... ... @@ -446,7 +446,7 @@
446 446  
447 447  There are two signals that serve charging the battery: "Charging" and "Allow charging". With the help of the "Allow charging" signal, the BMS commands the charger to start or stop charging.
448 448  
449 -The device supports three charge control algorithms:
449 +BMS Main 3 / BMS Main 2R supports three charge control algorithms:
450 450  
451 451  If the "**Always on**" algorithm is selected, the charging contactor and the allow charging contactor are always closed. If at least one of the errors from the "Errors 1, 2 ..." bitfields appears or one of the signals:
452 452  
... ... @@ -459,16 +459,12 @@
459 459  When the algorithm "**On charger connected**" is selected, the control is performed as follows:
460 460  
461 461  * If there is a signal “Charger connected” and there are no errors (see the "Errors 1, 2 ..." bitfields), then through the delay time T,,on,, the charging contactor and the allow charging contactor close;
462 -* If the signal “Charger connected” disappears, the allow charging contactor opens and after the delay time T,,off,, the charging contactor opens;
463 -* If in the process of charging the voltage on the cell exceeds the “Ready to charge” level, the allow charging contactor opens (while the charging contactor remains closed);
464 -* If errors from the "Errors 1, 2 ..." bitfields occur the charging contactor and allow charging contactor open.
462 +* If the signal “Charger connected” disappears or errors occur (see the "Errors 1, 2 ..." bitfields), the allow charging contactor opens and after the delay time T,,off,, the charging contactor opens.
465 465  
466 466  When the "**On charge request**" algorithm selected, the control is performed as follows:
467 467  
468 468  * If there is a signal “Charge request” and there are no errors (see the "Errors 1, 2 ..." bitfields), then through the delay time T,,on,, the charging contactor and the allow charging contactor close;
469 -* If the signal “Charge request” disappears, the allow charging contactor opens and after the delay time T,,off,, the charging contactor opens;
470 -* If in the process of charging the voltage on the cell exceeds the “Ready to charge” level, the allow charging contactor opens (while the charging contactor remains closed);
471 -* If errors from the "Errors 1, 2 ..." bitfields occur the charging contactor and allow charging contactor open.
467 +* If the signal “Charge request” disappears or errors occur (see the "Errors 1, 2 ..." bitfields), the allow charging contactor opens and after the delay time T,,off,, the charging contactor opens;
472 472  
473 473  (% class="box infomessage" %)
474 474  (((
... ... @@ -497,10 +497,12 @@
497 497  
498 498  === Discharge ===
499 499  
500 -The device controls the discharging contactor to connect battery to the load.
496 +The BMS Main 3 / BMS Main 2R device controls the discharging contactor to connect battery to the load.
501 501  
502 -The device supports three algorithms to control battery discharging:When the algorithm "**Always on**" is selected, the discharging contactor is always closed. If at least one of the errors from the "Errors 1, 2 ..." bitfields appears or one of the signals:
498 +BMS Main 3 / BMS Main 2R supports three algorithms to control battery discharging:
503 503  
500 +When the algorithm "**Always on**" is selected, the discharging contactor is always closed. If at least one of the errors from the "Errors 1, 2 ..." bitfields appears or one of the signals:
501 +
504 504  * Service reset
505 505  * Power down request
506 506  * Inhibit discharging
... ... @@ -528,32 +528,46 @@
528 528  
529 529  In this section:
530 530  
531 -* Enable – a flag to activate the discharge control;
532 -* Algorithm:
533 -** Always on – load is always connected;
534 -** On charger disconnected – load is connected when there is no signal “Charger connected”;
535 -** On discharge request – load is connected when there is signal “Discharge request”;
536 -* Allow charging only when the "Ready to discharge" signal is set – discharging contactor will open if "Ready to discharge" signal is cleared;
537 -* Delay before starting discharging – a time delay T,,on,, before closing the discharging contactor, millisecond;
538 -* Delay before stopping discharging – a time delay T,,off,, before opening the discharging contactor, millisecond;
539 -* Control the precharging contactor – a flag that allows control of the precharging contactor while closing the discharge contactor (see [[Precharge>>doc:||anchor="HPrecharge"]]);
540 -* Errors 1, 2 to open the discharging contactor – bitfields to choose the errors which will open the discharging contactor;
541 -* Use custom delays before stopping discharging (on errors) – a flag to enable manual settings of time delays T,,off,, for specific errors;
542 -* Custom delay: <error> – specific error delay, millisecond;
543 -* Switch off the discharging contactor on errors without delay – a flag to protectively open the discharging contactor without a delay. In the opposite case, when an error is detected, the discharging contactor opens always with the delay “Delay before stopping discharging”.
