... ... @@ -618,7 +618,7 @@
618 618  A balancing resistor is connected to the cell if the following conditions are simultaneously met:
619 619  
620 620  * the voltage on the cell is higher than the balancing start voltage;
621 -* the difference between the voltage on the cell and the minimum voltage among the battery cells is greater than the balancing start threshold.
621 +* the difference between the voltage on the cell and the minimum voltage among the battery cells is greater than the balancing start threshold;
622 622  
623 623  A balancing resistor is disconnected from the cell if any of the following conditions are met:
624 624  
... ... @@ -629,6 +629,8 @@
629 629  
630 630  The BMS Main 3 can enable the cell balancing by the external “Balancing request” signal. Balancing process will be started to cells which the voltage is higher than the balancing start voltage and the difference between the cell voltage and the minimum voltage among all the cells is greater than the balancing stop threshold.
631 631  
632 +BMS Main 3 can force a cell balancing, if its voltage is higher than estimated value.
633 +
632 632  To change the cell balancing parameters, select the "Control → Cell balancing" section:
633 633  
634 634  [[image:1735065702806-422.png||data-xwiki-image-style-alignment="center" data-xwiki-image-style-border="true" height="130" width="800"]]
... ... @@ -728,7 +728,10 @@
728 728  
729 729  * the minimum temperature among all cells of the battery is greater than the “Tolerant cell temperature” value during the “Delay before stopping the heater” time.
730 730  
733 +(% class="box infomessage" %)
734 +(((
731 731  If there is the "Heater" signal, the heater contactor closes and/or a signal is set to the corresponding digital output.
736 +)))
732 732  
733 733  === Cooler ===
734 734  
... ... @@ -755,7 +755,10 @@
755 755  
756 756  * the maximum temperature among all cells of the battery is less than the “Tolerant cell temperature” value during the “Delay before stopping the cooler” time.
757 757  
763 +(% class="box infomessage" %)
764 +(((
758 758  If there is the "Cooler" signal, the cooler contactor closes and/or a signal is set to the corresponding digital output.
766 +)))
759 759  
760 760  === High voltage ===
761 761