Changes for page 3.3 Control

Last modified by Admin on 2026/04/30 15:56

From version 76.7
edited by Admin
on 2026/03/31 12:59
Change comment: There is no comment for this version
To version 76.8
edited by Admin
on 2026/03/31 13:00
Change comment: There is no comment for this version

Summary

Details

Page properties
Content
... ... @@ -319,12 +319,12 @@
319 319  In **“Always on”** mode main contactor closes if all the following is true:
320 320  
321 321  * Other contactors are open;
322 -* There are no errors from the "Errors 1, 2 ..." bitfileds.
322 +* There are __no errors__ from the "Errors 1, 2 ..." bitfileds.
323 323  
324 324  and opens if all the following is true:
325 325  
326 326  * Other contactors are open;
327 -* There is an error from the the "Errors 1, 2 ..." bitfileds.
327 +* There is __an error__ from the the "Errors 1, 2 ..." bitfileds.
328 328  
329 329  In **“Automatic”** mode, the main contactor closes by internal algorithms at the same time with other contactors.
330 330  
... ... @@ -343,13 +343,13 @@
343 343  
344 344  * **Enable **– a flag to enable the main contactor control;
345 345  * **Algorithm** – main contactor control algorithm:
346 -** Always on – contactor is always closed;
347 -** Automatic – contactor closes by internal charge and discharge algorithms;
348 -** On demand – contactor is closed by an external request;
349 -* Time to keep the contactor closed before closing the others – a time for other contactors to be open after the main contactor is closed;
350 -* Delay before opening the contactor – a time which is used to detect conditions for opening the contactor, s;
351 -* Keep the contactor open until the device is restarted – a flag for keeping the main contactor open until the system is reset;
352 -* Errors 1, 2 to open the main contactor – bitfields to choose the errors which will open the main contactor.
346 +** **Always on** – contactor is always closed;
347 +** **Automatic** – contactor closes by internal charge and discharge algorithms;
348 +** **On demand** – contactor is closed by an external request;
349 +* **Time to keep the contactor closed before closing the others** – a time for other contactors to be open after the main contactor is closed;
350 +* **Delay before opening the contactor** – a time which is used to detect conditions for opening the contactor, s;
351 +* **Keep the contactor open until the device is restarted** – a flag for keeping the main contactor open until the system is reset;
352 +* **Errors 1, 2 to open the main contactor** – bitfields to choose the errors which will open the main contactor.
353 353  
354 354  === Charging status ===
355 355  
... ... @@ -359,7 +359,7 @@
359 359  
360 360  In this section:
361 361  
362 -* Current to set the "Charging current present" – a current level to generate the "Charging current present" signal, A;
362 +* **Current to set the "Charging current present"** – a current level to generate the "Charging current present" signal, A;
363 363  * Current to clear the "Charging current present" – a current level to clear the "Charging current present" signal, A;
364 364  * Voltage to clear the “Ready to charge” – a threshold U,,ocv,, (corrected due to current and cell resistance) voltage level on the cell, V; if the voltage of any cell is above this level, the “Ready to charge” (hence, the “Allow charging”) signal is cleared;
365 365  * Voltage to reset the “Ready to charge” – a tolerant U,,ocv,, (corrected due to current and cell resistance) voltage level on the cell, V; if all cell voltages are below the tolerant level, the “Ready to charge” (hence, the “Allow charging”) signal is set;