Changes for page 3.3 Control

Last modified by Admin on 2026/04/30 15:56

From version 77.5
edited by Admin
on 2026/03/31 14:23
Change comment: There is no comment for this version
To version 77.3
edited by Admin
on 2026/03/31 14:21
Change comment: There is no comment for this version

Summary

Details

Page properties
Content
... ... @@ -546,7 +546,7 @@
546 546  
547 547  Charge/Discharge contactor has three algorithms of operation:
548 548  
549 -On **Dependent (on Charging and Discharging signals)** algorithm the charge/discharge contactor depends on Charge and Discharge controllers and behaves:
549 +On **Dependent (on Charging and Discharging signals)** algorithm the charge/discharge contactor depends on Charge and Discharge algorithms and their signals and behaves
550 550  
551 551  * as Charging contactor if "Charging" signal is set;
552 552  * as Discharging contactor in other cases.
... ... @@ -560,8 +560,9 @@
560 560  
561 561  the charging/discharging contactor opens.
562 562  
563 -On **Independent (on Charge request or Discharge request)** algorithm charge/discharge contactor is based on its own controller and performs as follows:
564 564  
564 +**Independent (on Charge request or Discharge request)** - charge/discharge contactor is based on its own controller and performs as follows:
565 +
565 565  * if there is "Charge request" or "Discharge request" signal and there are no errors (see the "Errors 1, 2 ..." bitfields), then through the delay time T,,on,, the charging/discharging contactor closes;
566 566  * If the "Charge request" or "Discharge request" disappears or errors occur (see the "Errors 1, 2 ..." bitfields), then after the delay time T,,off,, the charging/discharging contactor opens.
567 567  
... ... @@ -734,14 +734,13 @@
734 734  * **Tolerant cell temperature**, °C;
735 735  * **Delay before starting the heater**, millisecond;
736 736  * **Delay before stopping the heater**, millisecond;
737 -* **Errors 1, 2 to open the heater** bitfields to choose the errors which will open the heater.
738 +* **Switch off the heater on errors** switch off the Heater Undervoltage, Overcurrent, High temperature, Short circuit or Critical error).
738 738  
739 739  As a result of operating the heating algorithm, the “Heater” signal is generated.
740 740  
741 741  Conditions for signal generation:
742 742  
743 -* the minimum temperature among all cells of the battery is less than the “Minimum cell temperature” value during the “Delay before starting the heater” time;
744 -* Th
744 +* the minimum temperature among all cells of the battery is less than the “Minimum cell temperature” value during the “Delay before starting the heater” time.
745 745  
746 746  Conditions for clearing the signal:
747 747