Content
... ... @@ -14,7 +14,6 @@
14 14  
15 15  * Cell capacity – nominal capacity of cells, Ah;
16 16  * Cell resistance – nominal (maximum) internal resistance of the cells, Ohm;
17 -* Connection of cells –
18 18  * Relax time (after charging) – a relaxation time after charging, second;
19 19  * Relax time (atfer discharging) – a relaxation time after discharging, second;
20 20  * Reset parameters – a command to reset cells state of charge, capacity, and resistance;
... ... @@ -378,7 +378,7 @@
378 378  
379 379  To change the parameters of charging process status, select the "Control → Charging status" section:
380 380  
381 -[[image:1771432488941-251.png||data-xwiki-image-style-alignment="center" data-xwiki-image-style-border="true" height="154" width="800"]]
380 +[[image:1760435790050-496.png||data-xwiki-image-style-alignment="center" data-xwiki-image-style-border="true" height="140" width="800"]]
382 382  
383 383  In this section:
384 384  
... ... @@ -386,7 +386,6 @@
386 386  * Current to clear the "Charging current present" – a current level to clear the "Charging current present" signal, A;
387 387  * Voltage to clear the “Ready to charge” – a threshold U,,ocv,, (corrected due to current and cell resistance) voltage level on the cell, V; if the voltage of any cell is above this level, the “Ready to charge” (hence, the “Allow charging”) signal is cleared;
388 388  * Voltage to reset the “Ready to charge” – a tolerant U,,ocv,, (corrected due to current and cell resistance) voltage level on the cell, V; if all cell voltages are below the tolerant level, the “Ready to charge” (hence, the “Allow charging”) signal is set;
389 -* Use actual voltage to generate the "Ready to charge" signal – a flag to disable voltage correction for "Ready to charge" signal;
390 390  * Treat negative currents as zero currents for generating the "Ready to charge" signal – a flag to disable voltage correction for "Ready to charge" signal at discharging current;
391 391  * Delay before recharging – a time after which the previously opened the allow charging contactor closes again, minute; to disable the operation by timeout set "Delay before recharging" to 0;
392 392  * Check the 'Charge current limit' value to generate the 'Ready to charge' – a flag to enable check of "Charging current limit" to generate the "Ready to charge" signal;
... ... @@ -413,7 +413,6 @@
413 413  * Current to clear the "Discharging current present" – a current level to clear the "Discharging current present" signal, А;
414 414  * Voltage to clear the “Ready to discharge” – a threshold U,,ocv,, (corrected due to current and cell resistance) voltage level on the cell, V; if the voltage of any cell is below this level, the “Ready to discharge” signal is cleared;
415 415  * Voltage to reset the “Ready to discharge” – a tolerant U,,ocv,, (corrected due to current and cell resistance) voltage level on the cell, V; if all cells voltages are above the tolerant level, the “Ready to discharge” signal is set;
416 -* Use actual voltage to generate the "Ready to discharge" signal – a flag to disable voltage correction for "Ready to discharge" signal;
417 417  * Treat positive currents as zero currents for generating the "Ready to discharge" signal – a flag to disable voltage correction for "Ready to discharge" signal at charging current;
418 418  * Check the 'Discharge current limit' value to generate the 'Ready to discharge' – a flag to enable check of "Discharging current limit" to generate the "Ready to discharge" signal;
419 419  * Discharge current limit to clear the 'Ready to discharge' – a threshold discharging current limit value, A; if the limit is //above //this level, the “Ready to discharge” signal is cleared;