... ... @@ -15,7 +15,7 @@
15 15  * **Cell capacity** – nominal capacity of cells, Ah;
16 16  * **Cell resistance** – nominal (maximum) internal resistance of the cells, Ohm;
17 17  * **Connection of cells:**
18 -** **Serial **– all cells are connected in series in a single string.
18 +** **Serial **– all cells are connected in series in a single string;
19 19  ** **Parallel-Serial **– cells are grouped in parallel and serial items;
20 20  * **Parallel-Serial: Number of Logic devices in a chain**;
21 21  * **Parallel-Serial: Number of parallel chains in a block**;
... ... @@ -29,7 +29,7 @@
29 29  ** **Summation of cell voltages** – the overall voltage is calculated as on sum of all cells in the battery;
30 30  ** **Using voltage before contactors** – the overall voltage is estimated as voltage before contactors measured by BMS.
31 31  
32 -The **"Parallel-Serial"** connection works as follows: a bunch of serial connected Logics are grouped into chains. A bunch of parallel connected chains are grouped to blocks. A bunch of serial connected blocks are grouped into string. By configuring the corresponding settings it is possible to create a complex string configuration. Current through each chain will be estimated as a fraction of overall current accordingly to the number of chains in a block.
32 +The **"Parallel-Serial"** connection works as follows: a bunch of serial connected Logics are grouped into chains. A bunch of parallel connected chains are grouped to blocks. A bunch of serial connected blocks are grouped into string. By configuring the corresponding settings it is possible to create a complex string configuration. Current through each chain will be calculated as overall string current divided by number of chains in a block.
33 33  
34 34  The values **“Capacity”** and **“Resistance”** are used to calculate the SOC of cells and the battery.
35 35  
... ... @@ -39,7 +39,7 @@
39 39  
40 40  === SOC estimation ===
41 41  
42 -The BMS Main 3 / BMS Main 2R device calculates the state of charge (SOC) of each cell, and then the overall battery SOC, by using following algorithms:
42 +The BMS Main 3 / BMS Main 2R device calculates the state of charge (SOC) of each cell by using following algorithms:
43 43  
44 44  The **“Voltage”** SOC calculation algorithm calculates cells SOC based on the tabular dependence Uocv = Uocv(SOC, t °C).
45 45  
... ... @@ -94,11 +94,11 @@
94 94  
95 95  === SOH estimation ===
96 96  
97 -The BMS Main 3 device calculates the state of health of the battery (SOH) using two algorithms:
97 +The BMS Main 3 / BMS Main 2R device calculates the state of health of the battery (SOH) using two algorithms:
98 98  
99 99  In **"By effective capacity" **mode SOH is calculated as a ratio of effective capacity to nominal capacity. Effective capacity is estimated to DOD value when battery SOC reaches 0%, so SOH is recalculated each full battery discharge.
100 100  
101 -In** "By total charge–"** mode SOH is calculated as a linear function of "Total charge-" counter. While "Total charge-" constantly increases during battery operation, SOH will be linearly decrease at the same time. This mode requires a confirmed data about cell health depending of amount of discharge rate to configure the linear function.
101 +In** "By total charge–"** mode SOH is calculated as a linear function of "Total charge-" counter. While "Total charge-" constantly increases during battery operation, SOH will be linearly decrease at the same time. This mode requires a confirmed data about cell health depending of amount of discharge rate to configure the linear function.
102 102  
103 103  To configure parameters for battery state of health calculation, select the "Control → SOH correction" section:
104 104  
... ... @@ -373,9 +373,9 @@
373 373  
374 374  (% class="box infomessage" %)
375 375  (((
376 -**Note:** The "Allow charging" signal activates under two independent conditions:
376 +**Note:** The **"Allow charging"** signal activates under two independent conditions:
377 377  1) the voltage on the cells reaches the “Voltage to reset the “Ready to charge"” level and
378 -2) the "Delay before recharging" time has passed since the opening of the allow charging contactor.
378 +2) the "Delay before recharging" time has passed since the clearing of the "Allow charging" signal.
379 379  )))
380 380  
381 381  === Discharging status ===
... ... @@ -402,9 +402,9 @@
402 402  
403 403  The BMS Main 3 / BMS Main 2R device can control the precharge contactor. The precharge contactor is used to charge the intermediate capacity with low current and usually placed with the limiting resistor in parallel to charging or discharging contactor.
404 404  
405 -BMS Main 3 can detect errors while pre-charging the load capacity by monitoring **the current and voltage difference** before and after contactors.
405 +BMS Main 3 can check the preacharge process by monitoring **the current and voltage difference** before and after contactors.
406 406  
407 -BMS Main 2R can detect errors while pre-charging the load capacity **only by monitoring the current**.
407 +BMS Main 2R can check the preacharge process **only by monitoring the current**.
408 408  
409 409  In **simple **mode precharge contactor closes a "Precharge time" before the closing of Charge or Discharge contactors and opens after the same amount of time after closing them.
