... ... @@ -741,11 +741,12 @@
741 741  Conditions for signal generation:
742 742  
743 743  * the minimum temperature among all cells of the battery is less than the “Minimum cell temperature” value during the “Delay before starting the heater” time;
744 -* there are no errors from** Errors 1, 2**
744 +* there are no errors from "Errors 1, 2..." bitfields.
745 745  
746 746  Conditions for clearing the signal:
747 747  
748 -* the minimum temperature among all cells of the battery is greater than the “Tolerant cell temperature” value during the “Delay before stopping the heater” time.
748 +* the minimum temperature among all cells of the battery is greater than the “Tolerant cell temperature” value during the “Delay before stopping the heater” time;
749 +* there is an error from "Errors 1, 2..." bitfields.
749 749  
750 750  (% class="box infomessage" %)
751 751  (((
... ... @@ -765,17 +765,19 @@
765 765  * Tolerant cell temperature, °C;
766 766  * Delay before starting the cooler, millisecond;
767 767  * Delay before stopping the cooler, millisecond;
768 -* Switch off the cooler contactor on errors (Undervoltage, Overcurrent, Low temperature, Short circuit or Critical error).
769 +* **Errors 1, 2 to open the heater** bitfields to choose the errors which will open the heater.
769 769  
770 770  As a result of operating the cooling algorithm, the "Cooler" signal is generated.
771 771  
772 772  Conditions for signal generation:
773 773  
774 -* the maximum temperature among all cells of the battery is greater than the “Maximum cell temperature” value during the “Delay before starting the cooler” time.
775 +* the maximum temperature among all cells of the battery is greater than the “Maximum cell temperature” value during the “Delay before starting the cooler” time;
776 +* there are no errors from "Errors 1, 2..." bitfields.
775 775  
776 776  Conditions for clearing the signal:
777 777  
778 -* the maximum temperature among all cells of the battery is less than the “Tolerant cell temperature” value during the “Delay before stopping the cooler” time.
780 +* the maximum temperature among all cells of the battery is less than the “Tolerant cell temperature” value during the “Delay before stopping the cooler” time;
781 +* there is an error from "Errors 1, 2..." bitfields.
779 779  
780 780  (% class="box infomessage" %)