Changes for page 3.3 Control

Last modified by Admin on 2026/04/30 15:56

From version 77.3
edited by Admin
on 2026/03/31 14:21
Change comment: There is no comment for this version
To version 77.4
edited by Admin
on 2026/03/31 14:22
Change comment: There is no comment for this version

Summary

Details

Page properties
Content
... ... @@ -560,9 +560,8 @@
560 560  
561 561  the charging/discharging contactor opens.
562 562  
563 +On **Independent (on Charge request or Discharge request)** algorithm charge/discharge contactor is based on its own controller and performs as follows:
563 563  
564 -**Independent (on Charge request or Discharge request)** - charge/discharge contactor is based on its own controller and performs as follows:
565 -
566 566  * if there is "Charge request" or "Discharge request" signal and there are no errors (see the "Errors 1, 2 ..." bitfields), then through the delay time T,,on,, the charging/discharging contactor closes;
567 567  * If the "Charge request" or "Discharge request" disappears or errors occur (see the "Errors 1, 2 ..." bitfields), then after the delay time T,,off,, the charging/discharging contactor opens.
568 568  
... ... @@ -735,13 +735,14 @@
735 735  * **Tolerant cell temperature**, °C;
736 736  * **Delay before starting the heater**, millisecond;
737 737  * **Delay before stopping the heater**, millisecond;
738 -* **Switch off the heater on errors** switch off the Heater Undervoltage, Overcurrent, High temperature, Short circuit or Critical error).
737 +* **Errors 1, 2 to open the heater** bitfields to choose the errors which will open the heater.
739 739  
740 740  As a result of operating the heating algorithm, the “Heater” signal is generated.
741 741  
742 742  Conditions for signal generation:
743 743  
744 -* the minimum temperature among all cells of the battery is less than the “Minimum cell temperature” value during the “Delay before starting the heater” time.
743 +* the minimum temperature among all cells of the battery is less than the “Minimum cell temperature” value during the “Delay before starting the heater” time;
744 +*
745 745  
746 746  Conditions for clearing the signal:
747 747