410 410  
... ... @@ -431,7 +431,7 @@
431 431  * **Delay before clearing the "Precharge error"**, second;
432 432  * **Lock the "Precharge error"** – a flag to block the error until the device is restarted.
433 433  
434 -“Precharge error” generation conditions if any of the following is true:
434 +“Precharge error” generates if any of the following is true:
435 435  
436 436  * the precharge current does not decrease during the "Precharge time" after "Number of precharging attempts";
437 437  * voltages before and after contactors are not equal during the "Precharge time" after "Number of precharging attempts";
... ... @@ -444,35 +444,31 @@
444 444  
445 445  === Charge ===
446 446  
447 -There are two signals that serve charging the battery: "Charging" and "Allow charging". With the help of the "Allow charging" signal, the BMS commands the charger to start or stop charging.
447 +The BMS Main 3 / BMS Main 2R device connect battery to the charger using the "Charging" signal.
448 448  
449 -The device supports three charge control algorithms:
449 +BMS Main 3 / BMS Main 2R supports three charge control algorithms:
450 450  
451 -If the "**Always on**" algorithm is selected, the charging contactor and the allow charging contactor are always closed. If at least one of the errors from the "Errors 1, 2 ..." bitfields appears or one of the signals:
451 +If the "**Always on**" algorithm is selected, the harging" signal ialways set. If at least one of the errors from the "Errors 1, 2 ..." bitfields appears or one of the signals:
452 452  
453 453  * Service reset;
454 454  * Power down request;
455 455  * Inhibit charging,
456 456  
457 -both contactors are open (no current flows).
457 +the "Charging" signal is cleared.
458 458  
459 459  When the algorithm "**On charger connected**" is selected, the control is performed as follows:
460 460  
461 -* If there is a signal “Charger connected” and there are no errors (see the "Errors 1, 2 ..." bitfields), then through the delay time T,,on,, the charging contactor and the allow charging contactor close;
462 -* If the signal “Charger connected” disappears, the allow charging contactor opens and after the delay time T,,off,, the charging contactor opens;
463 -* If in the process of charging the voltage on the cell exceeds the “Ready to charge” level, the allow charging contactor opens (while the charging contactor remains closed);
464 -* If errors from the "Errors 1, 2 ..." bitfields occur the charging contactor and allow charging contactor open.
461 +* If there is a signal “Charger connected” and there are no errors (see the "Errors 1, 2 ..." bitfields), then through the delay time T,,on,, the "Charging" signal is set;
462 +* If the signal “Charger connected” disappears or errors occur (see the "Errors 1, 2 ..." bitfields), then after the delay time T,,off,, the "Charging" signal is cleared.
465 465  
466 466  When the "**On charge request**" algorithm selected, the control is performed as follows:
467 467  
468 -* If there is a signal “Charge request” and there are no errors (see the "Errors 1, 2 ..." bitfields), then through the delay time T,,on,, the charging contactor and the allow charging contactor close;
469 -* If the signal “Charge request” disappears, the allow charging contactor opens and after the delay time T,,off,, the charging contactor opens;
470 -* If in the process of charging the voltage on the cell exceeds the “Ready to charge” level, the allow charging contactor opens (while the charging contactor remains closed);
471 -* If errors from the "Errors 1, 2 ..." bitfields occur the charging contactor and allow charging contactor open.
466 +* If there is a signal “Charge request” and there are no errors (see the "Errors 1, 2 ..." bitfields), then through the delay time T,,on,, the "Charging" signal is set;
467 +* If the signal “Charge request” disappears or errors occur (see the "Errors 1, 2 ..." bitfields), then after the delay time T,,off,, the "Charging" signal is cleared;
472 472  
473 473  (% class="box infomessage" %)
474 474  (((
475 -**Note: **when errors occur in the system, the **Charge **contactor opens either immediately or with the delay T,,off,, (depends on the settings described below).
471 +**Note: **when errors occur in the system, the **"Charing" **signal is cleared either immediately or with the delay T,,off,, (depends on the settings described below).
476 476  )))
477 477  
478 478  To change the parameters of the battery charge control algorithm, select the "Control → Charge" section:
... ... @@ -497,29 +497,31 @@
497 497  
498 498  === Discharge ===
499 499  
500 -The device controls the discharging contactor to connect battery to the load.
496 +The BMS Main 3 / BMS Main 2R device connect battery to the load using the "Discharging" signal.
501 501  
502 -The device supports three algorithms to control battery discharging:When the algorithm "**Always on**" is selected, the discharging contactor is always closed. If at least one of the errors from the "Errors 1, 2 ..." bitfields appears or one of the signals:
498 +BMS Main 3 / BMS Main 2R supports three algorithms to control battery discharging:
503 503  
500 +When the algorithm "**Always on**" is selected, the "Discharging" signal is always set. If at least one of the errors from the "Errors 1, 2 ..." bitfields appears or one of the signals:
501 +
504 504  * Service reset
505 505  * Power down request
506 506  * Inhibit discharging
507 507  
508 -the discharging contactor opens.
506 +the "Discharging" signal is cleared.
509 509  
510 510  If the algorithm "**On charger disconnected**" is selected, the control is performed as follows:
511 511  
512 -* if there is no signal “Charger connected”, the charging contactor is open and there are no errors (see the "Errors 1, 2 ..." bitfields), then through the delay time T,,on,, the discharging contactor closes;
513 -* If the signal “Charger connected” appears or errors occur (see the "Errors 1, 2 ..." bitfields), then after the delay time T,,off,, the discharging contactor opens.
510 +* if there are no “Charger connected” and "Charging" signals and there are no errors (see the "Errors 1, 2 ..." bitfields), then through the delay time T,,on,, the "Discharging" signal is set;
511 +* If the signal “Charger connected” appears or errors occur (see the "Errors 1, 2 ..." bitfields), then after the delay time T,,off,, the "Discharging" signal is cleared.
514 514  
515 515  When the "**On discharge request**" algorithm selected, the control is performed as follows:
516 516  
517 -* if there is signal “Discharge request”, the charging contactor is open and there are no errors (see the "Errors 1, 2 ..." bitfields), then through the delay time T,,on,, the discharging contactor closes;
518 -* If the signal “Discharge request” disappears or errors occur (see the "Errors 1, 2 ..." bitfields), then after the delay time T,,off,, the discharging contactor opens.
515 +* if there is signal “Discharge request” and there are no errors (see the "Errors 1, 2 ..." bitfields), then through the delay time T,,on,, the "Discharging" signal is set;
516 +* If the signal “Discharge request” disappears or errors occur (see the "Errors 1, 2 ..." bitfields), then after the delay time T,,off,, the "Discharging" signal is cleared.
519 519  
520 520  (% class="box infomessage" %)
521 521  (((
522 -**Note: **when errors occur in the system, the **Discharge **contactor opens either immediately or with the delay T,,off,, (depends on the settings described below).
520 +**Note: **when errors occur in the system, the **"Discharge" **signal is cleared either immediately or with the delay T,,off,, (depends on the settings described below).
523 523  )))
524 524  
525 525  To change the parameters of the battery discharge control algorithm, select the "Control → Discharge" section:
... ... @@ -528,32 +528,45 @@
528 528  
529 529  In this section:
530 530  
531 -* Enable – a flag to activate the discharge control;
532 -* Algorithm:
533 -** Always on – load is always connected;
534 -** On charger disconnected – load is connected when there is no signal “Charger connected”;
535 -** On discharge request – load is connected when there is signal “Discharge request”;
536 -* Allow charging only when the "Ready to discharge" signal is set – discharging contactor will open if "Ready to discharge" signal is cleared;
537 -* Delay before starting discharging – a time delay T,,on,, before closing the discharging contactor, millisecond;
538 -* Delay before stopping discharging – a time delay T,,off,, before opening the discharging contactor, millisecond;
539 -* Control the precharging contactor – a flag that allows control of the precharging contactor while closing the discharge contactor (see [[Precharge>>doc:||anchor="HPrecharge"]]);
540 -* Errors 1, 2 to open the discharging contactor – bitfields to choose the errors which will open the discharging contactor;
541 -* Use custom delays before stopping discharging (on errors) – a flag to enable manual settings of time delays T,,off,, for specific errors;
542 -* Custom delay: <error> – specific error delay, millisecond;
543 -* Switch off the discharging contactor on errors without delay – a flag to protectively open the discharging contactor without a delay. In the opposite case, when an error is detected, the discharging contactor opens always with the delay “Delay before stopping discharging”.
529 +* **Enable **– a flag to activate the discharge control;
530 +* **Algorithm**:
531 +** **Always on** – load is always connected;
532 +** **On charger disconnected** – load is connected when there is no signal “Charger connected”;
533 +** **On discharge request** – load is connected when there is signal “Discharge request”;
534 +* **Allow charging only when the "Ready to discharge" signal is set** – discharging contactor will open if "Ready to discharge" signal is cleared;
535 +* **Delay before starting discharging** – a time delay T,,on,, before closing the discharging contactor, millisecond;
536 +* **Delay before stopping discharging** – a time delay T,,off,, before opening the discharging contactor, millisecond;
537 +* **Control the precharging contactor** – a flag that allows control of the precharging contactor while closing the discharge contactor (see [[Precharge>>doc:||anchor="HPrecharge"]]);
538 +* **Errors 1, 2 to open the discharging contactor** – bitfields to choose the errors which will open the discharging contactor;
539 +* **Use custom delays before stopping discharging (on errors)** – a flag to enable manual settings of time delays T,,off,, for specific errors;
540 +* **Custom delay: <error>** – specific error delay, millisecond;
541 +* **Switch off the discharging contactor on errors without delay** – a flag to protectively open the discharging contactor without a delay. In the opposite case, when an error is detected, the discharging contactor opens always with the delay “Delay before stopping discharging”.
