Changes for page 3.3 Control
Last modified by Admin on 2025/04/09 12:14
Summary
-
Page properties (1 modified, 0 added, 0 removed)
Details
- Page properties
-
- Content
-
... ... @@ -503,7 +503,7 @@ 503 503 504 504 When the "**On discharge request**" algorithm selected, the control is performed as follows: 505 505 506 -* if there is signal “Discharge request”, the charging contactor is open and there are no errors (see the "Errors1, 2 ..."bitfields), then through the delay time T,,on,, the discharging contactor closes;506 +* if there is signal “Discharge request”, the charging contactor is open and there are no errors (see the list above), then through the delay time T,,on,, the discharging contactor closes; 507 507 * If the signal “Discharge request” disappears or errors occur (see the "Errors 1, 2 ..." bitfields), then after the delay time T,,off,, the discharging contactor opens. 508 508 509 509 (% class="box infomessage" %) ... ... @@ -511,7 +511,7 @@ 511 511 **Note: **when errors occur in the system, the **Discharge **contactor opens either immediately or with the delay T,,off,, (depends on the settings described below). 512 512 ))) 513 513 514 -The device supports controlling the precharging contactor (see[[Precharge>>doc:||anchor="HPrecharge"]]).514 +The device supports controlling the precharging contactor. The duration of switching on the precharging contactor before closing the discharging (load) contactor is adjusted. 515 515 516 516 To change the parameters of the battery discharge control algorithm, select the "Control → Discharge" section: 517 517