errors occur in the system, the **Main **contactor opens either immediately or with the delay T,,off,, (depends on the settings described below).
354 )))
355
Admin 11.1 356 To change the parameters of the main contactor, select the "Control → Main contactor" section:
357
Admin 26.1 358 [[image:1735064488658-863.png||data-xwiki-image-style-alignment="center" data-xwiki-image-style-border="true" height="112" width="800"]]
Admin 11.1 359
360 In this section:
361
362 * Enable – a flag to enable the main contactor control;
363 * Algorithm – main contactor control algorithm:
364 ** Always on – contactor is always closed;
365 ** Automatic – contactor closes by internal charge and discharge algorithms;
366 ** On demand – contactor is closed by an external request;
367 * Time to keep the contactor closed before closing the others – a time for other contactors to be open after the main contactor is closed;
368 * Delay before opening the contactor – a time which is used to detect conditions for opening the contactor, s;
Admin 26.1 369 * Keep the contactor open until the device is restarted – a flag for keeping the main contactor open until the system is reset;
370 * Errors 1, 2 to open the main contactor – bitfields to choose the errors which will open the main contactor.
Admin 11.1 371
Admin 10.8 372 === Charging status ===
373
Admin 26.1 374 To change the parameters of charging process status, select the "Control → Charging status" section:
375
376 [[image:1735064935499-941.png||data-xwiki-image-style-alignment="center" data-xwiki-image-style-border="true" height="110" width="800"]]In this section:
377
378 * Current to set the "Charging current present" – a current level to generate the "Charging current present" signal, A;
379 * Current to clear the "Charging current present" – a current level to clear the "Charging current present" signal, A;
Admin 11.3 380 * Voltage to clear the “Ready to charge” – a threshold voltage level on the cell, V; if the voltage of any cell is above this level, the “Ready to charge” (hence, the “Allow charging”) signal is cleared;
381 * Voltage to reset the “Ready to charge” – a tolerant voltage level on the cell, V; if all cell voltages are below the tolerant level, the “Ready to charge” (hence, the “Allow charging”) signal is set;
Admin 26.1 382 * Delay before recharging – a time after which the previously opened the allow charging contactor closes again, minute; to disable the operation by timeout set "Delay before recharging" to 0;
383 * Errors 1, 2 to clear the "Ready to charge" – bitfields to choose the errors which will clear the "Ready to charge" signal.
Admin 10.8 384
Admin 11.3 385 (% class="box infomessage" %)
386 (((
Admin 12.2 387 **Note:** The "Allow charging" signal activates under two independent conditions:
Admin 11.3 388 1) the voltage on the cells reaches the “Voltage to reset the “Ready to charge"” level and
389 2) the "Delay before recharging" time has passed since the opening of the allow charging contactor.
390 )))
391
Admin 10.8 392 === Discharging status ===
393
Admin 26.1 394 To change the parameters of charging process status, select the "Control → Discharging status" section:
395
396 [[image:1735064980481-209.png||data-xwiki-image-style-alignment="center" data-xwiki-image-style-border="true" height="102" width="800"]]In this section:
397
398 * Current to set the "Discharging current present" – a current level to generate the "Discharging current present" signal, А;
399 * Current to clear the "Discharging current present" – a current level to clear the "Discharging current present" signal, А;
Admin 12.3 400 * Voltage to clear the “Ready to discharge” – a threshold voltage level on the cell, V; if the voltage of any cell is below this level, the “Ready to discharge” signal is cleared;
401 * Voltage to reset the “Ready to discharge” – a tolerant voltage level on the cell, V; if all cells voltages are above the tolerant level, the “Ready to discharge” signal is set;
Admin 26.1 402 * Errors 1, 2 to clear the "Ready to discharge" – bitfields to choose the errors which will clear the "Ready to discharge" signal.
Admin 10.8 403
Admin 30.2 404 === Precharge () ===
Admin 10.8 405
Admin 26.1 406 The BMS Main 3 device can control the precharge contactor. The precharge contactor is used to charge the intermediate capacity with low current and usually placed with the limiting resistor in parallel to charging or discharging contactor.