544 544  
545 545  === Charge/Discharge ===
546 546  
547 -The BMS Main 3 device can control the charge/discharge contactor, which combines algorithms of charging and discharging contactor.
545 +The BMS Main 3 / BMS Main 2R device can control the contactor, used in power line both used for connecting battery to charger and load, by using the "Charging/Discharging" signal.
548 548  
549 -Charge/Discharge contactor has three algorithms of operation:
547 +"Charging/Discharging" signal has three algorithms of operation:
550 550  
551 -* Dependent (on Charging and Discharging signals) - Charge/Discharge contactor depends on Charge and Discharge algorithms and their signals and behaves as Charging contactor if Charging signal is set, otherwise – as Discharging contactor;
552 -* Independent (Always) - Charge/Discharge contactor is always closed if there is no errors;
553 -* Independent (on Charge request or Discharge request) - Charge/Discharge contactor is based on its own controller that listen to Charge and Discharge requests and closes if one of these signals occurs.
549 +On **Dependent (on Charging and Discharging signals)** algorithm the "Charging/Discharging" signal depends on Charge and Discharge controllers and equal to:
554 554  
555 -TBA
551 +* "Charging" signal if "Charging" signal is set;
552 +* "Discharging" signal in other cases.
556 556  
554 +When **Independent (Always) **algorithm is selected, the "Charging/Discharging" signal is always set. If at least one of the errors from the "Errors 1, 2 ..." bitfields appears or one of the signals:
555 +
556 +* Service reset
557 +* Power down request
558 +* Inhibit charging
559 +* Inhibit discharging
560 +
561 +the Charging/Discharging signal is cleared.
562 +
563 +On **Independent (on Charge request or Discharge request)** algorithm "Charging/Discharging" signal is based on its own controller and performs as follows:
564 +
565 +* if there is "Charge request" or "Discharge request" signal and there are no errors (see the "Errors 1, 2 ..." bitfields), then through the delay time T,,on,, the Charging/Discharging signal is set;
566 +* If the "Charge request" or "Discharge request" disappears or errors occur (see the "Errors 1, 2 ..." bitfields), then after the delay time T,,off,, the "Charging/Discharging" signal is cleared.
567 +
557 557  (% class="box infomessage" %)
558 558  (((
559 559  **Note: **when errors occur in the system, the **Charge/Discharge **contactor opens either immediately or with the delay T,,off,, (depends on the settings described below).
... ... @@ -565,23 +565,23 @@
565 565  
566 566  In this section:
567 567  
568 -* Enable – a flag to enable the charge/discharge controller.
569 -* Algorithm:
570 -** Dependent (on Charging and Discharging signals) - Charge/Discharge contactor depends on Charge and Discharge algorithms and their signals and behaves as Charging contactor if Charging signal is set, otherwise – as Discharging contactor;
571 -** Independent (Always) - Charge/Discharge contactor is always closed if there is no errors;
572 -** Independent (on Charge request or Discharge request);
573 -* Delay before starting charging or discharging, millisecond;
574 -* Delay before stopping charging or discharging, millisecond;
575 -* Control the precharging contactor – a flag that enables control of precharging contactor while closing the charge/discharge contactor;
576 -* Emulate the "Charging" and "Discharging" signals – a flag to enable generation of "Charging" and "Discharging" signals when closing charge/discharge contactor;
577 -* Errors 1, 2 to prevent CHARGING through charging/discharging contactor, Errors 1, 2 to prevent DISCHARGING through charging/discharging contactor – bitfields to choose the errors which will open the charging/discharging contactor. This bitfields are combined by bitwise OR and intended to separate settings for charging and discharging processes;
578 -* Errors 1, 2 which affect the contactor only if battery CHARGING is detected – a bitfield to choose the errors which will trigger only if charging current is present. This bitfield is combined with "Errors 1, 2 to prevent CHARGING through charging/discharging contactor" by bitwise AND;
579 -* Errors 1, 2 which affect the contactor only if battery DISCHARGING is detected – a bitfield to choose the errors which will trigger only if discharging current is present. This bitfield is combined with "Errors 1, 2 to prevent DISCHARGING through charging/discharging contactor" by bitwise AND;
580 -* Switch off the charging/discharging contactor on errors without delay – a flag to protectively open the charging/discharging contactor without a delay. In the opposite case, when an error is detected, the charging/discharging contactor opens always with the delay “Delay before stopping discharging”.
579 +* **Enable **– a flag to enable the charge/discharge controller.