529 +* **Enable **– a flag to activate the discharge control;
530 +* **Algorithm**:
531 +** **Always on** – load is always connected;
532 +** **On charger disconnected** – load is connected when there is no signal “Charger connected”;
533 +** **On discharge request** – load is connected when there is signal “Discharge request”;
534 +* **Allow charging only when the "Ready to discharge" signal is set** – discharging contactor will open if "Ready to discharge" signal is cleared;
535 +* **Delay before starting discharging** – a time delay T,,on,, before closing the discharging contactor, millisecond;
536 +* **Delay before stopping discharging** – a time delay T,,off,, before opening the discharging contactor, millisecond;
537 +* **Control the precharging contactor** – a flag that allows control of the precharging contactor while closing the discharge contactor (see [[Precharge>>doc:||anchor="HPrecharge"]]);
538 +* **Errors 1, 2 to open the discharging contactor** – bitfields to choose the errors which will open the discharging contactor;
539 +* **Use custom delays before stopping discharging (on errors)** – a flag to enable manual settings of time delays T,,off,, for specific errors;
540 +* **Custom delay: <error>** – specific error delay, millisecond;
541 +* **Switch off the discharging contactor on errors without delay** – a flag to protectively open the discharging contactor without a delay. In the opposite case, when an error is detected, the discharging contactor opens always with the delay “Delay before stopping discharging”.
544 544  
545 545  === Charge/Discharge ===
546 546  
547 -The BMS Main 3 device can control the charge/discharge contactor, which combines algorithms of charging and discharging contactor.
545 +The BMS Main 3 / BMS Main 2R device can control the Charge/Discharge contactor, which combines algorithms of charging and discharging contactor.
548 548  
549 549  Charge/Discharge contactor has three algorithms of operation:
550 550  
551 -* Dependent (on Charging and Discharging signals) - Charge/Discharge contactor depends on Charge and Discharge algorithms and their signals and behaves as Charging contactor if Charging signal is set, otherwise – as Discharging contactor;
552 -* Independent (Always) - Charge/Discharge contactor is always closed if there is no errors;
553 -* Independent (on Charge request or Discharge request) - Charge/Discharge contactor is based on its own controller that listen to Charge and Discharge requests and closes if one of these signals occurs.
549 +On **Dependent (on Charging and Discharging signals)** algorithm the charge/discharge contactor depends on Charge and Discharge algorithms and their signals and behaves
554 554  
555 -TBA
551 +* as Charging contactor if "Charging" signal is set;
552 +* as Discharging contactor in other cases.
556 556  
554 +When **Independent (Always) **algorithm is selected, the charging/discharging contactor is always closed. If at least one of the errors from the "Errors 1, 2 ..." bitfields appears or one of the signals:
555 +
556 +* Service reset
557 +* Power down request
558 +* Inhibit charging
559 +* Inhibit discharging
560 +
561 +the charging/discharging contactor opens.