Admin 10.8 407
Admin 28.2 408 BMS Main 3 device detects errors while pre-charging the load capacity by monitoring the current and voltage difference before and after contactors. Also BMS can measure the power dissipated on precharge resistor and generate an error if it greater than configured limit.
Admin 26.1 409
410 To change the parameters of precharge contactor, select the "Control → Precharge" section:
411
412 [[image:1735065073836-743.png||data-xwiki-image-style-alignment="center" data-xwiki-image-style-border="true" height="160" width="800"]]
413
414 * Precharge current threshold to finish precharging – a minimum current value at which precharging process assumed to be finished, A;
415 * Check voltages before and after contactors to finish precharging – a flag to check the voltages before and after contactors to ensure that precharge process has finished and it is allowed to close the discharging contactor;
416 * Minimum voltage difference to finish precharging – minimal voltage difference before and after contactors at which precharge process is meant to be finished, V;
417 * Number of precharging attempts – maximum number of precharging attempts before setting the "Precharge error";
418 * Precharge time – a duration of closing the precharge contactor before closing the discharging contactor, millisecond;
419 * Relaxation between attempts – a duration between precharge attempts, millisecond;
420 * Check the power dissipated in the preacharge resistor - a flag to enable the calculation of power dissipated in precharge resistor;
421 * Precharge resistor resistance, Ohm;
422 * Maximum allowable power dissipated in the resistor, W;
423 * Delay before setting the "Precharge error" when checking power, millisecond;
424 * Delay before clearing the "Precharge error", second;
425 * Lock the "Precharge error" – a flag to block the error until the device is restarted.
426
427 “Precharge error” generation conditions:
428
429 * the precharge current does not decrease after "Number of precharging attempts";
430 * voltages before and after contactors are not equal after "Number of precharging attempts";
431 * power dissipated on the precharge resistor is above the maximum value during the “Delay before setting the 'Precharge error' when checking power” time.
432
Admin 29.2 433 (% class="box warningmessage" %)
Admin 26.1 434 (((
Admin 29.2 435 Behavior of contactors at “Precharge error” is configured in corresponding contactor settings!
Admin 26.1 436 )))
437
Admin 3.1 438 === Charge ===
Admin 1.3 439
440 There are two contactors that serve charging the battery: a charging contactor and an allow charging contactor. With the help of the allow charging contactor, the BMS commands the charger to start or stop charging.
441
442 The device supports three charge control algorithms:
443
444 * Always on – charging is always allowed;
445 * On charger connected – charging is allowed when there is a signal “Charger connected”;
446 * On charge request – charging is allowed when there is a signal “Charge request”.
447
448 If the "**Always on**" algorithm is selected, the charging contactor and the allow charging contactor are always closed. If at least one of the errors appears:
449
450 * Overvoltage;
451 * Overcurrent;
452 * High temperature (CH);
453 * Low temperature (CH);
454 * HYG offline (optional);
455 * Combilift offline (optional);
456 * Spirit offline (optional);
457 * Spirit charger error (optional);
458 * Short circuit (optional);
459 * High contactor temperature (optional);
460 * CH contactor cycles error;
461 * Precharge error (optional);
462 * Critical error
463
464 or one of the signals:
465
Admin 12.9 466 * Service reset;
467 * Power down request;
Admin 12.8 468 * Inhibit charging,
Admin 1.3 469
470 both contactors are open (no current flows).
471
472 When the algorithm "**On charger connected**" is selected, the control is performed as follows:
473
474 * If there is a signal “Charger connected” and there are no errors (see the list above), then through the delay time T,,on,, the charging contactor and the allow charging contactor close;
475 * If the signal “Charger connected” disappears, the allow charging contactor opens and after the delay time T,,off,, the charging contactor opens;
476 * If in the process of charging the voltage on the cell exceeds the “Ready to charge” level, the allow charging contactor opens (while the charging contactor remains closed);
477 * If errors in the list above occur the charging contactor and allow charging contactor open.
