... ... @@ -366,7 +366,8 @@ 366 366 * Voltage to reset the “Ready to charge” – a tolerant U,,ocv,, (corrected due to current and cell resistance) voltage level on the cell, V; if all cell voltages are below the tolerant level, the “Ready to charge” (hence, the “Allow charging”) signal is set; 367 367 * Treat negative currents as zero currents for generating the "Ready to charge" signal – a flag to disable voltage correction for "Ready to charge" signal at discharging current; 368 368 * Delay before recharging – a time after which the previously opened the allow charging contactor closes again, minute; to disable the operation by timeout set "Delay before recharging" to 0; 369 -* Check the 'Charge current limit' value to generate the 'Ready to charge' – a flag to enable 369 +* Check the 'Charge current limit' value to generate the 'Ready to charge' – a flag to enable check of "Charging current limit" to generate the "Ready to charge" signal; 370 +* Charge current limit to clear the 'Ready to charge' – a threshold ; if the voltage of any cell is above this level, the “Ready to charge” (hence, the “Allow charging”) signal is cleared; 370 370 * Errors 1, 2 to clear the "Ready to charge" – bitfields to choose the errors which will clear the "Ready to charge" signal. 371 371 372 372 (% class="box infomessage" %)