... ... @@ -360,16 +360,16 @@
360 360  In this section:
361 361  
362 362  * **Current to set the "Charging current present"** – a current level to generate the "Charging current present" signal, A;
363 -* **Current to clear the "Charging current present"** – a current level to clear the "Charging current present" signal, A;
364 -* **Voltage to clear the “Ready to charge”** – a threshold U,,ocv,, (corrected due to current and cell resistance) voltage level on the cell, V; if the voltage of any cell is above this level, the “Ready to charge” (hence, the “Allow charging”) signal is cleared;
365 -* **Voltage to reset the “Ready to charge”** – a tolerant U,,ocv,, (corrected due to current and cell resistance) voltage level on the cell, V; if all cell voltages are below the tolerant level, the “Ready to charge” (hence, the “Allow charging”) signal is set;
366 -* **Use actual voltage to generate the "Ready to charge" signal** – a flag to disable voltage correction for "Ready to charge" signal;
367 -* **Treat negative currents as zero currents for generating the "Ready to charge" signal** – a flag to disable voltage correction for "Ready to charge" signal at discharging current;
368 -* **Delay before recharging** – a time after which the previously opened the allow charging contactor closes again, minute; to disable the operation by timeout set "Delay before recharging" to 0;
369 -* **Check the 'Charge current limit' value to generate the 'Ready to charge'** – a flag to enable check of "Charging current limit" to generate the "Ready to charge" signal;
370 -* **Charge current limit to clear the 'Ready to charge'** – a threshold charging current limit value, A; if the limit is //above //this level, the “Ready to charge” signal is cleared;
371 -* **Charge current limit to set the 'Ready to charge'** – a tolerant charging current limit value, A; if the limit is //below //this level, the “Ready to charge” signal is set;
372 -* **Errors 1, 2 to clear the "Ready to charge"** – bitfields to choose the errors which will clear the "Ready to charge" signal.
363 +* Current to clear the "Charging current present" – a current level to clear the "Charging current present" signal, A;
364 +* Voltage to clear the “Ready to charge” – a threshold U,,ocv,, (corrected due to current and cell resistance) voltage level on the cell, V; if the voltage of any cell is above this level, the “Ready to charge” (hence, the “Allow charging”) signal is cleared;
365 +* Voltage to reset the “Ready to charge” – a tolerant U,,ocv,, (corrected due to current and cell resistance) voltage level on the cell, V; if all cell voltages are below the tolerant level, the “Ready to charge” (hence, the “Allow charging”) signal is set;
366 +* Use actual voltage to generate the "Ready to charge" signal – a flag to disable voltage correction for "Ready to charge" signal;
367 +* Treat negative currents as zero currents for generating the "Ready to charge" signal – a flag to disable voltage correction for "Ready to charge" signal at discharging current;
368 +* Delay before recharging – a time after which the previously opened the allow charging contactor closes again, minute; to disable the operation by timeout set "Delay before recharging" to 0;
369 +* Check the 'Charge current limit' value to generate the 'Ready to charge' – a flag to enable check of "Charging current limit" to generate the "Ready to charge" signal;
370 +* Charge current limit to clear the 'Ready to charge' – a threshold charging current limit value, A; if the limit is //above //this level, the “Ready to charge” signal is cleared;
371 +* Charge current limit to set the 'Ready to charge' – a tolerant charging current limit value, A; if the limit is //below //this level, the “Ready to charge” signal is set;
372 +* Errors 1, 2 to clear the "Ready to charge" – bitfields to choose the errors which will clear the "Ready to charge" signal.
373 373  
374 374  (% class="box infomessage" %)
375 375  (((
... ... @@ -386,15 +386,15 @@
386 386  
387 387  In this section:
388 388  
389 -* **Current to set the "Discharging current present"** – a current level to generate the "Discharging current present" signal, А;
390 -* **Current to clear the "Discharging current present"** – a current level to clear the "Discharging current present" signal, А;
391 -* **Voltage to clear the “Ready to discharge”** – a threshold U,,ocv,, (corrected due to current and cell resistance) voltage level on the cell, V; if the voltage of any cell is below this level, the “Ready to discharge” signal is cleared;
392 -* **Voltage to reset the “Ready to discharge”** – a tolerant U,,ocv,, (corrected due to current and cell resistance) voltage level on the cell, V; if all cells voltages are above the tolerant level, the “Ready to discharge” signal is set;
393 -* **Use actual voltage to generate the "Ready to discharge" signal** – a flag to disable voltage correction for "Ready to discharge" signal;
394 -* **Treat positive currents as zero currents for generating the "Ready to discharge" signal** – a flag to disable voltage correction for "Ready to discharge" signal at charging current;
395 -* **Check the 'Discharge current limit' value to generate the 'Ready to discharge'** – a flag to enable check of "Discharging current limit" to generate the "Ready to discharge" signal;
396 -* **Discharge current limit to clear the 'Ready to discharge'** – a threshold discharging current limit value, A; if the limit is //above //this level, the “Ready to discharge” signal is cleared;
397 -* **Discharge current limit to set the 'Ready to discharge'** – a tolerant discharging current limit value, A; if the limit is //below //this level, the “Ready to discharge” signal is set;
389 +* Current to set the "Discharging current present" – a current level to generate the "Discharging current present" signal, А;
390 +* Current to clear the "Discharging current present" – a current level to clear the "Discharging current present" signal, А;
391 +* Voltage to clear the “Ready to discharge” – a threshold U,,ocv,, (corrected due to current and cell resistance) voltage level on the cell, V; if the voltage of any cell is below this level, the “Ready to discharge” signal is cleared;
392 +* Voltage to reset the “Ready to discharge” – a tolerant U,,ocv,, (corrected due to current and cell resistance) voltage level on the cell, V; if all cells voltages are above the tolerant level, the “Ready to discharge” signal is set;
393 +* Use actual voltage to generate the "Ready to discharge" signal – a flag to disable voltage correction for "Ready to discharge" signal;
394 +* Treat positive currents as zero currents for generating the "Ready to discharge" signal – a flag to disable voltage correction for "Ready to discharge" signal at charging current;
395 +* Check the 'Discharge current limit' value to generate the 'Ready to discharge' – a flag to enable check of "Discharging current limit" to generate the "Ready to discharge" signal;
396 +* Discharge current limit to clear the 'Ready to discharge' – a threshold discharging current limit value, A; if the limit is //above //this level, the “Ready to discharge” signal is cleared;
397 +* Discharge current limit to set the 'Ready to discharge' – a tolerant discharging current limit value, A; if the limit is //below //this level, the “Ready to discharge” signal is set;
398 398  * Clear the 'Ready to discharge' signal if the 'Low SOC' signal is set;
399 399  * Errors 1, 2 to clear the "Ready to discharge" – bitfields to choose the errors which will clear the "Ready to discharge" signal.
400 400