478
479 When the "**On charge request**" algorithm selected, the control is performed as follows:
480
481 * If there is a signal “Charge request” and there are no errors (see the list above), then through the delay time T,,on,, the charging contactor and the allow charging contactor close;
482 * If the signal “Charge request” disappears, the allow charging contactor opens and after the delay time T,,off,, the charging contactor opens;
483 * If in the process of charging the voltage on the cell exceeds the “Ready to charge” level, the allow charging contactor opens (while the charging contactor remains closed);
484 * If errors in the list above occur the charging contactor and allow charging contactor open.
485
Admin 12.8 486 (% class="box infomessage" %)
487 (((
Admin 29.5 488 **Note: **when errors occur in the system, the **Charge **contactor opens either immediately or with the delay T,,off,, (depends on the settings described below).
Admin 12.8 489 )))
Admin 1.3 490
491 To change the parameters of the battery charge control algorithm, select the "Control → Charge" section:
492
Admin 12.3 493 [[image:1735063563460-549.png||data-xwiki-image-style-alignment="center" data-xwiki-image-style-border="true" height="262" width="800"]]
Admin 1.3 494
495 In this section:
496
497 * Enable – a flag to activate the charge control;
498 * Algorithm:
499 ** Always on – charging is always allowed;
500 ** On charger connected – charging is allowed when there is a signal “Charger connected”;
501 ** On charge request – charging is allowed when there is a signal “Charge request”;
Admin 12.6 502 * Allow charging only when the "Ready to charge" signal is set – charging contactor will open if "Ready to charge" signal is cleared;
Admin 1.3 503 * Delay before starting charging – a time delay T,,on,, before closing the charging contactor and the allow charging contactor, millisecond;
504 * Delay before stopping charging – a time delay T,,off,, before opening the charging contactor, millisecond;
Admin 12.10 505 * Control the precharging contactor – a flag that allows control of the precharging contactor while closing the charge contactor;
Admin 12.8 506 * Errors 1, 2 to open the charging contactor – bitfields to choose the errors which will open the charging contactor;
Admin 1.3 507 * Use custom delays before stopping charging (on errors) – a flag to enable manual settings of time delays T,,off,, for specific errors;
Admin 12.8 508 * Custom delay: <error> – delay for specific error, millisecond;
Admin 1.3 509 * Switch off the charging contactor on errors without delay – a flag to protectively open the charging contactor without a delay. In the opposite case, when an error is detected, the charging contactor opens always with the delay “Delay before stopping charging”;
510
Admin 3.1 511 === Discharge ===
Admin 1.3 512
513 The device controls the discharging contactor to connect battery to the load.
514
515 The device supports three algorithms to control battery discharging:
516
517 * Always on – load is always connected;
518 * On charger disconnected – load is connected when there is no signal “Charger connected”;
519 * On discharge request – load is connected when there is signal “Discharge request”.
520
521 When the algorithm "**Always on**" is selected, the discharging contactor is always closed. If at least one of the errors appears:
522
523 * Undervoltage;
524 * Overvoltage (optional);
525 * Overcurrent;
526 * High temperature (DCH);
527 * Low temperature (DCH) (optional);
528 * HYG offline (optional);
529 * Combilift offline (optional);
530 * Spirit offline (optional);
531 * Spirit charger error (optional);
532 * Short circuit (optional);
533 * High contactor temperature (optional);
534 * Unallowable charging;
535 * DCH contactor cycles error;
536 * Precharge error (optional);
537 * Critical error
538
539 or one of the signals:
540
541 * Service reset
542 * Power down request
543 * Inhibit discharging
544
545 the discharging contactor opens.
546
547 If the algorithm "**On charger disconnected**" is selected, the control is performed as follows:
548
549 * if there is no signal “Charger connected”, the charging contactor is open and there are no errors (see the list above), then through the delay time T,,on,, the discharging contactor closes;
550 * If the signal “Charger connected” appears or errors occur (see the list above), then after the delay time T,,off,, the discharging contactor opens.
551
552 When the "**On discharge request**" algorithm selected, the control is performed as follows:
553
554 * if there is signal “Discharge request”, the charging contactor is open and there are no errors (see the list above), then through the delay time T,,on,, the discharging contactor closes;
555 * If the signal “Discharge request” disappears or errors occur (see the list above), then after the delay time T,,off,, the discharging contactor opens.