580 +* **Algorithm**:
581 +** **Dependent (on Charging and Discharging signals)** - Charge/Discharge contactor depends on Charge and Discharge algorithms and their signals and behaves as Charging contactor if Charging signal is set, otherwise – as Discharging contactor;
582 +** **Independent (Always)** - Charge/Discharge contactor is always closed if there is no errors;
583 +** **Independent (on Charge request or Discharge request)**;
584 +* **Delay before starting charging or discharging**, millisecond;
585 +* **Delay before stopping charging or discharging**, millisecond;
586 +* **Control the precharging contactor** – a flag that enables control of precharging contactor while closing the charge/discharge contactor;
587 +* **Emulate the "Charging" and "Discharging" signals** – a flag to enable generation of "Charging" and "Discharging" signals when closing charge/discharge contactor. DO NOT use with enabled Charger and Disc;
588 +* **Errors 1, 2 to prevent CHARGING through charging/discharging contactor, Errors 1, 2 to prevent DISCHARGING through charging/discharging contactor** – bitfields to choose the errors which will open the charging/discharging contactor. This bitfields are combined by bitwise OR and intended to separate settings for charging and discharging processes;
589 +* **Errors 1, 2 which affect the contactor only if battery CHARGING is detected** – a bitfield to choose the errors which will trigger only if charging current is present. This bitfield is combined with "Errors 1, 2 to prevent CHARGING through charging/discharging contactor" by bitwise AND;
590 +* **Errors 1, 2 which affect the contactor only if battery DISCHARGING is detected** – a bitfield to choose the errors which will trigger only if discharging current is present. This bitfield is combined with "Errors 1, 2 to prevent DISCHARGING through charging/discharging contactor" by bitwise AND;
591 +* **Switch off the charging/discharging contactor on errors without delay** – a flag to protectively open the charging/discharging contactor without a delay. In the opposite case, when an error is detected, the charging/discharging contactor opens always with the delay “Delay before stopping discharging”.
581 581  
582 582  === Discharge (AUX) ===
583 583  
584 -The BMS Main 3 device can control the power supply of external equipment using the auxiliary (AUX) discharging contactor. An example of external equipment can be an inverter that converts DC to AC to power a service laptop and other devices.
595 +The BMS Main 3 / BMS Main 2R device can control the power supply of external equipment using the auxiliary (AUX) discharging contactor. An example of external equipment can be an inverter that converts DC to AC to power a service laptop and other devices.
585 585  
586 586  The power supply circuit of the external equipment using the auxiliary (AUX) discharging contactor is independent of the battery load circuit. The closing and opening of the auxiliary (AUX) discharging contactor is performed according to its program.
587 587  
... ... @@ -597,27 +597,27 @@
597 597  
598 598  In this section:
599 599  
600 -* Enable – a flag to activate the auxiliary discharge control;
601 -* Switch off the discharging (AUX) contactor if the SOC is too low;
602 -* Minimum SOC – a minimum SOC value, when reached, the auxiliary (AUX) discharging contactor opens, %;
603 -* Tolerant SOC – a permissive SOC value, upon reaching which the auxiliary (AUX) discharging contactor re-closes, %;
604 -* Switch off the discharging (AUX) contactor if the cell voltage is out of the range;
605 -* Minimum cell voltage, V;
606 -* Maximum cell voltage, V;
607 -* Switch off the discharging (AUX) contactor if the battery voltage is out of the range;
608 -* Minimum battery voltage, V;
609 -* Maximum battery voltage, V;
610 -* Errors 1, 2 to open the auxiliary discharging contactor – bitfields to choose the errors which will open the auxiliary discharging contactor.
611 +* **Enable **– a flag to activate the auxiliary discharge control;
612 +* **Switch off the discharging (AUX) contactor if the SOC is too low**;
613 +* **Minimum SOC** – a minimum SOC value, when reached, the auxiliary (AUX) discharging contactor opens, %;
614 +* **Tolerant SOC** – a permissive SOC value, upon reaching which the auxiliary (AUX) discharging contactor re-closes, %;
615 +* **Switch off the discharging (AUX) contactor if the cell voltage is out of the range**;
616 +* **Minimum cell voltage**, V;
617 +* **Maximum cell voltage**, V;
618 +* **Switch off the discharging (AUX) contactor if the battery voltage is out of the range**;
619 +* **Minimum battery voltage**, V;
620 +* **Maximum battery voltage**, V;
621 +* **Errors 1, 2 to open the auxiliary discharging contactor** – bitfields to choose the errors which will open the auxiliary discharging contactor.
611 611  
612 612  === Cell balancing ===
613 613  
614 614  Balancing makes the voltage of all cells equal to the minimum cell voltage.
615 615  
616 -The following balancing rules are supported:
627 +The following **balancing rules** are supported:
617 617  
618 -* when the battery is charging (current I > 0) and time after until the battery is relaxed;
619 -* when the battery is charging (current I > 0) or when the battery is in a state of relaxation;
620 -* always (regardless of battery state).
629 +* **Balance on charge** – perform balancing when the battery is charging (current I > 0) and time after until the battery is relaxed;
630 +* **Balance on charge or relaxed** – perform balancing when the battery is charging (current I > 0) or when the battery is in a state of relaxation ​​​​​;
631 +* **Balance always** regardless of battery state.
621 621  
622 622  A balancing resistor is connected to the cell if the following conditions are simultaneously met:
623 623  
... ... @@ -634,9 +634,9 @@
634 634  If the “High logic temperature” occurs, then the balancing of the cells connected to the overheated BMS Logic device will not be performed.
635 635  )))
636 636  
637 -The BMS Main 3 can enable the cell balancing by the external “Balancing request” signal. Balancing process will be started to cells which the voltage is higher than the balancing start voltage and the difference between the cell voltage and the minimum voltage among all the cells is greater than the balancing stop threshold.
648 +The BMS Main 3 / BMS Main 2R can enable the cell balancing by the external **“Balancing request”** signal. Balancing process will be started to cells which the voltage is higher than the balancing start voltage and the difference between the cell voltage and the minimum voltage among all the cells is greater than the balancing stop threshold.
638 638  
639 -BMS Main 3 can force a cell balancing, if its voltage is higher than estimated value.
650 +BMS Main 3 / BMS Main 2R can **force balancing **of the cell, if its voltage is higher than estimated value.
640 640  
641 641  To change the cell balancing parameters, select the "Control → Cell balancing" section:
642 642  
... ... @@ -644,24 +644,25 @@
644 644  
645 645  In this section:
646 646  
647 -* Enable – a flag to enable cell balancing;
648 -* Balancing rule:
649 -** Balance on charge – balancing is performed while and after the charging (in the “Charge ON” and “Charge OFF” states);
650 -** Balance on charge or relaxed - balancing is performed while and after the charging and in the relaxed state (in “Charge ON”, “Charge OFF”, “Relaxed (after charging)” and “Relaxed (after discharging)” states);
651 -** Balance always – balancing is always performed regardless the battery state;
652 -* Balancing condition:
653 -** Automatic – balancing will be performed automatically if needed conditions are met;
654 -** On balancing request – balancing will start only if a remote request is received. In this case cells will start to balance regardless the "Voltage deviation to start balancing" value;
655 -* Minimum cell voltage to start balancing, V;
656 -* Voltage deviation to start balancing;
657 -* Voltage deviation to stop balancing;
658 -* Voltage for forced balancing – if cell voltage is above this value, it will start discharging through balancing resistor;
659 -* Maximum allowable temperature of BMS Logic devices, ºC;
660 -* Command to discharge all cells – a flag to force the balancing of all cells.
658 +* **Enable **– a flag to enable cell balancing;
659 +* **Balancing rule**:
660 +** **Balance on charge** – balancing is performed while and after the charging (in the “Charge ON” and “Charge OFF” states);
661 +** **Balance on charge or relaxed** - balancing is performed while and after the charging and in the relaxed state (in “Charge ON”, “Charge OFF”, “Relaxed (after charging)” and “Relaxed (after discharging)” states);
662 +** **Balance always** – balancing is always performed regardless the battery state;
663 +* **Balancing condition**:
664 +** **Automatic **– balancing will be performed automatically if needed conditions are met;
665 +** **On balancing request** – balancing will start only if a remote request is received. In this case cells will start to balance regardless the "Voltage deviation to start balancing" value;
666 +* **Minimum cell voltage to start balancing**, V;
667 +* **Voltage deviation to start balancing**;
668 +* **Voltage deviation to stop balancing**;
669 +* **Voltage to start forced balancing** – if cell voltage is above this value, it will start discharging through balancing resistor;
670 +* **Voltage to stop forced balancing** – if cell voltage is below this value, it will stop discharging through balancing resistor;
671 +* **Maximum allowable temperature of BMS Logic devices**, ºC;
672 +* **Command to discharge all cells** – a flag to force the balancing of all cells.
661 661  
662 662  === Series balancing ===
663 663  
664 -The BMS Main 3 device supports work with two independent (galvanically unrelated) cell series. To monitor the status of two series, two current sensors are used. A series of cells must be equivalent: they must have the same number of cells and the same capacity.
676 +The BMS Main 3 / BMS Main 2R device supports work with two independent (galvanically unrelated) cell series. To monitor the status of two series, two current sensors are used. A series of cells must be equivalent: they must have the same number of cells and the same capacity.
665 665  
666 666  Since the series of cells can operate at different loads, they must be balanced. For this, the BMS Main 3 provides two signals to power switches: “Balancing series 1” and “Balancing series 2”, as well as a combined algorithm that considers both the voltage of each series and the charge that these series gave load. The “Balancing series 1” and “Balancing series 2” signals are used to connect high-power balancing resistors in parallel with cell series 1 and 2.