562 +
563 +
564 +**Independent (on Charge request or Discharge request)** - charge/discharge contactor is based on its own controller and performs as follows:
565 +
566 +* if there is "Charge request" or "Discharge request" signal and there are no errors (see the "Errors 1, 2 ..." bitfields), then through the delay time T,,on,, the charging/discharging contactor closes;
567 +* If the "Charge request" or "Discharge request" disappears or errors occur (see the "Errors 1, 2 ..." bitfields), then after the delay time T,,off,, the charging/discharging contactor opens.
568 +
557 557  (% class="box infomessage" %)
558 558  (((
559 559  **Note: **when errors occur in the system, the **Charge/Discharge **contactor opens either immediately or with the delay T,,off,, (depends on the settings described below).
... ... @@ -565,23 +565,23 @@
565 565  
566 566  In this section:
567 567  
568 -* Enable – a flag to enable the charge/discharge controller.
569 -* Algorithm:
570 -** Dependent (on Charging and Discharging signals) - Charge/Discharge contactor depends on Charge and Discharge algorithms and their signals and behaves as Charging contactor if Charging signal is set, otherwise – as Discharging contactor;
571 -** Independent (Always) - Charge/Discharge contactor is always closed if there is no errors;
572 -** Independent (on Charge request or Discharge request);
573 -* Delay before starting charging or discharging, millisecond;
574 -* Delay before stopping charging or discharging, millisecond;
575 -* Control the precharging contactor – a flag that enables control of precharging contactor while closing the charge/discharge contactor;
576 -* Emulate the "Charging" and "Discharging" signals – a flag to enable generation of "Charging" and "Discharging" signals when closing charge/discharge contactor;
577 -* Errors 1, 2 to prevent CHARGING through charging/discharging contactor, Errors 1, 2 to prevent DISCHARGING through charging/discharging contactor – bitfields to choose the errors which will open the charging/discharging contactor. This bitfields are combined by bitwise OR and intended to separate settings for charging and discharging processes;
578 -* Errors 1, 2 which affect the contactor only if battery CHARGING is detected – a bitfield to choose the errors which will trigger only if charging current is present. This bitfield is combined with "Errors 1, 2 to prevent CHARGING through charging/discharging contactor" by bitwise AND;
579 -* Errors 1, 2 which affect the contactor only if battery DISCHARGING is detected – a bitfield to choose the errors which will trigger only if discharging current is present. This bitfield is combined with "Errors 1, 2 to prevent DISCHARGING through charging/discharging contactor" by bitwise AND;
580 -* Switch off the charging/discharging contactor on errors without delay – a flag to protectively open the charging/discharging contactor without a delay. In the opposite case, when an error is detected, the charging/discharging contactor opens always with the delay “Delay before stopping discharging”.
580 +* **Enable **– a flag to enable the charge/discharge controller.
581 +* **Algorithm**:
582 +** **Dependent (on Charging and Discharging signals)** - Charge/Discharge contactor depends on Charge and Discharge algorithms and their signals and behaves as Charging contactor if Charging signal is set, otherwise – as Discharging contactor;
583 +** **Independent (Always)** - Charge/Discharge contactor is always closed if there is no errors;
584 +** **Independent (on Charge request or Discharge request)**;
585 +* **Delay before starting charging or discharging**, millisecond;
586 +* **Delay before stopping charging or discharging**, millisecond;
587 +* **Control the precharging contactor** – a flag that enables control of precharging contactor while closing the charge/discharge contactor;
588 +* **Emulate the "Charging" and "Discharging" signals** – a flag to enable generation of "Charging" and "Discharging" signals when closing charge/discharge contactor;
589 +* **Errors 1, 2 to prevent CHARGING through charging/discharging contactor, Errors 1, 2 to prevent DISCHARGING through charging/discharging contactor** – bitfields to choose the errors which will open the charging/discharging contactor. This bitfields are combined by bitwise OR and intended to separate settings for charging and discharging processes;
590 +* **Errors 1, 2 which affect the contactor only if battery CHARGING is detected** – a bitfield to choose the errors which will trigger only if charging current is present. This bitfield is combined with "Errors 1, 2 to prevent CHARGING through charging/discharging contactor" by bitwise AND;
591 +* **Errors 1, 2 which affect the contactor only if battery DISCHARGING is detected** – a bitfield to choose the errors which will trigger only if discharging current is present. This bitfield is combined with "Errors 1, 2 to prevent DISCHARGING through charging/discharging contactor" by bitwise AND;
592 +* **Switch off the charging/discharging contactor on errors without delay** – a flag to protectively open the charging/discharging contactor without a delay. In the opposite case, when an error is detected, the charging/discharging contactor opens always with the delay “Delay before stopping discharging”.
