Changes for page 3.3 Control
Last modified by Admin on 2026/04/30 15:56
Summary
-
Page properties (1 modified, 0 added, 0 removed)
Details
- Page properties
-
- Content
-
... ... @@ -15,7 +15,7 @@ 15 15 * **Cell capacity** – nominal capacity of cells, Ah; 16 16 * **Cell resistance** – nominal (maximum) internal resistance of the cells, Ohm; 17 17 * **Connection of cells:** 18 -** **Serial **– all cells are connected in series in a single string .18 +** **Serial **– all cells are connected in series in a single string; 19 19 ** **Parallel-Serial **– cells are grouped in parallel and serial items; 20 20 * **Parallel-Serial: Number of Logic devices in a chain**; 21 21 * **Parallel-Serial: Number of parallel chains in a block**; ... ... @@ -626,9 +626,9 @@ 626 626 627 627 The following **balancing rules** are supported: 628 628 629 -* when the battery is charging (current I > 0) and time after until the battery is relaxed; 630 -* when the battery is charging (current I > 0) or when the battery is in a state of relaxation; 631 -* always (regardless of battery state).629 +* **Balance on charge** – perform balancing when the battery is charging (current I > 0) and time after until the battery is relaxed; 630 +* **Balance on charge or relaxed** – perform balancing when the battery is charging (current I > 0) or when the battery is in a state of relaxation ; 631 +* **Balance always** regardless of battery state. 632 632 633 633 A balancing resistor is connected to the cell if the following conditions are simultaneously met: 634 634 ... ... @@ -645,9 +645,9 @@ 645 645 If the “High logic temperature” occurs, then the balancing of the cells connected to the overheated BMS Logic device will not be performed. 646 646 ))) 647 647 648 -The BMS Main 3 / BMS Main 2R can enable the cell balancing by the external “Balancing request” signal. Balancing process will be started to cells which the voltage is higher than the balancing start voltage and the difference between the cell voltage and the minimum voltage among all the cells is greater than the balancing stop threshold. 648 +The BMS Main 3 / BMS Main 2R can enable the cell balancing by the external **“Balancing request”** signal. Balancing process will be started to cells which the voltage is higher than the balancing start voltage and the difference between the cell voltage and the minimum voltage among all the cells is greater than the balancing stop threshold. 649 649 650 -BMS Main 3 / BMS Main 2R can force a cellbalancing, if its voltage is higher than estimated value.650 +BMS Main 3 / BMS Main 2R can **force balancing **of the cell, if its voltage is higher than estimated value. 651 651 652 652 To change the cell balancing parameters, select the "Control → Cell balancing" section: 653 653 ... ... @@ -707,7 +707,7 @@ 707 707 * the battery voltage is below the minimum level; 708 708 * the “Charger connected” signal is cleared for 60 seconds. 709 709 710 -The BMS Main 3 device also shuts down the battery if it stays in the “Charging OFF”, “Discharging OFF”, “Relaxed (after charging)” or “Relaxed (after discharging)” forthe configuredtime.710 +The BMS Main 3 device also shuts down the battery if it **stays for a long time **in the “Charging OFF”, “Discharging OFF”, “Relaxed (after charging)” or “Relaxed (after discharging)” state. 711 711 712 712 To change the parameters of the power down control, select the "Control → Power down" section: 713 713 ... ... @@ -741,11 +741,12 @@ 741 741 Conditions for signal generation: 742 742 743 743 * the minimum temperature among all cells of the battery is less than the “Minimum cell temperature” value during the “Delay before starting the heater” time; 744 -* there are no errors from **Errors 1, 2**744 +* there are no errors from "Errors 1, 2..." bitfields. 745 745 746 746 Conditions for clearing the signal: 747 747 748 -* the minimum temperature among all cells of the battery is greater than the “Tolerant cell temperature” value during the “Delay before stopping the heater” time. 748 +* the minimum temperature among all cells of the battery is greater than the “Tolerant cell temperature” value during the “Delay before stopping the heater” time; 749 +* there is an error from "Errors 1, 2..." bitfields. 