... ... @@ -315,8 +315,7 @@
315 315  The Main contactor algorithm supports the following modes:
316 316  
317 317  * Always on;
318 -* Automatic;
319 -* On demand.
318 +* Automatic.
320 320  
321 321  In “Always on” mode main contactor closes if all the following is true:
322 322  
... ... @@ -622,7 +622,7 @@
622 622  
623 623  A balancing resistor is disconnected from the cell if any of the following conditions are met:
624 624  
625 -* the voltage on the cell is less than the balancing start voltage;
624 +* the voltage on the cell is less than the balancing stop voltage;
626 626  * the difference between the voltage on the cell and the minimum voltage among the battery cells is less than the balancing stop threshold.
627 627  