556
Admin 12.9 557 (% class="box infomessage" %)
558 (((
Admin 29.5 559 **Note: **when errors occur in the system, the **Discharge **contactor opens either immediately or with the delay T,,off,, (depends on the settings described below).
Admin 12.9 560 )))
Admin 1.3 561
562 The device supports controlling the precharging contactor. The duration of switching on the precharging contactor before closing the discharging (load) contactor is adjusted.
563
564 To change the parameters of the battery discharge control algorithm, select the "Control → Discharge" section:
565
Admin 13.2 566 [[image:1735064038329-836.png||data-xwiki-image-style-alignment="center" data-xwiki-image-style-border="true" height="273" width="800"]]
Admin 1.3 567
568 In this section:
569
570 * Enable – a flag to activate the discharge control;
571 * Algorithm:
572 ** Always on – load is always connected;
573 ** On charger disconnected – load is connected when there is no signal “Charger connected”;
574 ** On discharge request – load is connected when there is signal “Discharge request”;
Admin 13.3 575 * Allow charging only when the "Ready to discharge" signal is set – discharging contactor will open if "Ready to discharge" signal is cleared;
Admin 1.3 576 * Delay before starting discharging – a time delay T,,on,, before closing the discharging contactor, millisecond;
577 * Delay before stopping discharging – a time delay T,,off,, before opening the discharging contactor, millisecond;
Admin 12.10 578 * Control the precharging contactor – a flag that allows control of the precharging contactor while closing the discharge contactor;
Admin 13.2 579 * Errors 1, 2 to open the discharging contactor – bitfields to choose the errors which will open the discharging contactor;
Admin 1.3 580 * Use custom delays before stopping discharging (on errors) – a flag to enable manual settings of time delays T,,off,, for specific errors;
581 * Custom delay: <error> – specific error delay, millisecond;
582 * Switch off the discharging contactor on errors without delay – a flag to protectively open the discharging contactor without a delay. In the opposite case, when an error is detected, the discharging contactor opens always with the delay “Delay before stopping discharging”.
583
Admin 3.1 584 === Charge/Discharge ===
Admin 1.3 585
Admin 27.3 586 The BMS Main 3 device can control the charge/discharge contactor, which combines algorithms of charging and discharging contactor.
Admin 1.3 587
Admin 27.3 588 Charge/Discharge contactor has three algorithms of operation:
Admin 27.2 589
Admin 28.1 590 * Dependent (on Charging and Discharging signals) - Charge/Discharge contactor depends on Charge and Discharge algorithms and their signals and behaves as Charging contactor if Charging signal is set, otherwise – as Discharging contactor;
591 * Independent (Always) - Charge/Discharge contactor is always closed if there is no errors;
Admin 28.3 592 * Independent (on Charge request or Discharge request) - Charge/Discharge contactor is based on its own controller that listen to Charge and Discharge requests and closes if one of these signals occurs.
Admin 27.3 593
Admin 29.2 594 (% class="box infomessage" %)
595 (((
Admin 29.5 596 **Note: **when errors occur in the system, the **Charge/Discharge **contactor opens either immediately or with the delay T,,off,, (depends on the settings described below).
Admin 29.2 597 )))
598
Admin 1.3 599 The charging/discharging contactor control is configured in the “Control – Charge/Discharge” section:
600
Admin 27.2 601 [[image:1735122153011-166.png||data-xwiki-image-style-alignment="center" data-xwiki-image-style-border="true" height="162" width="800"]]
Admin 1.3 602
603 In this section:
604
605 * Enable – a flag to enable the charge/discharge controller.
Admin 28.1 606 * Algorithm:
607 ** Dependent (on Charging and Discharging signals) - Charge/Discharge contactor depends on Charge and Discharge algorithms and their signals and behaves as Charging contactor if Charging signal is set, otherwise – as Discharging contactor;
608 ** Independent (Always) - Charge/Discharge contactor is always closed if there is no errors;
609 ** Independent (on Charge request or Discharge request);
610 * Delay before starting charging or discharging, millisecond;
611 * Delay before stopping charging or discharging, millisecond;
612 * Control the precharging contactor – a flag that enables control of precharging contactor while closing the charge/discharge contactor;
613 * Emulate the "Charging" and "Discharging" signals – a flag to enable generation of "Charging" and "Discharging" signals when closing charge/discharge contactor;
614 * Errors 1, 2 to prevent CHARGING through charging/discharging contactor, Errors 1, 2 to prevent DISCHARGING through charging/discharging contactor – bitfields to choose the errors which will open the charging/discharging contactor. This bitfields are combined by bitwise OR and intended to separate settings for charging and discharging processes;
615 * Errors 1, 2 which affect the contactor only if battery CHARGING is detected – a bitfield to choose the errors which will trigger only if charging current is present. This bitfield is combined with "Errors 1, 2 to prevent CHARGING through charging/discharging contactor" by bitwise AND;
616 * Errors 1, 2 which affect the contactor only if battery DISCHARGING is detected – a bitfield to choose the errors which will trigger only if discharging current is present. This bitfield is combined with "Errors 1, 2 to prevent DISCHARGING through charging/discharging contactor" by bitwise AND;
617 * Switch off the charging/discharging contactor on errors without delay – a flag to protectively open the charging/discharging contactor without a delay. In the opposite case, when an error is detected, the charging/discharging contactor opens always with the delay “Delay before stopping discharging”.
Admin 1.3 618
Admin 3.1 619 === Discharge (AUX) ===
Admin 1.3 620
621 The BMS Main 3 device can control the power supply of external equipment using the auxiliary (AUX) discharging contactor. An example of external equipment can be an inverter that converts DC to AC to power a service laptop and other devices.
622
623 The power supply circuit of the external equipment using the auxiliary (AUX) discharging contactor is independent of the battery load circuit. The closing and opening of the auxiliary (AUX) discharging contactor is performed according to its program.
624
625 If the power supply function of the external equipment is enabled, the auxiliary (AUX) discharging contactor closes. The opening of this contactor occurs on three independent conditions:
626
627 * the battery has low SOC;
628 * the battery voltage is out of range;
629 * the battery system errors are detected.
630
Admin 29.2 631 (% class="box infomessage" %)
632 (((
633 **Note: **when errors occur in the system, the **Discharge (AUX) **contactor opens either immediately or with the delay T,,off,, (depends on the settings described below).
634 )))
635
Admin 1.3 636 To change the parameters of the powering of external equipment, select the "Control → Discharge (AUX)" section:
637
Admin 26.1 638 [[image:1735066190419-838.png||data-xwiki-image-style-alignment="center" data-xwiki-image-style-border="true" height="161" width="800"]]
Admin 1.3 639
640 In this section:
641
642 * Enable – a flag to activate the auxiliary discharge control;
643 * Switch off the discharging (AUX) contactor if the SOC is too low;
644 * Minimum SOC – a minimum SOC value, when reached, the auxiliary (AUX) discharging contactor opens, %;
645 * Tolerant SOC – a permissive SOC value, upon reaching which the auxiliary (AUX) discharging contactor re-closes, %;
646 * Switch off the discharging (AUX) contactor if the battery voltage is out of the range;
647 * Minimum voltage – minimum battery voltage, V;
648 * Maximum voltage – maximum battery voltage, V;
Admin 26.1 649 * Switch off the discharging (AUX) contactor on errors – the auxiliary (AUX) discharging contactor opens if the following errors occur: Undervoltage, Overcurrent, High temperature (DCH), Short circuit, Critical error;
650 * Minimum battery voltage, V;
651 * Maximum battery voltage, V;
652 * Errors 1, 2 to open the auxiliary discharging contactor – bitfields to choose the errors which will open the auxiliary discharging contactor;
Admin 1.3 653
Admin 3.1 654 === Cell balancing ===
Admin 1.4 655
656 Balancing makes the voltage of all cells equal to the minimum cell voltage.
657
658 The following balancing rules are supported:
659
660 * when the battery is charging (current I > 0) and time after until the battery is relaxed;
661 * when the battery is charging (current I > 0) or when the battery is in a state of relaxation;
662 * always (regardless of battery state).
663
664 A balancing resistor is connected to the cell if the following conditions are simultaneously met:
665
666 * the voltage on the cell is higher than the balancing start voltage;
667 * the difference between the voltage on the cell and the minimum voltage among the battery cells is greater than the balancing start threshold.
668
669 A balancing resistor is disconnected from the cell if any of the following conditions are met:
670
671 * the voltage on the cell is less than the balancing start voltage;
672 * the difference between the voltage on the cell and the minimum voltage among the battery cells is less than the balancing stop threshold.
673
674 If the “High logic temperature” occurs, then the balancing of the cells connected to the overheated BMS Logic device will not be performed.
675
676 The BMS Main 3 can enable the cell balancing by the external “Balancing request” signal. Balancing process will be started to cells which the voltage is higher than the balancing start voltage and the difference between the cell voltage and the minimum voltage among all the cells is greater than the balancing stop threshold.
677
678 To change the cell balancing parameters, select the "Control → Cell balancing" section:
679
Admin 26.1 680 [[image:1735065702806-422.png||data-xwiki-image-style-alignment="center" data-xwiki-image-style-border="true" height="130" width="800"]]
Admin 1.4 681
682 In this section:
683
684 * Enable – a flag to enable cell balancing;
685 * Balancing rule:
686 ** Balance on charge – balancing is performed while and after the charging (in the “Charge ON” and “Charge OFF” states);
687 ** Balance on charge or relaxed - balancing is performed while and after the charging and in the relaxed state (in “Charge ON”, “Charge OFF”, “Relaxed (after charging)” and “Relaxed (after discharging)” states);
688 ** Balance always – balancing is always performed regardless the battery state;
689
Admin 26.1 690 [[image:1735065666891-686.png||data-xwiki-image-style-alignment="center" data-xwiki-image-style-border="true" height="132" width="800"]]
Admin 1.4 691
Admin 26.1 692 * Balancing condition:
693 ** Automatic – balancing will be performed automatically if needed conditions are met;
694 ** On balancing request – balancing will start only if a remote request is received. In this case cells will start to balance regardless the "Voltage deviation to start balancing" value;
Admin 1.4 695 * Minimum cell voltage to start balancing, V;
696 * Voltage deviation to start balancing;
697 * Voltage deviation to stop balancing;
Admin 28.4 698 * Voltage for forced balancing – if cell voltage is above this value, it will start discharging through balancing resistor;
Admin 26.1 699 * Maximum allowable temperature of BMS Logic devices, ºC;
Admin 1.4 700 * Command to discharge all cells – a flag to force the balancing of all cells.
701
Admin 3.1 702 === Series balancing ===
Admin 1.4 703
704 The BMS Main 3 device supports work with two independent (galvanically unrelated) cell series. To monitor the status of two series, two current sensors are used. A series of cells must be equivalent: they must have the same number of cells and the same capacity.
705
706 Since the series of cells can operate at different loads, they must be balanced. For this, the BMS Main 3 provides two signals to power switches: “Balancing series 1” and “Balancing series 2”, as well as a combined algorithm that considers both the voltage of each series and the charge that these series gave load. The “Balancing series 1” and “Balancing series 2” signals are used to connect high-power balancing resistors in parallel with cell series 1 and 2.
707
708 When charging the battery, balancing is performed based on the voltage of the series. A balancing resistor is connected to the cell series if:
709
710 * the series voltage is higher than the start balancing voltage;
711 * the difference between the voltage of a series of cells and the minimum voltage among the battery series is greater than the balancing threshold.
712
713 When the battery is discharging (work on load), balancing is turned on if one of the series gives the load a charge (Ah), which is more by the amount Qthr of the charge given off by another series.
