Changes for page 3.3 Control

Last modified by Admin on 2026/04/30 15:56

From version 76.1
edited by Admin
on 2026/02/18 16:36
Change comment: Загрузить новое вложение 1771432563405-644.png
To version 74.1
edited by Admin
on 2026/02/18 16:34
Change comment: Uploaded new attachment "1771432488941-251.png", version {1}

Summary

Details

Page properties
Content
... ... @@ -377,7 +377,7 @@
377 377  
378 378  To change the parameters of charging process status, select the "Control → Charging status" section:
379 379  
380 -[[image:1771432488941-251.png||data-xwiki-image-style-alignment="center" data-xwiki-image-style-border="true" height="154" width="800"]]
380 +[[image:1760435790050-496.png||data-xwiki-image-style-alignment="center" data-xwiki-image-style-border="true" height="140" width="800"]]
381 381  
382 382  In this section:
383 383  
... ... @@ -385,7 +385,6 @@
385 385  * Current to clear the "Charging current present" – a current level to clear the "Charging current present" signal, A;
386 386  * Voltage to clear the “Ready to charge” – a threshold U,,ocv,, (corrected due to current and cell resistance) voltage level on the cell, V; if the voltage of any cell is above this level, the “Ready to charge” (hence, the “Allow charging”) signal is cleared;
387 387  * Voltage to reset the “Ready to charge” – a tolerant U,,ocv,, (corrected due to current and cell resistance) voltage level on the cell, V; if all cell voltages are below the tolerant level, the “Ready to charge” (hence, the “Allow charging”) signal is set;
388 -* Use actual voltage to generate the "Ready to charge" signal – a flag to disable voltage correction for "Ready to charge" signal;
389 389  * Treat negative currents as zero currents for generating the "Ready to charge" signal – a flag to disable voltage correction for "Ready to charge" signal at discharging current;
390 390  * Delay before recharging – a time after which the previously opened the allow charging contactor closes again, minute; to disable the operation by timeout set "Delay before recharging" to 0;
391 391  * Check the 'Charge current limit' value to generate the 'Ready to charge' – a flag to enable check of "Charging current limit" to generate the "Ready to charge" signal;
... ... @@ -412,7 +412,6 @@
412 412  * Current to clear the "Discharging current present" – a current level to clear the "Discharging current present" signal, А;
413 413  * Voltage to clear the “Ready to discharge” – a threshold U,,ocv,, (corrected due to current and cell resistance) voltage level on the cell, V; if the voltage of any cell is below this level, the “Ready to discharge” signal is cleared;
414 414  * Voltage to reset the “Ready to discharge” – a tolerant U,,ocv,, (corrected due to current and cell resistance) voltage level on the cell, V; if all cells voltages are above the tolerant level, the “Ready to discharge” signal is set;
415 -* Use actual voltage to generate the "Ready to discharge" signal – a flag to disable voltage correction for "Ready to discharge" signal;
416 416  * Treat positive currents as zero currents for generating the "Ready to discharge" signal – a flag to disable voltage correction for "Ready to discharge" signal at charging current;
417 417  * Check the 'Discharge current limit' value to generate the 'Ready to discharge' – a flag to enable check of "Discharging current limit" to generate the "Ready to discharge" signal;
418 418  * Discharge current limit to clear the 'Ready to discharge' – a threshold discharging current limit value, A; if the limit is //above //this level, the “Ready to discharge” signal is cleared;
1771432563405-644.png
Author
... ... @@ -1,1 +1,0 @@
1 -XWiki.admin
Size
... ... @@ -1,1 +1,0 @@
1 -40.1 KB
Content