... ... @@ -741,12 +741,11 @@
741 741  Conditions for signal generation:
742 742  
743 743  * the minimum temperature among all cells of the battery is less than the “Minimum cell temperature” value during the “Delay before starting the heater” time;
744 -* there are no errors from "Errors 1, 2..." bitfields.
744 +* Th
745 745  
746 746  Conditions for clearing the signal:
747 747  
748 -* the minimum temperature among all cells of the battery is greater than the “Tolerant cell temperature” value during the “Delay before stopping the heater” time;
749 -* there is an error from "Errors 1, 2..." bitfields.
748 +* the minimum temperature among all cells of the battery is greater than the “Tolerant cell temperature” value during the “Delay before stopping the heater” time.
750 750  
751 751  (% class="box infomessage" %)
752 752  (((
... ... @@ -766,19 +766,17 @@
766 766  * Tolerant cell temperature, °C;
767 767  * Delay before starting the cooler, millisecond;
768 768  * Delay before stopping the cooler, millisecond;
769 -* **Errors 1, 2 to open the heater** bitfields to choose the errors which will open the heater.
768 +* Switch off the cooler contactor on errors (Undervoltage, Overcurrent, Low temperature, Short circuit or Critical error).
770 770  
771 771  As a result of operating the cooling algorithm, the "Cooler" signal is generated.
772 772  
773 773  Conditions for signal generation:
774 774  
775 -* the maximum temperature among all cells of the battery is greater than the “Maximum cell temperature” value during the “Delay before starting the cooler” time;
776 -* there are no errors from "Errors 1, 2..." bitfields.
774 +* the maximum temperature among all cells of the battery is greater than the “Maximum cell temperature” value during the “Delay before starting the cooler” time.
777 777  
778 778  Conditions for clearing the signal:
779 779  
780 -* the maximum temperature among all cells of the battery is less than the “Tolerant cell temperature” value during the “Delay before stopping the cooler” time;
781 -* there is an error from "Errors 1, 2..." bitfields.
778 +* the maximum temperature among all cells of the battery is less than the “Tolerant cell temperature” value during the “Delay before stopping the cooler” time.
782 782  