714
715 To change the series balancing parameters, select the "Control → Series balancing" section:
716
Admin 2.1 717 [[image:1733322892811-410.png||data-xwiki-image-style-alignment="center" data-xwiki-image-style-border="true" height="126" width="800"]]
Admin 1.4 718
719 In this section:
720
721 * Enable – a flag to enable series balancing;
722 * Number of Logics in a series;
723 * Minimum series voltage to start balancing, V;
724 * Balancing threshold, V;
725 * Coulomb threshold – the difference of the charges Qthr, given by a series of cells, above which balancing to be started, Ah;
726 * Period – a period to reset of charge counters for each series (to avoid accumulation of error), second;
Admin 2.1 727 * Do not sum series voltages – a flag to disable the summing of series voltages.3
Admin 1.4 728
Admin 3.1 729 === Power down ===
Admin 1.4 730
731 The BMS Main 3 device can shut down itself if the battery voltage is low or the battery is idle for a long time.
732
733 Shutting down the battery system is performed according to the following conditions:
734
735 * the battery voltage is below the minimum level;
736 * the “Charger connected” signal is cleared for 60 seconds.
737
738 The BMS Main 3 device also shuts down the battery if it stays in the “Charging OFF”, “Discharging OFF”, “Relaxed (after charging)” or “Relaxed (after discharging)” for the configured time.
739
740 To change the parameters of the power down control, select the "Control → Power down" section:
741
Admin 2.1 742 [[image:1733322892813-562.png||data-xwiki-image-style-alignment="center" data-xwiki-image-style-border="true" height="103" width="800"]]
Admin 1.4 743
744 In this section:
745
746 * Minimum voltage to power down – a minimum voltage level of the battery below which the BMS commands to shut down the battery, V;
747 * Idle time to power down – a time of battery inactivity after which the battery is shut down, minute;
748 * Wait the "Power up/down request" is cleared (on startup) – a flag to enable delay for clearing the “Power up/down request” signal while starting the BMS.
749 * Power down if KEYRUN and CHARGE_ON are cleared – a flag to power down the device if KEYRUN and CHARGE_ON signals are cleared;
750 * Delay before setting the internal power down signal – a delay before turning off the device power when removing KEYRUN and CHARGE_ON or receiving the “Power down request” command, ms.
751
Admin 3.1 752 === Heater ===
Admin 1.4 753
754 To change the parameters of the heater control algorithm, select the "Control → Heater" section:
755
Admin 2.1 756 [[image:1733322901923-144.png||data-xwiki-image-style-alignment="center" data-xwiki-image-style-border="true" height="108" width="800"]]
Admin 1.4 757
758 In this section:
759
760 * Enable – a flag to enable the heater control;
761 * Minimum cell temperature, °C;
762 * Tolerant cell temperature, °C;
763 * Delay before starting the heater, millisecond;
764 * Delay before stopping the heater, millisecond;
765 * Switch off the heater on errors (Undervoltage, Overcurrent, High temperature, Short circuit or Critical error).
766
767 As a result of operating the heating algorithm, the “Heater” signal is generated.
768
769 Conditions for signal generation:
770
771 * the minimum temperature among all cells of the battery is less than the “Minimum cell temperature” value during the “Delay before starting the heater” time.
772
773 Conditions for clearing the signal:
774
775 * the minimum temperature among all cells of the battery is greater than the “Tolerant cell temperature” value during the “Delay before stopping the heater” time.
776
777 If there is the "Heater" signal, the heater contactor closes and/or a signal is output to the corresponding digital output.
778
Admin 3.1 779 === Cooler ===
Admin 1.4 780
781 To change the parameters of the cooler control algorithm, select the "Control → Cooler" section:
782
Admin 2.1 783 [[image:1733322901924-962.png||data-xwiki-image-style-alignment="center" data-xwiki-image-style-border="true" height="107" width="800"]]
Admin 1.4 784
785 In this section:
786
787 * Enable – a flag to enable the cooler control;
788 * Maximum cell temperature, °C;
789 * Tolerant cell temperature, °C;
790 * Delay before starting the cooler, millisecond;
791 * Delay before stopping the cooler, millisecond;
792 * Switch off the cooler contactor on errors (Undervoltage, Overcurrent, Low temperature, Short circuit or Critical error).
793
794 As a result of operating the cooling algorithm, the "Cooler" signal is generated.
795
796 Conditions for signal generation:
797
798 * the maximum temperature among all cells of the battery is greater than the “Maximum cell temperature” value during the “Delay before starting the cooler” time.