667 667  
... ... @@ -678,17 +678,17 @@
678 678  
679 679  In this section:
680 680  
681 -* Enable – a flag to enable series balancing;
682 -* Number of Logics in a series;
683 -* Minimum series voltage to start balancing, V;
684 -* Balancing threshold, V;
685 -* Coulomb threshold – the difference of the charges Qthr, given by a series of cells, above which balancing to be started, Ah;
686 -* Period – a period to reset of charge counters for each series (to avoid accumulation of error), second;
687 -* Do not sum series voltages – a flag to disable the summing of series voltages.3
693 +* **Enable **– a flag to enable series balancing;
694 +* **Number of Logics in a series**;
695 +* **Minimum series voltage to start balancing**, V;
696 +* **Balancing threshold**, V;
697 +* **Coulomb threshold** – the difference of the charges Qthr, given by a series of cells, above which balancing to be started, Ah;
698 +* **Period **– a period to reset of charge counters for each series (to avoid accumulation of error), second;
699 +* **Do not sum series voltages** – a flag to disable the summing of series voltages.
688 688  
689 689  === Power down ===
690 690  
691 -The BMS Main 3 device can shut down itself if the battery voltage is low or the battery is idle for a long time.
703 +The BMS Main 3 / BMS Main 2R device can shut down itself if the battery voltage is low or the battery is idle for a long time.
692 692  
693 693  Shutting down the battery system is performed according to the following conditions:
694 694  
... ... @@ -695,7 +695,7 @@
695 695  * the battery voltage is below the minimum level;
696 696  * the “Charger connected” signal is cleared for 60 seconds.
697 697  
698 -The BMS Main 3 device also shuts down the battery if it stays in the “Charging OFF”, “Discharging OFF”, “Relaxed (after charging)” or “Relaxed (after discharging)” for the configured time.
710 +The BMS Main 3 device also shuts down the battery if it **stays for a long time **in the “Charging OFF”, “Discharging OFF”, “Relaxed (after charging)” or “Relaxed (after discharging)” state.
699 699  
700 700  To change the parameters of the power down control, select the "Control → Power down" section:
701 701  
... ... @@ -703,11 +703,11 @@
703 703  
704 704  In this section:
705 705  
706 -* Minimum voltage to power down – a minimum voltage level of the battery below which the BMS commands to shut down the battery, V;
707 -* Idle time to power down – a time of battery inactivity after which the battery is shut down, minute;
708 -* Wait the "Power up/down request" is cleared (on startup) – a flag to enable delay for clearing the “Power up/down request” signal while starting the BMS.
709 -* Power down if KEYRUN and CHARGE_ON are cleared – a flag to power down the device if KEYRUN and CHARGE_ON signals are cleared;
710 -* Delay before setting the internal power down signal – a delay before turning off the device power when removing KEYRUN and CHARGE_ON or receiving the “Power down request” command, ms.
718 +* **Minimum voltage to power down** – a minimum voltage level of the battery below which the BMS commands to shut down the battery, V;
719 +* **Idle time to power down** – a time of battery inactivity after which the battery is shut down, minute;
720 +* **Wait the "Power up/down request" is cleared (on startup)** – a flag to enable delay for clearing the “Power up/down request” signal while starting the BMS.
721 +* **Power down if KEYRUN and CHARGE_ON are cleared** – a flag to power down the device if KEYRUN and CHARGE_ON signals are cleared;
722 +* **Delay before setting the internal power down signal** – a delay before turning off the device power when removing KEYRUN and CHARGE_ON or receiving the “Power down request” command, ms.
711 711  
712 712  === Heater ===
713 713  
... ... @@ -717,22 +717,24 @@
717 717  
718 718  In this section:
719 719  
720 -* Enable – a flag to enable the heater control;
721 -* Minimum cell temperature, °C;
722 -* Tolerant cell temperature, °C;
723 -* Delay before starting the heater, millisecond;
724 -* Delay before stopping the heater, millisecond;
725 -* Switch off the heater on errors (Undervoltage, Overcurrent, High temperature, Short circuit or Critical error).
732 +* **Enable **– a flag to enable the heater control;
733 +* **Minimum cell temperature**, °C;
734 +* **Tolerant cell temperature**, °C;
735 +* **Delay before starting the heater**, millisecond;
736 +* **Delay before stopping the heater**, millisecond;
737 +* **Errors 1, 2 to open the heater** bitfields to choose the errors which will open the heater.
726 726  
727 727  As a result of operating the heating algorithm, the “Heater” signal is generated.
728 728  
729 729  Conditions for signal generation:
730 730  
731 -* the minimum temperature among all cells of the battery is less than the “Minimum cell temperature” value during the “Delay before starting the heater” time.
743 +* the minimum temperature among all cells of the battery is less than the “Minimum cell temperature” value during the “Delay before starting the heater” time;
744 +* there are no errors from "Errors 1, 2..." bitfields.
732 732  
733 733  Conditions for clearing the signal:
734 734  
735 -* the minimum temperature among all cells of the battery is greater than the “Tolerant cell temperature” value during the “Delay before stopping the heater” time.
748 +* the minimum temperature among all cells of the battery is greater than the “Tolerant cell temperature” value during the “Delay before stopping the heater” time;
749 +* there is an error from "Errors 1, 2..." bitfields.