581 581  
582 582  === Discharge (AUX) ===
583 583  
584 -The BMS Main 3 device can control the power supply of external equipment using the auxiliary (AUX) discharging contactor. An example of external equipment can be an inverter that converts DC to AC to power a service laptop and other devices.
596 +The BMS Main 3 / BMS Main 2R device can control the power supply of external equipment using the auxiliary (AUX) discharging contactor. An example of external equipment can be an inverter that converts DC to AC to power a service laptop and other devices.
585 585  
586 586  The power supply circuit of the external equipment using the auxiliary (AUX) discharging contactor is independent of the battery load circuit. The closing and opening of the auxiliary (AUX) discharging contactor is performed according to its program.
587 587  
... ... @@ -597,17 +597,17 @@
597 597  
598 598  In this section:
599 599  
600 -* Enable – a flag to activate the auxiliary discharge control;
601 -* Switch off the discharging (AUX) contactor if the SOC is too low;
602 -* Minimum SOC – a minimum SOC value, when reached, the auxiliary (AUX) discharging contactor opens, %;
603 -* Tolerant SOC – a permissive SOC value, upon reaching which the auxiliary (AUX) discharging contactor re-closes, %;
604 -* Switch off the discharging (AUX) contactor if the cell voltage is out of the range;
605 -* Minimum cell voltage, V;
606 -* Maximum cell voltage, V;
607 -* Switch off the discharging (AUX) contactor if the battery voltage is out of the range;
608 -* Minimum battery voltage, V;
609 -* Maximum battery voltage, V;
610 -* Errors 1, 2 to open the auxiliary discharging contactor – bitfields to choose the errors which will open the auxiliary discharging contactor.
612 +* **Enable **– a flag to activate the auxiliary discharge control;
613 +* **Switch off the discharging (AUX) contactor if the SOC is too low**;
614 +* **Minimum SOC** – a minimum SOC value, when reached, the auxiliary (AUX) discharging contactor opens, %;
615 +* **Tolerant SOC** – a permissive SOC value, upon reaching which the auxiliary (AUX) discharging contactor re-closes, %;
616 +* **Switch off the discharging (AUX) contactor if the cell voltage is out of the range**;
617 +* **Minimum cell voltage**, V;
618 +* **Maximum cell voltage**, V;
619 +* **Switch off the discharging (AUX) contactor if the battery voltage is out of the range**;
620 +* **Minimum battery voltage**, V;
621 +* **Maximum battery voltage**, V;
622 +* **Errors 1, 2 to open the auxiliary discharging contactor** – bitfields to choose the errors which will open the auxiliary discharging contactor.
611 611  
612 612  === Cell balancing ===
613 613  
... ... @@ -644,7 +644,7 @@
644 644  
645 645  In this section:
646 646  
647 -* Enable – a flag to enable cell balancing;
659 +* **Enable **– a flag to enable cell balancing;
648 648  * Balancing rule:
649 649  ** Balance on charge – balancing is performed while and after the charging (in the “Charge ON” and “Charge OFF” states);
650 650  ** Balance on charge or relaxed - balancing is performed while and after the charging and in the relaxed state (in “Charge ON”, “Charge OFF”, “Relaxed (after charging)” and “Relaxed (after discharging)” states);