Changes for page 3.3 Control
Last modified by Admin on 2025/12/11 10:32
Summary
-
Page properties (1 modified, 0 added, 0 removed)
-
Attachments (0 modified, 1 added, 0 removed)
Details
- Page properties
-
- Content
-
... ... @@ -102,6 +102,17 @@ 102 102 * Ignore the linear zone – a flag to ignore linear SOC zone while correction (recommended to be unset); 103 103 * Last correction timestamp – time when last correction was made. 104 104 105 +=== SOH estimation === 106 + 107 +The BMS Main 3 device calculates the state of health of the battery (SOH) using two algorithms: 108 + 109 +* by effective capacity; 110 +* by total charge-. 111 + 112 +In "By effective capacity" mode SOH is calculated as a ratio of effective capacity to nominal capacity. 113 + 114 +In "By total charge-" mode SOH is calculated 115 + 105 105 === Resistance estimation === 106 106 107 107 Calculation of the resistance of cells is carried out in two ways. The first method is used when the battery passes from a relaxation state to a charge or discharge state, wherein the cell resistance value ... ... @@ -356,7 +356,7 @@ 356 356 357 357 To change the parameters of charging process status, select the "Control → Charging status" section: 358 358 359 -[[image:1750 261016583-434.png||data-xwiki-image-style-alignment="center" data-xwiki-image-style-border="true" height="114" width="800"]]370 +[[image:1760435790050-496.png||data-xwiki-image-style-alignment="center" data-xwiki-image-style-border="true" height="140" width="800"]] 360 360 361 361 In this section: 362 362 ... ... @@ -366,6 +366,9 @@ 366 366 * Voltage to reset the “Ready to charge” – a tolerant U,,ocv,, (corrected due to current and cell resistance) voltage level on the cell, V; if all cell voltages are below the tolerant level, the “Ready to charge” (hence, the “Allow charging”) signal is set; 367 367 * Treat negative currents as zero currents for generating the "Ready to charge" signal – a flag to disable voltage correction for "Ready to charge" signal at discharging current; 368 368 * Delay before recharging – a time after which the previously opened the allow charging contactor closes again, minute; to disable the operation by timeout set "Delay before recharging" to 0; 380 +* Check the 'Charge current limit' value to generate the 'Ready to charge' – a flag to enable check of "Charging current limit" to generate the "Ready to charge" signal; 381 +* Charge current limit to clear the 'Ready to charge' – a threshold charging current limit value, A; if the limit is //above //this level, the “Ready to charge” signal is cleared; 382 +* Charge current limit to set the 'Ready to charge' – a tolerant charging current limit value, A; if the limit is //below //this level, the “Ready to charge” signal is set; 369 369 * Errors 1, 2 to clear the "Ready to charge" – bitfields to choose the errors which will clear the "Ready to charge" signal. 370 370 371 371 (% class="box infomessage" %) ... ... @@ -379,7 +379,7 @@ 379 379 380 380 To change the parameters of discharging process status, select the "Control → Discharging status" section: 381 381 382 -[[image:17502 61289590-730.png||data-xwiki-image-style-alignment="center" data-xwiki-image-style-border="true" height="103" width="800"]]396 +[[image:1760435802140-274.png||data-xwiki-image-style-alignment="center" data-xwiki-image-style-border="true" height="129" width="800"]] 383 383 384 384 In this section: 385 385 ... ... @@ -388,6 +388,9 @@ 388 388 * Voltage to clear the “Ready to discharge” – a threshold U,,ocv,, (corrected due to current and cell resistance) voltage level on the cell, V; if the voltage of any cell is below this level, the “Ready to discharge” signal is cleared; 389 389 * Voltage to reset the “Ready to discharge” – a tolerant U,,ocv,, (corrected due to current and cell resistance) voltage level on the cell, V; if all cells voltages are above the tolerant level, the “Ready to discharge” signal is set; 390 390 * Treat positive currents as zero currents for generating the "Ready to discharge" signal – a flag to disable voltage correction for "Ready to discharge" signal at charging current; 405 +* Check the 'Discharge current limit' value to generate the 'Ready to discharge' – a flag to enable check of "Discharging current limit" to generate the "Ready to discharge" signal; 406 +* Discharge current limit to clear the 'Ready to discharge' – a threshold discharging current limit value, A; if the limit is //above //this level, the “Ready to discharge” signal is cleared; 407 +* Discharge current limit to set the 'Ready to discharge' – a tolerant discharging current limit value, A; if the limit is //below //this level, the “Ready to discharge” signal is set; 391 391 * Errors 1, 2 to clear the "Ready to discharge" – bitfields to choose the errors which will clear the "Ready to discharge" signal. 392 392 393 393 === Precharge ===
- 1760435802140-274.png
-
- Author
-
... ... @@ -1,0 +1,1 @@ 1 +XWiki.admin - Size
-
... ... @@ -1,0 +1,1 @@ 1 +35.3 KB - Content