Changes for page 3.3 Control
Last modified by Admin on 2026/04/30 15:56
Summary
-
Page properties (1 modified, 0 added, 0 removed)
Details
- Page properties
-
- Content
-
... ... @@ -431,7 +431,7 @@ 431 431 * **Delay before clearing the "Precharge error"**, second; 432 432 * **Lock the "Precharge error"** – a flag to block the error until the device is restarted. 433 433 434 -“Precharge error” generat es if any of the following is true:434 +“Precharge error” generation conditions if any of the following is true: 435 435 436 436 * the precharge current does not decrease during the "Precharge time" after "Number of precharging attempts"; 437 437 * voltages before and after contactors are not equal during the "Precharge time" after "Number of precharging attempts"; ... ... @@ -448,27 +448,27 @@ 448 448 449 449 BMS Main 3 / BMS Main 2R supports three charge control algorithms: 450 450 451 -If the "**Always on**" algorithm is selected, the "Сhargingsignals"and the"Allow charging"signalsare always set. If at least one of the errors from the "Errors 1, 2 ..." bitfields appears or one of the signals:451 +If the "**Always on**" algorithm is selected, the charging contactor and the allow charging contactor are always closed. If at least one of the errors from the "Errors 1, 2 ..." bitfields appears or one of the signals: 452 452 453 453 * Service reset; 454 454 * Power down request; 455 455 * Inhibit charging, 456 456 457 -both signals arecleared.457 +both contactors are open (no current flows). 458 458 459 459 When the algorithm "**On charger connected**" is selected, the control is performed as follows: 460 460 461 -* If there is a signal “Charger connected” and there are no errors (see the "Errors 1, 2 ..." bitfields), then through the delay time T,,on,, the "Charging"and the"Allow charging"signal areset;462 -* If the signal “Charger connected” disappears or errors occur (see the "Errors 1, 2 ..." bitfields), the "Allow charging"signaliscleared and after the delay time T,,off,, the"Charging"signal iscleared.461 +* If there is a signal “Charger connected” and there are no errors (see the "Errors 1, 2 ..." bitfields), then through the delay time T,,on,, the charging contactor and the allow charging contactor close; 462 +* If the signal “Charger connected” disappears or errors occur (see the "Errors 1, 2 ..." bitfields), the allow charging contactor opens and after the delay time T,,off,, the charging contactor opens. 463 463 464 464 When the "**On charge request**" algorithm selected, the control is performed as follows: 465 465 466 -* If there is a signal “Charge request” and there are no errors (see the "Errors 1, 2 ..." bitfields), then through the delay time T,,on,, the "Charging"and the"Allow charging"signal areset;467 -* If the signal “Charge request” disappears or errors occur (see the "Errors 1, 2 ..." bitfields), the "Allow charging"signaliscleared and after the delay time T,,off,, the"Charging"signal iscleared;466 +* If there is a signal “Charge request” and there are no errors (see the "Errors 1, 2 ..." bitfields), then through the delay time T,,on,, the charging contactor and the allow charging contactor close; 467 +* If the signal “Charge request” disappears or errors occur (see the "Errors 1, 2 ..." bitfields), the allow charging contactor opens and after the delay time T,,off,, the charging contactor opens; 468 468 469 469 (% class="box infomessage" %) 470 470 ((( 471 -**Note: **when errors occur in the system, the ** "Charing"**signal isclearedeither immediately or with the delay T,,off,, (depends on the settings described below).471 +**Note: **when errors occur in the system, the **Charge **contactor opens either immediately or with the delay T,,off,, (depends on the settings described below). 472 472 ))) 473 473 474 474 To change the parameters of the battery charge control algorithm, select the "Control → Charge" section: ... ... @@ -493,21 +493,21 @@ 493 493 494 494 === Discharge === 495 495 496 -The BMS Main 3 / BMS Main 2R device con nectbattery totheload usingthe"Discharging"signal.496 +The BMS Main 3 / BMS Main 2R device controls the discharging contactor to connect battery to the load. 497 497 498 498 BMS Main 3 / BMS Main 2R supports three algorithms to control battery discharging: 499 499 500 -When the algorithm "**Always on**" is selected, the "Discharging"signalis always set. If at least one of the errors from the "Errors 1, 2 ..." bitfields appears or one of the signals:500 +When the algorithm "**Always on**" is selected, the discharging contactor is always closed. If at least one of the errors from the "Errors 1, 2 ..." bitfields appears or one of the signals: 501 501 502 502 * Service reset 503 503 * Power down request 504 504 * Inhibit discharging 505 505 506 -the "Discharging"signal iscleared.506 +the discharging contactor opens. 507 507 508 508 If the algorithm "**On charger disconnected**" is selected, the control is performed as follows: 509 509 510 -* if there is no “Charger connected” and"Charging"signals and there are no errors (see the "Errors 1, 2 ..." bitfields), then through the delay time T,,on,, the"Discharging"contactor closes;510 +* if there is no signal “Charger connected”, the charging contactor is open and there are no errors (see the "Errors 1, 2 ..." bitfields), then through the delay time T,,on,, the discharging contactor closes; 511 511 * If the signal “Charger connected” appears or errors occur (see the "Errors 1, 2 ..." bitfields), then after the delay time T,,off,, the discharging contactor opens. 512 512 513 513 When the "**On discharge request**" algorithm selected, the control is performed as follows: