Changes for page 3.3 Control

Last modified by Admin on 2026/04/30 15:56

From version 68.1
edited by Admin
on 2025/12/11 10:17
Change comment: There is no comment for this version
To version 73.1
edited by Admin
on 2026/02/18 16:19
Change comment: There is no comment for this version

Summary

Details

Page properties
Content
... ... @@ -111,7 +111,7 @@
111 111  
112 112  In "By effective capacity" mode SOH is calculated as a ratio of effective capacity to nominal capacity. Effective capacity is estimated to DOD value when battery SOC reaches 0%, so SOH is recalculated each full battery discharge.
113 113  
114 -In "By total charge-" mode SOH is calculated as a linear function of "Total charge-" counter. While "Total charge-" constantly increases during battery operation, SOH will be linearly decrease at the same time. This mode requires a confirmed cell data to set the expecting SOH at the expecting amount of charge-.
114 +In "By total charge-" mode SOH is calculated as a linear function of "Total charge-" counter. While "Total charge-" constantly increases during battery operation, SOH will be linearly decrease at the same time. This mode requires a confirmed data about cell health depending of amount of discharge rate to configure the linear function.
115 115  
116 116  To configure parameters for battery state of health calculation, select the "Control → SOH correction" section:
117 117  
... ... @@ -403,7 +403,7 @@
403 403  
404 404  To change the parameters of discharging process status, select the "Control → Discharging status" section:
405 405  
406 -[[image:1760435802140-274.png||data-xwiki-image-style-alignment="center" data-xwiki-image-style-border="true" height="129" width="800"]]
406 +[[image:1771431570393-551.png||data-xwiki-image-style-alignment="center" data-xwiki-image-style-border="true" height="155" width="800"]]
407 407  
408 408  In this section:
409 409  
... ... @@ -415,6 +415,7 @@
415 415  * Check the 'Discharge current limit' value to generate the 'Ready to discharge' – a flag to enable check of "Discharging current limit" to generate the "Ready to discharge" signal;
416 416  * Discharge current limit to clear the 'Ready to discharge' – a threshold discharging current limit value, A; if the limit is //above //this level, the “Ready to discharge” signal is cleared;
417 417  * Discharge current limit to set the 'Ready to discharge' – a tolerant discharging current limit value, A; if the limit is //below //this level, the “Ready to discharge” signal is set;
418 +* Clear the 'Ready to discharge' signal if the 'Low SOC' signal is set;
418 418  * Errors 1, 2 to clear the "Ready to discharge" – bitfields to choose the errors which will clear the "Ready to discharge" signal.
419 419  
420 420  === Precharge ===
1765448283865-334.png
Author
... ... @@ -1,0 +1,1 @@
1 +XWiki.admin
Size
... ... @@ -1,0 +1,1 @@
1 +20.9 KB
Content
1771431551882-439.png
Author
... ... @@ -1,0 +1,1 @@
1 +XWiki.admin
Size
... ... @@ -1,0 +1,1 @@
1 +43.7 KB
Content
1771431570393-551.png
Author
... ... @@ -1,0 +1,1 @@
1 +XWiki.admin
Size
... ... @@ -1,0 +1,1 @@
1 +43.7 KB
Content