799
800 Conditions for clearing the signal:
801
802 * the maximum temperature among all cells of the battery is less than the “Tolerant cell temperature” value during the “Delay before stopping the cooler” time.
803
804 If there is the "Cooler" signal, the cooler contactor closes and/or a signal is output to the corresponding digital output.
805
Admin 3.1 806 === High voltage ===
Admin 1.4 807
808 The BMS Main 3 device has an ability to measure high voltages before and after contactors.
809
810 To change the parameters of high voltage fault, select the "Control → High voltage" section:
811
Admin 3.1 812 [[image:1733322914683-203.png||data-xwiki-image-style-alignment="center" data-xwiki-image-style-border="true" height="87" width="800"]]
Admin 1.4 813
814 In this section:
815
816 * Enable – a flag to enable High voltage control;
817 * Delay before clearing the High voltage fault, second;
818 * Lock the High voltage fault.
819
820 The BMS Main 3 implements a self-diagnostics of high-voltage measurement lines. If measurement line breaks or high-voltage polarity is wrong, “High voltage fault” is generated.
821
Admin 26.1 822 (% class="box warningmessage" %)
823 (((
Admin 29.5 824 If there is the “High voltage fault”, **the “Critical error” is generated.**
Admin 26.1 825 )))
Admin 1.4 826
Admin 3.1 827 === Cell analysis ===
Admin 1.4 828
829 The battery discharge characteristic – the dependence Uocv = Uocv(DOD) – is used to determine the tabular dependence Uocv = Uocv(SOC, t°C), which is necessary for calculating the battery charge level.
830
831 The BMS Main 3 device can automatically determine the battery discharge characteristic.
832
833 Before starting the process of determining the discharge characteristic, it is necessary to prepare a BMS:
834
835 1. Charge the battery.
836 1. Connect a resistive load to the discharging contactor, which will provide a discharge current of 0.5C (where C is the cell capacitance).
837
838 To configure parameters for determining the discharge characteristic of the battery, select the "Control → Cell analysis" section:
839
Admin 3.1 840 [[image:1733322914685-558.png||data-xwiki-image-style-alignment="center" data-xwiki-image-style-border="true" height="107" width="800"]]
Admin 1.4 841
842 In this section:
843
844 * Enable – a flag to enable cell analysis;
845 * Discharge step, Ah;
846 * Delta voltage – a maximum allowable voltage drop for the cell, V;
847 * Logic index, Cell index – a position of the analyzed cell;
848 * Analyse the most discharged cell – a flag to analyse of the least charged cell (in this case, the values “Logic index” and “Cell index” are ignored).
849
850 Discharge step should be set equal to
851
852 Discharge step= С/21,
853
854 where C is the cell capacity.
855
856 The discharge characteristic will be constructed for the given cell (its position is determined by the fields “Logic index” and “Cell index”).
857
858 The algorithm for determining the discharge characteristic of the battery will be started if the “Enable” flag is set. From this moment, the control of the discharge contactor is performed by this algorithm.
859
860 Algorithm steps:
861
862 1. DOD = 0.
863 1. Opening the discharging contactor.
864 1. Waiting for the relaxation of the battery.
865 1. Measuring Uocv = U.
866 1. Saving the point of the discharge characteristic (Q, U,,OCV,,).
867 1. Closing of the discharging contactor. DOD,,1,, = DOD + Discharge step, U,,1,, = U
868 1. If DOD = DOD,,1,, or U < (U,,1,, – Delta voltage), then go to step 2.
869 1. If the "Undervoltage" error is detected, then the end of the algorithm.
870
871 During the operation of the algorithm, a file with the name "CELLANALYSIS.TXT" in the CSV format will be created on the SD card.
872
873 File structure:
874
875 |**Time**|**DOD**|**Logic**|**Cell**|**OCV**|**Resistance**
876 |**10.11.2017 12:28:34**|0.0|1|1|4.180|0.080000
877 |**...**|...| |…|...|...
878
879 Parameter names:
880
881 * Time – date and time;
882 * DOD – depth of discharge, Ah;
883 * Logic - position of the Logic device to which the analyzed cell is connected;