... ... @@ -503,7 +503,7 @@
503 503  
504 504  When the "**On discharge request**" algorithm selected, the control is performed as follows:
505 505  
506 -* if there is signal “Discharge request”, the charging contactor is open and there are no errors (see the list above), then through the delay time T,,on,, the discharging contactor closes;
506 +* if there is signal “Discharge request”, the charging contactor is open and there are no errors (see the "Errors 1, 2 ..." bitfields), then through the delay time T,,on,, the discharging contactor closes;
507 507  * If the signal “Discharge request” disappears or errors occur (see the "Errors 1, 2 ..." bitfields), then after the delay time T,,off,, the discharging contactor opens.
508 508  
509 509  (% class="box infomessage" %)
... ... @@ -511,7 +511,7 @@
511 511  **Note: **when errors occur in the system, the **Discharge **contactor opens either immediately or with the delay T,,off,, (depends on the settings described below).
512 512  )))
513 513  
514 -The device supports controlling the precharging contactor. The duration of switching on the precharging contactor before closing the discharging (load) contactor is adjusted.
514 +The device supports controlling the precharging contactor (see [[Precharge>>doc:||anchor="HPrecharge"]]).
515 515  
516 516  To change the parameters of the battery discharge control algorithm, select the "Control → Discharge" section:
517 517  
... ... @@ -580,7 +580,7 @@
580 580  
581 581  * the battery has low SOC;
582 582  * the battery voltage is out of range;
583 -* the battery system errors are detected.
583 +* the errors are detected (configured in the "Errors 1, 2 ..." bitfields).
584 584  
585 585  (% class="box infomessage" %)
586 586  (((
... ... @@ -728,7 +728,7 @@
728 728  
729 729  * the minimum temperature among all cells of the battery is greater than the “Tolerant cell temperature” value during the “Delay before stopping the heater” time.
730 730  
731 -If there is the "Heater" signal, the heater contactor closes and/or a signal is output to the corresponding digital output.
731 +If there is the "Heater" signal, the heater contactor closes and/or a signal is set to the corresponding digital output.
732 732  
733 733  === Cooler ===
734 734  
... ... @@ -755,7 +755,7 @@
755 755  
756 756  * the maximum temperature among all cells of the battery is less than the “Tolerant cell temperature” value during the “Delay before stopping the cooler” time.
757 757  
758 -If there is the "Cooler" signal, the cooler contactor closes and/or a signal is output to the corresponding digital output.
758 +If there is the "Cooler" signal, the cooler contactor closes and/or a signal is set to the corresponding digital output.
759 759  
760 760  === High voltage ===