749 749 750 750 (% class="box infomessage" %) 751 751 ((( ... ... @@ -760,22 +760,24 @@ 760 760 761 761 In this section: 762 762 763 -* Enable – a flag to enable the cooler control; 764 -* Maximum cell temperature, °C; 765 -* Tolerant cell temperature, °C; 766 -* Delay before starting the cooler, millisecond; 767 -* Delay before stopping the cooler, millisecond; 768 -* Switchoffthe coolercontactoron errors(Undervoltage,Overcurrent, Low temperature,Short circuitorCriticalerror).764 +* **Enable** – a flag to enable the cooler control; 765 +* **Maximum cell temperature**, °C; 766 +* **Tolerant cell temperature**, °C; 767 +* **Delay before starting the cooler**, millisecond; 768 +* **Delay before stopping the cooler**, millisecond; 769 +* **Errors 1, 2 to open the cooler **– bitfields to choose the errors which will open the cooler. 769 769 770 770 As a result of operating the cooling algorithm, the "Cooler" signal is generated. 771 771 772 772 Conditions for signal generation: 773 773 774 -* the maximum temperature among all cells of the battery is greater than the “Maximum cell temperature” value during the “Delay before starting the cooler” time. 775 +* the maximum temperature among all cells of the battery is greater than the “Maximum cell temperature” value during the “Delay before starting the cooler” time; 776 +* there are no errors from "Errors 1, 2..." bitfields. 775 775 776 776 Conditions for clearing the signal: 777 777 778 -* the maximum temperature among all cells of the battery is less than the “Tolerant cell temperature” value during the “Delay before stopping the cooler” time. 780 +* the maximum temperature among all cells of the battery is less than the “Tolerant cell temperature” value during the “Delay before stopping the cooler” time; 781 +* there is an error from "Errors 1, 2..." bitfields. 779 779 780 780 (% class="box infomessage" %) 781 781 ((( ... ... @@ -784,6 +784,11 @@ 784 784 785 785 === High voltage === 786 786 790 +(% class="box warningmessage" %) 791 +((( 792 +This section is not available on BMS Main 2R. 793 +))) 794 + 787 787 The BMS Main 3 device has an ability to measure high voltages before and after contactors. 788 788 789 789 To change the parameters of high voltage fault, select the "Control → High voltage" section: ... ... @@ -792,9 +792,9 @@ 792 792 793 793 In this section: 794 794 795 -* Enable – a flag to enable High voltage control; 796 -* Delay before clearing the High voltage fault, second; 797 -* Lock the High voltage fault. 803 +* **Enable **– a flag to enable High voltage control; 804 +* **Delay before clearing the High voltage fault**, second; 805 +* **Lock the High voltage fault**. 798 798 799 799 The BMS Main 3 implements a self-diagnostics of high-voltage measurement lines. If measurement line breaks or high-voltage polarity is wrong, “High voltage fault” is generated. 800 800 ... ... @@ -807,7 +807,7 @@ 807 807 808 808 The battery discharge characteristic – the dependence Uocv = Uocv(DOD) – is used to determine the tabular dependence Uocv = Uocv(SOC, t°C), which is necessary for calculating the battery charge level. 809 809 810 -The BMS Main 3 device can automatically determine the battery discharge characteristic. 818 +The BMS Main 3 / BMS Main 2R device can automatically determine the battery discharge characteristic. 811 811 812 812 Before starting the process of determining the discharge characteristic, it is necessary to prepare a BMS: 813 813 ... ... @@ -820,18 +820,14 @@ 820 820 821 821 In this section: 822 822 823 -* Enable – a flag to enable cell analysis; 824 -* Discharge step, Ah; 825 -* Delta voltage – a maximum allowable voltage drop for the cell, V; 826 -* Logic index, Cell index – a position of the analyzed cell; 827 -* Analyse the most discharged cell – a flag to analyse of the least charged cell (in this case, the values “Logic index” and “Cell index” are ignored). 831 +* **Enable **– a flag to enable cell analysis; 832 +* **Discharge step**, Ah; 833 +* **Delta voltage** – a maximum allowable voltage drop for the cell, V; 834 +* **Logic index, Cell index** – a position of the analyzed cell; 835 +* **Analyse the most discharged cell** – a flag to analyse of the least charged cell (in this case, the values “Logic index” and “Cell index” are ignored). 828 828 829 -Discharge step should be set equal to 837 +Discharge step should be set equal to С/21, where C is the cell capacity. 830 830 831 -Discharge step= С/21, 832 - 833 -where C is the cell capacity. 834 - 835 835 The discharge characteristic will be constructed for the given cell (its position is determined by the fields “Logic index” and “Cell index”). 836 836 837 837 The algorithm for determining the discharge characteristic of the battery will be started if the “Enable” flag is set. From this moment, the control of the discharge contactor is performed by this algorithm.