Summary

Details

Page properties
Parent
... ... @@ -1,1 +1,1 @@
1 -drafts.bms-main-3.3\. Settings.WebHome
1 +Battery management systems.BMS Main 3.3\. Configuration.WebHome
Content
... ... @@ -83,7 +83,7 @@
83 83  
84 84  === SOC correction ===
85 85  
86 -The BMS Main 3 device can recalculate the battery SOC after long-term storage or after long-term working in the case when the battery was not charged fully or discharged totally. Recalculation is done based on the tabular dependency Uocv = Uocv (SOC, t) (see section** **2.3.2).
86 +The BMS Main 3 device can recalculate the battery SOC after long-term storage or after long-term working in the case when the battery was not charged fully or discharged totally. Recalculation is done based on the tabular dependency Uocv = Uocv (SOC, t) (see [[SOC estimation>>doc:||anchor="HSOCestimation"]]).
87 87  
88 88  To configure parameters for periodically correcting the battery state of charge, select the "Control → SOC correction" section:
89 89  
... ... @@ -128,7 +128,7 @@
128 128  * Minimum SOC – minimum cell SOC value for resistance calculation;
129 129  * Maximum SOC – maximum cell SOC value for resistance calculation.
130 130  
131 -The calculated resistance is accepted by the system as valid (and therefore updated) if its value is in the range from Resistance/2 to “Maximum resistance factor” × Resistance, where "Resistance" is the nominal resistance of the cell (see section 2.3.1). If the calculated resistance value is greater than the value (Maximum resistance factor × Resistance), the updated resistance value will be equal to the value (Maximum resistance factor × Resistance).
131 +The calculated resistance is accepted by the system as valid (and therefore updated) if its value is in the range from Resistance/2 to “Maximum resistance factor” × Resistance, where "Resistance" is the nominal resistance of the cell (see [[Common settings>>doc:||anchor="HCommonsettings"]]). If the calculated resistance value is greater than the value (Maximum resistance factor × Resistance), the updated resistance value will be equal to the value (Maximum resistance factor × Resistance).
132 132  
133 133  === Low SOC (signal) ===
134 134  
... ... @@ -570,7 +570,7 @@
570 570  ** Balance on charge or relaxed - balancing is performed while and after the charging and in the relaxed state (in “Charge ON”, “Charge OFF”, “Relaxed (after charging)” and “Relaxed (after discharging)” states);
571 571  ** Balance always – balancing is always performed regardless the battery state;
572 572  
573 -[[image:1733322883462-975.png]]
573 +[[image:1733322883462-975.png||data-xwiki-image-style-alignment="center" data-xwiki-image-style-border="true" height="74" width="600"]]
574 574  
575 575  * Minimum cell voltage to start balancing, V;
576 576  * Voltage deviation to start balancing;
1735054851946-552.png
Author
... ... @@ -1,0 +1,1 @@
1 +XWiki.admin
Size
... ... @@ -1,0 +1,1 @@
1 +22.9 KB
Content