736 736  
737 737  (% class="box infomessage" %)
738 738  (((
... ... @@ -747,22 +747,24 @@
747 747  
748 748  In this section:
749 749  
750 -* Enable – a flag to enable the cooler control;
751 -* Maximum cell temperature, °C;
752 -* Tolerant cell temperature, °C;
753 -* Delay before starting the cooler, millisecond;
754 -* Delay before stopping the cooler, millisecond;
755 -* Switch off the cooler contactor on errors (Undervoltage, Overcurrent, Low temperature, Short circuit or Critical error).
764 +* **Enable** – a flag to enable the cooler control;
765 +* **Maximum cell temperature**, °C;
766 +* **Tolerant cell temperature**, °C;
767 +* **Delay before starting the cooler**, millisecond;
768 +* **Delay before stopping the cooler**, millisecond;
769 +* **Errors 1, 2 to open the cooler **– bitfields to choose the errors which will open the cooler.
756 756  
757 757  As a result of operating the cooling algorithm, the "Cooler" signal is generated.
758 758  
759 759  Conditions for signal generation:
760 760  
761 -* the maximum temperature among all cells of the battery is greater than the “Maximum cell temperature” value during the “Delay before starting the cooler” time.
775 +* the maximum temperature among all cells of the battery is greater than the “Maximum cell temperature” value during the “Delay before starting the cooler” time;
776 +* there are no errors from "Errors 1, 2..." bitfields.
762 762  
763 763  Conditions for clearing the signal:
764 764  
765 -* the maximum temperature among all cells of the battery is less than the “Tolerant cell temperature” value during the “Delay before stopping the cooler” time.
780 +* the maximum temperature among all cells of the battery is less than the “Tolerant cell temperature” value during the “Delay before stopping the cooler” time;
781 +* there is an error from "Errors 1, 2..." bitfields.
766 766  
767 767  (% class="box infomessage" %)
768 768  (((
... ... @@ -771,6 +771,11 @@
771 771  
772 772  === High voltage ===
773 773  
790 +(% class="box warningmessage" %)
791 +(((
792 +This section is not available on BMS Main 2R.
793 +)))
794 +
774 774  The BMS Main 3 device has an ability to measure high voltages before and after contactors.
775 775  
776 776  To change the parameters of high voltage fault, select the "Control → High voltage" section:
... ... @@ -779,9 +779,9 @@
779 779  
780 780  In this section:
781 781  
782 -* Enable – a flag to enable High voltage control;
783 -* Delay before clearing the High voltage fault, second;
784 -* Lock the High voltage fault.
803 +* **Enable **– a flag to enable High voltage control;
804 +* **Delay before clearing the High voltage fault**, second;
805 +* **Lock the High voltage fault**.
785 785  
786 786  The BMS Main 3 implements a self-diagnostics of high-voltage measurement lines. If measurement line breaks or high-voltage polarity is wrong, “High voltage fault” is generated.
787 787  
... ... @@ -794,7 +794,7 @@
794 794  
795 795  The battery discharge characteristic – the dependence Uocv = Uocv(DOD) – is used to determine the tabular dependence Uocv = Uocv(SOC, t°C), which is necessary for calculating the battery charge level.
796 796  
797 -The BMS Main 3 device can automatically determine the battery discharge characteristic.
818 +The BMS Main 3 / BMS Main 2R device can automatically determine the battery discharge characteristic.
798 798  
799 799  Before starting the process of determining the discharge characteristic, it is necessary to prepare a BMS:
800 800  
... ... @@ -807,18 +807,14 @@
807 807  
808 808  In this section:
809 809  
810 -* Enable – a flag to enable cell analysis;
811 -* Discharge step, Ah;
812 -* Delta voltage – a maximum allowable voltage drop for the cell, V;
813 -* Logic index, Cell index – a position of the analyzed cell;
814 -* Analyse the most discharged cell – a flag to analyse of the least charged cell (in this case, the values “Logic index” and “Cell index” are ignored).
831 +* **Enable **– a flag to enable cell analysis;
832 +* **Discharge step**, Ah;
833 +* **Delta voltage** – a maximum allowable voltage drop for the cell, V;
834 +* **Logic index, Cell index** – a position of the analyzed cell;
835 +* **Analyse the most discharged cell** – a flag to analyse of the least charged cell (in this case, the values “Logic index” and “Cell index” are ignored).
815 815  
816 -Discharge step should be set equal to
837 +Discharge step should be set equal to С/21, where C is the cell capacity.
817 817  
818 -Discharge step= С/21,
819 -
820 -where C is the cell capacity.
821 -
822 822  The discharge characteristic will be constructed for the given cell (its position is determined by the fields “Logic index” and “Cell index”).
823 823  
824 824  The algorithm for determining the discharge characteristic of the battery will be started if the “Enable” flag is set. From this moment, the control of the discharge contactor is performed by this algorithm.