Summary

Details

Page properties
Content
... ... @@ -111,7 +111,7 @@
111 111  
112 112  In "By effective capacity" mode SOH is calculated as a ratio of effective capacity to nominal capacity. Effective capacity is estimated to DOD value when battery SOC reaches 0%, so SOH is recalculated each full battery discharge.
113 113  
114 -In "By total charge-" mode SOH is calculated as a linear function of "Total charge-" counter. While "Total charge-" constantly increases during battery operation, SOH will be linearly decrease at the same time. This mode requires a confirmed data about cell health depending of amount of discharge rate to configure the linear function.
114 +In "By total charge-" mode SOH is calculated as a linear function of "Total charge-" counter. While "Total charge-" constantly increases during battery operation, SOH will be linearly decrease at the same time. This mode requires a confirmed cell data to set the expecting SOH at the expecting amount of charge-.
115 115  
116 116  To configure parameters for battery state of health calculation, select the "Control → SOH correction" section: